Shunt Reactor Switching

Similar documents
DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

Insulation Co-ordination For HVDC Station

Tab 2 Voltage Stresses Switching Transients

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

This is a preview - click here to buy the full publication

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

2. Current interruption transients

High-Power Testing of Circuit Breakers

High voltage engineering

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

FACTORY AND FIELD VERIFICATION TESTS OF CONTROLLED SWITCHING SYSTEM

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

Electric Stresses on Surge Arrester Insulation under Standard and

Potential Risk of Failures in Switching EHV Shunt Reactors in Some One-and-a-half Breaker Scheme Substations

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

(2) New Standard IEEE P (3) Core : (4) Windings :

In power system, transients have bad impact on its

DC current interruption tests with HV mechanical DC circuit breaker

Modelling of Restriking and Reignition Phenomena in Three-phase Capacitor and Shunt Reactor Switching

5. Black box arc modelling

Modeling insulation in high-voltage substations

SYSTEM STUDIES for HVDC

SIMPLE SOLUTIONS FOR IMPROVING LIFE OF BREAKERS USED IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad

Transient recovery voltage analysis for various current breaking mathematical models: shunt reactor and capacitor bank de-energization study

HIGH VOLTAGE CIRCUIT BREAKERS

EE 1402 HIGH VOLTAGE ENGINEERING

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET

Medium voltage circuit breaker technical guide

Power Quality and Reliablity Centre

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

POWER SYSTEM TRANSIENTS - Switching Overvoltages in Power Systems - Juan A. Martinez-Velasco, Jacinto Martin-Arnedo

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker. ABB Group May 11, 2016 Slide 1

CONTENTS. 1. Introduction Generating Stations 9 40

GUIDE FOR APPLICATION OF IEC AND IEC

AC High-Voltage Circuit Breakers

Simulation of switching overvoltages of 400 kv shunt reactor. Shunt reactor grounded through a neutral reactor in 400/132 kv highvoltage

Error vs. Uncertainty Historical Perspective

Power and Instrument Transformer Failures Root Causes and Modern Methods Used to Mitigate Risk. IEEE-NCS,IAS/PES (March 2017)

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Cahier technique no. 101

Abstract. 1 Introduction

DEVELOPMENTS IN EHV/UHV CIRCUIT BREAKER TESTING

TRV OVERVIEW FOR REACTANCE LIMITED FAULTS

Revision of TRV Requirements for the Application of Generator Circuit-Breakers

Surge Protection for Ladle Melt Furnaces

GIS Disconnector Switching Operation VFTO Study

INTERNATIONAL STANDARD

A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks

Tab 8 Surge Arresters

Real Time Monitoring of SF6 Gas Pressure for Optimization Point on Wave Switching of SF6 Circuit Breaker

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Roadmap For Power Quality Standards Development

DC VACUUM CIRCUIT BREAKER

OCCURRENCE OF DELAYED CURRENT ZERO CROSSING DUE TO LINE REACTIVE OVERCOMPENSATION LT CAMPINAS FERNAO DIAS 500 kv.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Although shunt capacitors

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

CURRENT interrupting tests constitute an important part. Medium Voltage Laboratory for Load Break Switch Development. Erik Jonsson and Magne Runde

Fixed Series Compensation

Recent Improvements in K-Factor Models dl

Cahier technique no. 193

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Do Capacitor Switching Transients Still Cause Problems?

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

AORC Technical meeting 2014

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

Great Northern Transmission Line: Behind the (Electrical) Design

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

System Protection and Control Subcommittee

Grounding System Theory and Practice

Effects of Transient Recovery Voltages on Circuit Breaker Ratings

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

INTERNATIONAL STANDARD

Upgrading Your Electrical Distribution System To Resistance Grounding

Transients under energizing multiple power filter circuits

Conventional Paper-II-2011 Part-1A

Impact Assessment Generator Form

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Are snubbers required with Eaton s Cooper Power series liquid-filled hardened transformers?

