Solmetric White Paper: Winning Contracts with PV Array Testing

Similar documents
New Tools for PV Array Commissioning and Troubleshooting

New Tools for PV Array Commissioning and Troubleshooting

New Tools for PV Array Commissioning and Troubleshooting

Solmetric PVA-600 PV Analyzer

PV Array Commissioning and Troubleshooting with the Solmetric PV Analyzer

Introducing the Solmetric PV Analyzer and the New Features of v2.0 PVA Software

PV Array Commissioning and Troubleshooting. Solmetric PV Analyzer

For more information:

Commissioning and Troubleshooting PV Arrays. Solmetric PV Analyzer

Advanced Test Equipment Rentals

Field Applications. for I-V Curve Tracers. Silicon PV modules are. By Paul Hernday. I-V Curve Measurements

Upsolar Smart Modules

Peter Hoberg VP Marketing

Understanding Temperature Effects on Crystalline PV Modules

PV210. Why buy the PV210?

Solmetric PVA-1000S Startup Training

Analysis and Reporting of I-V Curve Data from Large PV Arrays

Laboratory 2: PV Module Current-Voltage Measurements

PV200. Why buy the PV200? The most compact I-V curve tracer around.

Solmetric PV Analyzer

Test Report. File No.: SHV04007/15-02 Test Report No.: , P.R. China

Optional Features. Linear Performance Warranty 10 Years product warranty 25 Years linear performance warranty

[Note to PSC: Include these sections in the Contract Documents, even though some are not included in the U of I Facilities Standards]

How to Evaluate PV Project Energy Yield

Photovoltaic System Commissioning and Testing A Guide for PV System Technicians and Engineers

CHAPTER 4 PERFORMANCE ANALYSIS OF DERIVED SPV ARRAY CONFIGURATIONS UNDER PARTIAL SHADED CONDITIONS

Test Report. File No.: SHV01023/16 Test Report No.: Taizhou, Zhejiang , P.R. China

MC Solarline 2 MC4 pin crimper for 10/12 AWG wire MC Solarline 2 open-end spanner set (2-pack)

Traditional PWM vs Morningstar s TrakStar MPPT Technology

Leading the World in PV Test Solutions

APS M1P Single-phase Micro-inverter Installation and User Manual

Dr E. Kaplani. Mechanical Engineering Dept. T.E.I. of Patras, Greece

PART I: DEPARTMENT AND VENDOR INFORMATION

60 cell LG300N1K-G4. Key Features. High Power Output. Enhanced Performance Warranty. Outstanding Durability. Aesthetic Roof

Evaluating the Effectiveness of Maximum Power Point Tracking Methods in Photovoltaic Power Systems using Array Performance Models

PV Charger System Using A Synchronous Buck Converter

PROCUREMENT OF GOODS UNDER OPEN TENDER PROCEDURE

Heat Exchanger Construction Checklist

Application Note: String sizing Conext CL Series

Engineering Thesis Project. By Evgeniya Polyanskaya. Supervisor: Greg Crebbin

INSTRUCTION MANUAL. I-V Curve Checker MP-11. Software Version Number: Firmware Version Number: Manual Version Number: 4

Your Origin SLIVER system will be supplied with one of the following sets of panels:

Power Rating of Photovoltaic Modules Using a. New Outdoor Method. Meena Gupta Vemula

Test Report. File No.: SHV01032/18-02 Test Report No.:

Type EN180-MS EN185-MS EN190-MS EN195-MS EN200-MS 13.5 A. Container Capacity Multiple Packing 40 feet (GP) 700 pcs / 28 pallets

Growatt 2000TL. Input Data Max. DC power Max. DC voltage. PV voltage range MPPT. Full load MPP-Voltage range

Guelbenzu Ingeteam Power Roberto González

Array. Source-circuit configuration is arguably the most

APS M1P Single-phase Micro-inverter Installation and User Manual

CP /240-MC4 User Manual

Understanding Potential Induced Degradation for LG NeON Model

APPENDIX V PRODUCT SHEETS

DC Current Transducers

Agenda. 1. Inverter technology. 2. Monitor system. 3. System application. 4. Error Codes and trouble-shooting

TUV Rheinland (India) Pvt. Ltd. Product Safety & Quality. Test Report

Presented in Electrical & Computer Engineering University of New Brunswick Fredericton, NB, Canada The Photovoltaic Cell

Comparative Study of P&O and InC MPPT Algorithms

Secure your solar investment. inside. 1OO % transparency = 1OO % performance.