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

TECHNICAL REPORT. Insulation co-ordination

Transformers connected via a cable Overvoltage protection

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER

Chip Varistor LVS B DESCRIPTION APPLICATIONS FEATURES ORDERING INFORMATION. Capacitance 030 = 3pF 300 = 30pF 301 = 300pF

THREE-PHASE SHORT-CIRCUIT TESTING OF HIGH-VOLTAGE CIRCUIT-BREAKERS USING SYNTHETIC CIRCUITS

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

Transcription:

Shunt Reactor Switching Dielectric stresses produced by circuit-breakers to shunt reactors. Presentation made during the IEEE Transformers Committee meeting, Amsterdam, Netherlands, April 2001 Presented by: Pierre Riffon P. Eng. Hydro-Québec Test Specialist Quality Control Department 01/04/11 1

Circuit-breaker testing 1- Circuit- breaker tests for shunt reactor switching are covered by the following guides : A- Technical Report IEC 1233, 1994 "High-voltage alternating current circuit-breaker - Inductive load switching". B- IEEE Std. C37.015-1993 "IEEE Application Guide for Shunt Reactor Switching". These two documents are technically identical since they are the result of a cooperative effort between a WG of the IEEE High Voltage Circuit-breaker Subcommittee and a Task Force of the IEC Technical Committee SC17A. 2

Circuit-breaker testing 2- Purpose of the circuit-breaker tests a) To determine the interrupting window without reignition. b) To determine the current chopping characteristics of the circuit-breaker. c) To determine the worst probable overvoltage that could appear across the reactor and across the circuit-breaker. 3

4

5

Circuit-breaker testing Tests results: 1- Re-ignition performance vs arcing time ; 2- Chopping number (overvoltage) vs arcing time ; 3- Re-ignition voltage vs arcing time. 6

Graph no.1; I = 250 A; Minimum gas pressure Withstand / Re-ignition 0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 Prospective arcing time (ms) 7

Graph no.2: I = 250 A; Minimum gas pressure 1,40E+05 1,20E+05 1,00E+05 Chopping number 8,00E+04 6,00E+04 4,00E+04 2,00E+04 0,00E+00 0 2 4 6 8 10 12 Arcing time (ms) 8

Graph no. 3: I = 250 A; Minimum gas pressure 250,0 Reignition voltage (kv peak) 200,0 150,0 100,0 50,0 0,0 0,0 1,0 2,0 3,0 4,0 5,0 Prospective arcing time (ms) 9

Important aspect : Shunt reactor switching is a daily event (in some cases, shunt reactors may be switched on and off several times during the same day) 10

1- Ideal case, no re-ignition and no current chopping - Type of stresses: Switching surge type of waveshape (damped oscillatory overvoltage). Could be close to lightning impulse waveshape for dry-type reactors. 11

- Frequency : Dielectric stresses imposed 1- Ideal case, no re-ignition and no current chopping f transient = 2π 1 LC L Typical frequencies : - 1,0 to 41 khz for oil-immersed reactor (stray capacitance 0,8 to 4 nf); - >100 khz for dry-type shunt reactors (stray capacitance 100 to 500 pf) 12

REACTOR CURRENT -10-30 Current (p.u.) -50-70 -90-110 -130-150 0,075 0,076 0,077 0,078 0,079 0,08 0,081 0,082 0,083 0,084 0,085 Time (s) REACTOR VOLTAGE Voltage (V) 700000 600000 500000 400000 300000 200000 100000 0-100000,075 0,076 0,077 0,078 0,079 0,08 0,081 0,082 0,083 0,084 0,085-200000 -300000-400000 -500000-600000 -700000 Time (s) IDEAL CASE 13

1- Ideal case, no re-ignition and no current chopping - Reactor transient voltage amplitude (grounded neutral): U peak = 2 U n 3 This transient voltage is not severe since it is the phase to ground peak voltage. 14

1- Ideal case, no re-ignition and no current chopping (continued) Ideal circuit-breakers do not exist, some are more sensitive to re-ignitions while others may chopped considerably the current. 15

2- Real case, no re-ignition and current chopping Current chopping is circuit-breaker dependent. For example : - For air-blast circuit-breakers : Typical chopping number : 15-25 x 10 4 ; -For SF 6 circuit-breakers : Typical chopping number : 4-17 x 10 4 ; - For minimum oil circuit-breakers : Typical chopping number : 7-10 x 10 4 ; 16

on shunt reactors: 2- Real case, no re-ignition and current chopping (continued) Where: Chopping number (λ) = i ch / C t i ch = Copping current; C t = Total capacitance seen by the circuit-breaker (stray capacitance on the shunt reactor + parallel capacitance across the circuit-breaker pole). Chopping results in an overvoltage across the shunt reactor and across the circuit-breaker. 17

18

on shunt reactors: 2- Real case, no re-ignition and current chopping (continued) The trapped energy in the reactor at the instant of current chopping (½ x L (i ch ) 2 ) has to be transferred to the parallel capacitance. Thus, ½ x L x (i ch ) 2 = ½ x C T x ( V) 2 Where " V" is the overvoltage produced by current chopping. 19

2- Real case, no re-ignition and current chopping (continued) For a given shunt reactor "L", the overvoltage produced is proportional to the current chopped. Moreover, a reactor with a large stray capacitance (e.g. oil-immersed) will be less affected by the current chopping (larger C T ). And, V = i ch x (L/C T ) 20

2- Real case, no re-ignition and current chopping (continued) The amplitude of the current chopping is proportional to the arcing time of the circuit breaker. For a longer arcing time, the "interrupting strength" of the circuit-breaker is larger and the breaker can chop more current. 21

2- Real case, no re-ignition and current chopping (continued) - Type of stresses: Switching surge type of waveshape (damped oscillatory overvoltage). Could be close to lightning impulse waveshape for dry-type reactors. - Frequency : f transient 1 = 2π LC L 22

2- Real case, no re-ignition and current chopping (continued) Typical frequencies: - 1,0 to 41 khz for oil-immersed reactors (stray capacitance 0,8 to 4 nf); - >100 khz for dry-type shunt reactors (stray capacitance 100 to 500 pf) ; 23

2- Real case, no re-ignition and current chopping (continued) - Reactor transient amplitude (grounded neutral): U peak U = k 2 a n 3 Where: k a : Overshoot factor due to current chopping 24

2- Real case, no re-ignition and current chopping (continued) This transient voltage can be severe depending of the circuitbreaker chopping characteristics and on the shunt reactor value and its stray capacitance. The Hydro-Québec's technical approach on this problem consists, for each specific case, to evaluate the worst probable overvoltage that will be imposed on a specific combination "reactor-circuit-breaker". 25

2- Real case, no re-ignition and current chopping (continued) The test results (chopping number vs arcing time) are evaluated and an equation of the chopping number vs arcing time is derived from the test results (linear regression of the results obtained). Since this has also a statistical behavior (that it is why a large number of tests are required), the worst probable overvoltage is calculated considering the longest possible arcing time (t arc max. ) without re-ignition (i.e. 8,3 ms for 60 Hz application) and by using "3 x S e " (99,9% of the cases) where "S e " is the "standard error of estimate". 26

on shunt reactors: 2- Real case, no re-ignition and current chopping (continued) The equations used are: and λ max = λ o + B x t arc max. + 3 x S e N k = a 1 + 3 λ 2 ω Q 2 max W here: N : N u m b e r o f in te rru p tin g u n its in s e rie s ; λ m a x : W orst probable chopping num ber derived from test result analysis; ω : 2 x π x f; Q : Three-phase reactive power of the shunt reactor; B and λ 0 : E q u a tio n c o n s ta n ts. 27

2- Real case, no re-ignition and current chopping (continued) and U peak U = k 2 a n 3 Note: IEC technical report and IEEE guide suggest to use "2 x S e " (97,7% of the cases). W ithin Hydro-Québec, shunt reactors are norm ally used on 800 kv system s (directly connected) and the m argin between the protective level of the surge arrester and the S IW L of the reactor is m uch low er than for low er system voltages. Because 800 kv shunt reactors are strategic equipm ent and because of their replacem ent cost, a "3 x S e " criteria is u s e d. 28

2- Real case, no re-ignition and current chopping (continued) As a typical example, a 800 kv SF 6 puffer type circuit-breaker used to switch a 330 MVA r reactor (3 single phase units rated 110 MVA r ) may produced overvoltages "k a " in the range of 1,32 p.u. The same circuit-breaker used to switch a 165 MVA r reactor (3 single phase units rated 55 MVA r ) may produced overvoltages "k a " in the range of 1,55 p.u. 29

2- Real case, no re-ignition and current chopping (continued) For extra-high voltage applications (550 kv and 800 kv), because of the low margin between the SIPL and SIWL (typically 25%) and because that reactor switching is a daily event, we do recommend that the calculated overvoltage peak to be less than 0,68 x SIWL (0,8 (ageing) x 0,85 (margin) = 0,68). For these cases, the arrester can not give a proper protection, mainly if we consider a certain dielectric strength reduction of the reactor due to ageing. 30