TOSHIBA International Corp

Quality criteria and certificates

BETTER DESIGN BETTER MATERIALS BETTER PROCESSES BETTER MODULES

Large Area Steady State Solar Simulator - Apollo

Est Static Frequency Converter. SFX 10kVA - 10MVA

FSEC APPROVAL # XL15-NT

Defense Microelectronics Activity (DMEA) Advanced Technology Support Program IV (ATSP4) Organizational Perspective and Technical Requirements

SOLARONIX. Solixon A-1525-V

1. Executive Summary. 2. Introduction. Selection of a DC Solar PV Arc Fault Detector

FJB/IFB enclosures Photovoltaic string protection and monitoring enclosures for solar parks from 8 to 32 strings

Solar Simulation Standards and QuickSun Measurement System. Antti Tolvanen Endeas Oy

Failure and Degradation Modes of PV modules in a Hot Dry Climate: Results after 4 and 12 years of field exposure. Jaya Krishna Mallineni

SECTION CLOSEOUT SUBMITTALS SECTION CLOSEOUT SUBMITTALS

PV Activity 3 PV Loads

Impact of Spectral Irradiance on Energy Yield of PV Modules Measured in Different Climates

Proposed test procedure for the laboratory characterisation of gridconnected

Photovoltaic / Solar Array Simulation Solution

OUTDOOR PV MODULE DEGRADATION OF CURRENT-VOLTAGE PARAMETERS

Performance of high-eciency photovoltaic systems in a maritime climate

PSPICE Simulation For A Solar Panel To Understand Shading Effects

Tools for field testing

Performance Loss of PV systems. Giorgio Belluardo

CHAPTER 5 MPPT OF PV MODULE BY CONVENTIONAL METHODS

DS-1000 I-V CURVE TRACER User Manual

Bifacial Outdoor Rotor Tester- BIFROT

An Interleaved High-Power Fly back Inverter for Photovoltaic Applications

COOPER POWER SERIES. Upgrade instructions for CL-6 series control firmware. Voltage Regulators MN225071EN

Traditional PWM vs. Morningstar s TrakStar MPPT Technology

KNX PY. Global Irradiance Sensor. Installation and Adjustment

The Nanosolar Utility Panel An Overview of the Solar Panel and its Advantages. May 2010

High Power Programmable DC Power Supplies PVS Series

Elgar ETS TerraSAS. 1kW-1MW V. Standalone TerraSAS Photovoltaic Simulator

Fiscal 2007 Environmental Technology Verification Pilot Program Implementation Guidelines

Aqua-Gen 3PV INSTRUCTIONS

Potential Induced degradation

CHAPTER-3 Design Aspects of DC-DC Boost Converter in Solar PV System by MPPT Algorithm

Fault Evolution in Photovoltaic Array During Night-to-Day Transition

SoP for I-V System. Part - 1 SUN 3000 SOLAR SIMULATOR. ABET Technologies

G7K. Latching Relay. Compact Mechanical Lock Latching Relays with Manual Buttons. Model Number Structure. Ordering Information

CONVEYANCE PIPELINE AND PUMP STATION

SINAMICS drives. SINAMICS DCM as a DC voltage source. Application. Answers for industry. Edition 01/2014

Photovoltaic Systems I EE 446/646

Transcription:

Solmetric White Paper: Winning Contracts with PV Array Testing Contents Introduction...1 Background: I-V Curves in Field Applications...2 What is an I-V curve?...2 Where has I-V curve tracing been used in the PV industry?...2 What accounts for the increasing popularity of I-V curve tracing for field testing?...2 What are the benefits of I-V curve tracing?...3 Why is the Solmetric PV Analyzer (PVA) the best choice for measuring I-V curves?...4 Proposal/Contract Language for Array Commissioning...4 Introduction This white paper is intended for solar PV project developers, EPC s, operation & maintenance companies and other solar service providers who want to win more business by promoting their use of best practices. Advanced I-V curve tracing measurement tools can be turned to your competitive advantage during the sales phase of new PV systems and O&M contracts. This paper helps you realize this advantage by providing language that you can conveniently re-use in your proposals. By specifying measurements made with the Solmetric PV Analyzer, you are demonstrating your commitment to quality and performance. PVA measurements during the commissioning process will ensure quality and reduce risk for the developers, EPC s, investors and solar service providers. This white paper contains two main parts: 1. Background. This section contains background about I-V curves and commissioning in FAQ format. It is a summary of key technical and business drivers for measuring I-V curves in field applications. Further information can be found at www.solmetric.com. 2. Proposal/Contract Language. This section contains wording about the specific procedures, measurement results, and documentation requirements for the I-V curve measurements. This language can be adapted for or included in any of the following: a. Request for Information (RFI) b. Requests for Proposal (RFP) c. Proposal d. Statement of Work (SOW) e. Contractual Agreement