2- Real case, no re-ignition and current chopping (continued) For high-voltage (< 362 kv) and for medium voltage applications, the SIPL of the shunt reactor surge arrester is relatively low and the margin between the SIPL and the SIWL is larger than 32%. For these cases, the parallel surge arrester is normally giving a proper shunt reactor switching overvoltage protection even for aged shunt reactors. 31

3- Real case, re-ignition and current chopping Re-ignition of a circuit-breaker occurs when the TRV applied to the circuit-breaker is higher than the "dynamic" voltage withstand capability of the circuit-breaker during an opening operation. Re-ignition occurs normally with small arcing times. For high voltage SF 6 circuit-breakers, it is typical that arcing times lower than 4 ms lead to re-ignitions. 32

3- Real case, re-ignition and current chopping (continued) Type of stresses: Fast transient type of waveshape (damped oscillatory overvoltage, lightning impulse or chopped wave). - Frequency : W here: f transient 1 = 2π C + C L s L C C B L s L B : Inductance of the re-ignition circuit (between the source side capacitor and the shunt reactor). C S : Source side capacitance; C L : Load side capacitance. 33

34

3- Real case, re-ignition and current chopping (continued) Typical frequencies: - From 50 khz to 1,0 MHz. This frequency is mainly dependent of the stray capacitance of the shunt reactor (C S >>> C L ) and the length of re-ignition circuit (L B ) between the source side capacitance and the shunt reactor. 35

on shunt reactors: 3- Real case, re-ignition and current chopping (continued) - Reactor transient voltage amplitude (grounded neutral) : a) Before the re-ignition, worst case : U U = ka 2 peak to ground n 3 (same as for current chopping case) 36

3- Real case, re-ignition and current chopping (continued) b) After re-ignition, worst case (re-ignition at the peak of the recovery voltage): U C S U k k = ( 1+ β) ( 1+ a ) a 2 C C S L peak to ground n 3 W here: β : Dam ping factor of the re-ignition transient, norm ally β 0,5; k a : Suppression peak overvoltage caused by current chopping; C S : Source side capacitance; C L : Load side capacitance. And generally, C S >>> C L 37

38

3- Real case, re-ignition and current chopping (continued) As for the case of current chopping, for high voltage and medium voltage shunt reactors ( 345 kv), the surge arrester will protect adequately the reactor against the maximum phase-to-ground peak voltage. Nevertheless, for extra high voltage shunt reactors (500 and 765 kv), the arrester may not adequately protect the reactor if we consider this type of stress as a daily event (margin of 20% for ageing and 15 % on the LIWL, 0,68 p.u. of the LIWL). 39

3- Real case, re-ignition and current chopping (continued) The phase-to-ground overvoltage produced by a re-ignition is not the worst dielectric stress generated during this event. The dv/dt applied to the shunt reactor during a re-ignition can be extremely severe and the surge arrester connected across the shunt reactor will not protect it. 40