Background: I-V Curves in Field Applications What is an I-V curve? The output power of a PV array depends on the voltage at which it is operated. For a given type of PV module, there will be a particular operating point that delivers the highest output. It is the job of the inverter to find that point and to track it as environmental conditions change. The I-V curve is just a collection or path of possible operating points, represented as a curved line on a graph of output voltage versus current. The curve starts at the short circuit current and ends at the open circuit voltage. The maximum power point is located at the knee of the curve. Figure 1 I-V and P-V curves for a PV module or string, showing key parameters Where has I-V curve tracing been used in the PV industry? I-V curve tracing has been used for decades in PV R&D, manufacturing, and field testing. It is the most comprehensive measurement that can be performed on a PV module, string or array. What accounts for the increasing popularity of I-V curve tracing for field testing? In the past year, the availability of affordable, compact, rugged, easy to use curve tracers has changed the game in PV system testing. The Solmetric PV Analyzer also allows the user to compare the measured I-V curve with the predictions of built-in PV models, giving immediate indication of the health of the array. Automated data analysis tools make quick work of digesting and displaying the test results for even very large multi-megawatt PV projects.

What are the benefits of I-V curve tracing? Reduced test time I-V curve tracing measures multiple performance parameters with a single electrical connection and a single measurement step. The curve tracer is connected to the output terminals of the combiner box, after isolating the combiner from the rest of the PV system. Inserting one PV fuse at a time allows testing individual strings. Data recording is automated and the entire process typically takes less than 15 seconds per string. No need to bring the inverter on-line to test PV string performance Traditional test methods required the inverter to be brought on-line in order to measure PV string performance under load. I-V curve tracing eliminates this requirement by measuring the performance of each PV string under all load conditions. This means you can test the array much earlier in the project, avoiding the long wait to bring the inverter on-line. Reduced start-up and commissioning risk Testing the array before the inverter is brought on-line means less risk of array-side problems showing up during start-up or commissioning. More detailed measurement results I-V curve tracing is the most comprehensive test possible for PV arrays. In addition to measuring the traditional parameters such as short circuit current and open circuit voltage, it uniquely measures the maximum power point of each string. And the shape of the measured I-V curve gives important troubleshooting information. Automated data recording and analysis I-V curve measurement data is digitally recorded, eliminating data recording errors. The Solmetric I-V Data Analysis tool automatically produces three displays of array performance, making it easy to visually demonstrate that PV strings are performing consistently and in line with expectations. If performance problems are present, the tool quickly draws attention to them and identifies the problem strings. Detailed performance baseline PV arrays are extremely robust and reliable, but they do degrade gradually with time. Occasionally a module will fail. I-V curve tracing gives you a detailed baseline against which to compare measurements over the life cycle of the PV system. Module degradation and failures are easily demonstrated, facilitating module warranty claims. Taken as a whole, these advantages reduce the costs and risks associated with PV system construction and testing, and provide a baseline for ongoing maintenance.