D i e l e c r i c s t r e s s e s o n s h u n t r e a c t o r s d u r i n g r e - i g n i t i o n s N o m in a l s y s t e m v o lt a g e B I L C h o p p e d w a v e L IP L (2,5 x p h a s e - t o - g r o u n d v o lt a g e p e a k ) 2 x L I P L (u ltim a te m a x im u m d v /d t d u rin g r e - ig n it io n ) d v /d t s t r e s s e s (% o f th e c h o p p e d w a v e le v e l) (k V ) (k V ) (k V ) (k V ) (k V ) (% ) P h a s e - t o - g r o u n d o v e r v o lt a g e (% o f th e L I W L ) * 1 5 1 1 0 1 2 0 3 0, 6 6 1, 2 5 1, 0 2 3, 9 2 5 1 5 0 1 6 5 5 1, 0 1 0 2, 1 6 1, 9 2 9, 3 3 4, 5 2 0 0 2 2 0 7 0, 4 1 4 0, 8 6 4, 0 3 0, 3 4 5 2 5 0 2 7 5 9 1, 9 1 8 3, 7 6 6, 8 3 1, 6 6 9 2 5 0 2 7 5 1 4 0, 8 2 8 1, 7 1 0 2, 4 4 8, 5 6 9 3 5 0 3 8 5 1 4 0, 8 2 8 1, 7 7 3, 2 3 4, 6 1 1 5 3 5 0 3 8 5 2 3 4, 7 4 6 9, 5 1 2 1, 9 5 7, 7 1 1 5 4 5 0 4 9 5 2 3 4, 7 4 6 9, 5 9 4, 8 4 4, 9 1 1 5 5 5 0 6 0 5 2 3 4, 7 4 6 9, 5 7 7, 6 3 6, 7 1 3 8 4 5 0 4 9 5 2 8 1, 7 5 6 3, 4 1 1 3, 8 5 3, 8 1 3 8 5 5 0 6 0 5 2 8 1, 7 5 6 3, 4 9 3, 1 4 4, 0 1 3 8 6 5 0 7 1 5 2 8 1, 7 5 6 3, 4 7 8, 8 3 7, 3 1 6 1 5 5 0 6 0 5 3 2 8, 6 6 5 7, 3 1 0 8, 6 5 1, 4 1 6 1 6 5 0 7 1 5 3 2 8, 6 6 5 7, 3 9 1, 9 4 3, 5 1 6 1 7 5 0 8 2 5 3 2 8, 6 6 5 7, 3 7 9, 7 3 7, 7 2 3 0 6 5 0 7 1 5 4 6 9, 5 9 3 9, 0 1 3 1, 3 6 2, 1 2 3 0 7 5 0 8 2 5 4 6 9, 5 9 3 9, 0 1 1 3, 8 5 3, 8 2 3 0 8 2 5 9 0 5 4 6 9, 5 9 3 9, 0 1 0 3, 8 4 8, 9 2 3 0 9 0 0 9 9 0 4 6 9, 5 9 3 9, 0 9 4, 8 4 4, 9 3 4 5 9 0 0 9 9 0 7 0 4, 2 1 4 0 8, 5 1 4 2, 3 6 7, 3 3 4 5 1 0 5 0 1 1 5 5 7 0 4, 2 1 4 0 8, 5 1 2 1, 9 5 7, 7 3 4 5 1 1 7 5 1 2 9 0 7 0 4, 2 1 4 0 8, 5 1 0 9, 2 5 1, 5 5 0 0 1 3 0 0 1 4 3 0 1 0 2 0, 6 2 0 4 1, 2 1 4 2, 7 6 7, 5 5 0 0 1 4 2 5 1 5 7 0 1 0 2 0, 6 2 0 4 1, 2 1 3 0, 0 6 1, 6 5 0 0 1 5 5 0 1 7 0 5 1 0 2 0, 6 2 0 4 1, 2 1 1 9, 7 5 6, 6 5 0 0 1 6 7 5 1 8 4 5 1 0 2 0, 6 2 0 4 1, 2 1 1 0, 6 5 2, 4 7 6 5 1 8 0 0 1 9 8 0 1 5 6 1, 5 3 1 2 3, 1 1 5 7, 7 7 4, 6 7 6 5 1 9 2 5 2 1 2 0 1 5 6 1, 5 3 1 2 3, 1 1 4 7, 3 6 9, 8 7 6 5 2 0 5 0 2 2 5 5 1 5 6 1, 5 3 1 2 3, 1 1 3 8, 5 6 5, 5 C a s e s w e r e t h e r e - g n it io n d v / d t is h ig h e r t h a n t h e c h o p p e d w a v e le v e l C a s e s w e r e t h e r e - g n it io n d v / d t is h ig h e r t h a n 6 8 % o f t h e c h o p p e d w a v e le v e l ( r e q u ir e d m a r g in ) * : C o n s id e r in g a d a m p in g f a c t o r o f 0, 5 a n d a k a o f 1, 3 41

3- Real case, re-ignition and current chopping (continued) For reactors rated 69 kv to 161 kv, the dv/dt produced by a re-ignition is in excess of the required margin for aged reactors (more than 68 % of the CWWL). For these cases, reignitions can be accepted as an accidental event. It should be noted that for some cases (lower BIL ratings of each nominal voltage class), the dv/dt produced by a reignition will exceed the dv/dt produced by a chopped wave. For these cases, re-ignitions of circuit-breaker shall be avoided. 42

3- Real case, re-ignition and current chopping (continued) As shown in the table, for medium voltage shunt reactors ( 45 kv), the dv/dt produced during single or multiple re-ignitions event (the later only applicable to vacuum circuit-breakers, max. value = 2 X LIPL) is generally well protected by the surge arrester (less than 68% of the CWWL) because of the huge margin between the protective level of the surge arrester and the chopped wave rated level of the shunt reactor. 43