Why is the Solmetric PV Analyzer (PVA) the best choice for measuring I-V curves? The Solmetric PV Analyzer combines an affordable, compact, fast and easy-to-use I-V curve measurement tool with built-in PV performance modeling, allowing users to immediately determine whether a PV module or string is performing to its potential. If it is not, the I-V curve provides critical information about potential causes of the performance problem. Advanced data analysis tools make fast work of analyzing data and providing exhibits to communicate test results to system stakeholders. And if it is ever needed, responsive tech and application support is at your service. The Solmetric PV Analyzer is also specifically designed to accurately measure high-efficiency PV modules, which require more time for electrical charge to properly transition as the I-V load curve is being traced. Proposal/Contract Language for Array Commissioning PV Array Commissioning Tests - Before Substantial Completion String I-V Curve Trace tests shall be performed in accordance with procedures detailed in this section, and test data shall be recorded, prior to commissioning of the Generating Facility. String I-V Curve Test Purpose: I-V curve tracing is the most comprehensive measurement that can be performed on PV modules, strings and arrays. Using a single electrical connection and a single test, I-V curve tracing measures the Open Circuit Voltage, Short Circuit Current, Max Power Voltage, Max Power Current, Maximum Power and Fill Factor of the selected PV string. The detailed shape of the I-V curve gives insight into the causes of any performance issues. Scope: All strings Party: EPC technical personnel or contracted testing service Schedule: During Commissioning Equipment/ Materials: Rubber insulating gloves and other PPE Fuse puller I-V Curve Tracer such as Solmetric PVA-600 or Daystar DS-100 Test leads

Procedure: Follow the manufacturer's procedures for use of the I-V curve tracer. Shut down the inverter. Locate the combiner box at which string I-V curves will be measured. Electrically isolate the combiner box from other PV array segments by opening its DC disconnect switch. Electrically isolate the combiner box buss bars from PV source circuits by lifting all of the string fuses. Connect the curve tracer to the buss bars (be aware of array and instrument polarities). Measure the I-V curve. Sweep the load such that it operates the array over its entire range from Isc to Voc (or as the load will allow). Record voltage and current readings for at least 10 steps in the curve (100 points is preferred). For each I-V curve, measure and record the irradiance in the plane of the array, the temperature on the backside of a typical PV module, and the date and time. Measure the irradiance and temperature values within 10 seconds of the I-V curve measurement. The I-V curve should be measured in less than 1s so that rapid irradiance and module backside temperature changes have minimal effect on the shape of the curve Also record the ambient temperature. Conditions: This test will be conducted under full sun with irradiance of at least 500 W/m2 and stable sky conditions (no cirrus clouds or fast moving clouds near sun) within the time period of four hours centered about solar noon. Solar noon can be determined using reference tools such as: http://www.esrl.noaa.gov/gmd/grad/solcalc/ If such conditions are not available due to weather conditions, then the Engineering Procurement and Construction (EPC) Provider or testing service shall not conduct such test until the earlier of the date on which such conditions exist and 5 business days following the date on which the test would otherwise have been conducted. If, upon the expiration of the foregoing period, such conditions are still not available, then the test will be conducted within 5 more days. In this case any anomalous data apparently due to changing sky conditions shall be re-measured under stable sky conditions. Criteria: Open Circuit Voltage Verify that the string Open Circuit Voltage is within 5% of expected values as determined from module manufacturer s data sheet (Voc at STC and temperature coefficient of Voc) and measured module temperature. Under stable irradiance and temperature conditions, the Open Circuit Voltage for each string should conform to within 2% of the average Open Circuit Voltage of all the strings in the same combiner box.

Short Circuit Current Under sky conditions of 500 W/m2 or greater, the measured current should be within 5% of the expected Isc calculated using equation below: Isc_expected = 0.95 n Isc_ref G/Gref Where: 0.95 = factor to account for soiling, misalignment, and other factors. n = number of modules or strings tested in parallel Isc_expected = expected short-circuit current of the test segment Isc_ref = module short-circuit current at some specified reference conditions (typically STC) G = measured plane of array irradiance, W/m2 Gref = irradiance at specified reference conditions for Isc_ref, W/m2 Under stable irradiance and temperature conditions, the Short Circuit Current for each string should conform to within 2% of the average Short Circuit Current of all strings in the same combiner box. Maximum Power Compare the measured Maximum Power value to the predictions of an advanced PV model such as the Sandia PV Array Model or 5-Parameter Model. If advanced models are not available, use a simple model based on values provided by the module manufacturer s data sheet. The Max Power of each string should be within 5% of the modeled Max Power. Under stable irradiance and temperature conditions, the measured Max Power value of each string should conform to within 2% of the average Max Power of all strings in the same combiner box. Comments: If results show anomalies, including fill factor, voltages, or currents outside expected limits, or anomalies on the I-V curve, then modules should be investigated for bypass diode conduction, out-of-tolerance module performance, or other possible problems. Any flaws must be rectified and any modified strings should be re-tested.