3- Real case, re-ignition and current chopping (continued) For reactors rated above 161 kv, the dv/dt produced by a re-ignition is always higher than the chopped wave rating of the reactor. For these cases, the dv/dt produced by a reignition will exceed the dv/dt produced by a chopped wave and re-ignitions of the circuit-breaker shall be avoided. 44

4- Ways to limit overvoltages a) Shunt reactor arrester protection (shall always be used, normal practice ) : Advantage: - Does limit the phase-to-ground overvoltage applied to the reactor; 45

4- Ways to limit overvoltages (continued) a) Shunt reactor arrester protection (shall always be used, normal practice ) : Disadvantages: - Does not give appropriate protection against the dv/dt produced during a re-ignition (mainly for reactors rated 69 kv and above). - Not effective to reduce the probability of a re-ignition of the circuit-breaker. 46

4- Ways to limit overvoltages (continued) b) Opening resistors (used in the past on air-blast circuitbreakers, normally not offered today): Advantages: - Does limit the amplitude of the current chopping; - Effective to limit the chopping overvoltage; - Effective to limit the probability of re-ignition and effective to limit the overvoltage caused by a reignition. 47

4- Ways to limit overvoltages (continued) b) Opening resistors (used in the past on air-blast circuitbreakers, normally not offered today; continued) : Disadvantages : - Expensive ; - Reduced reliability of the circuit-breaker ; - Increase the need of circuit-breaker maintenance ; - Thermal limitation. 48

4- Ways to limit overvoltages (continued) c) Arresters in parallel with the circuit-breaker (solution used on some SF 6 circuit-breakers) : Advantages : - Does limit the amplitude of the TRV across the circuitbreaker, effective to limit the re-ignition window; - Effective to limit the resulting dv/dt in case of a reignition; - Passive element. 49

4- Ways to limit overvoltages (continued) c) Arresters in parallel with the circuit-breaker (solution used on some SF 6 circuit-breakers; continued) : Disadvantages : - Expensive; - Thermal limitation. 50

4- Ways to limit overvoltages (continued) d) Synchronous switching (today's preferred solution) : Advantages : -Does forbid opening operations within the re-ignition window; - Cost (not necessarily for MV circuit-breakers); - Easy to implement for all types of circuit-breakers. 51

4- Ways to limit overvoltages (continued) d) Synchronous switching (today's preferred solution; continued) : Disadvantages : - Need to carry extensive circuit-breaker testing for the evaluation of the re-ignition window and current chopping characteristics; 52

4- Ways to limit overvoltages (continued) d) Synchronous switching (today's preferred solution; continued) : Disadvantages : - Need to carry special mechanical tests for the determination of the scatter in opening times in relation with control voltage, gas pressure, available energy in the operating mechanism, ambient temperature, etc...; - Electronic component (sensitivity to EMC). 53

Conclusions - Switching of shunt reactors may produce severe dielectric stresses to shunt reactors; - Determination of circuit-breaker characteristics (test procedure) in relation with shunt reactor switching (current chopping and re-ignition window) is well defined in IEC and IEEE; - C57.21 (IEEE Standards Requirements Terminology, and Test Code for shunt reactors Rated Over 500 kva) shall refer to these documents for the evaluation of the overvoltages; We do propose to use "3 x Se" instead of "2 X Se" for extra high voltage shunt reactors (500 and 765 kv) because of the reduced protective margin. 54

Conclusions - C57.21 shall prescribe maximum overvoltage levels that shunt reactors are able to withstand as a daily event (considering ageing and safety margin). This conclusion can be also applicable to power transformers. a) We propose that the maximum overvoltage produced by current chopping shall not exceed 68% of the rated SIWL rating of the reactor or 56% of the rated BIL rating (68% x 83% x LIWL) if SIWL is not defined; b) We propose that the maximum dv/dt produced during re-ignition (if re-ignitions are allowed as a possible daily event) to be less than 68% of the rated CWWL of the reactor; 55

Conclusions c) We propose to add in C57.21 that shunt reactors rated 230 kv and above are not designed to withstand the stresses produced by a re-ignition of the circuit-breaker unless special measures have been taken in the reactor design or in the circuitbreaker design. d) We propose to add in C57.21 that in no case, the dv/dt produced during a re-ignition should exceed the rated CWWL of the shunt reactor. 56