Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes

Similar documents
Transmission Protection Overview

PROTECTION SIGNALLING

Communication Aided Tripping. Common Methods, Schemes and Considerations

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

System Protection and Control Seminar

COPYRIGHTED MATERIAL. Index

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

System Protection and Control Subcommittee

SEL-311C TRANSMISSION PROTECTION SYSTEM

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525.

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Determination of Practical Transmission Relaying Loadability Settings Implementation Guidance for PRC System Protection and Control Subcommittee

Protection Challenges for Transmission Lines with Long Taps

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

Line Protection Roy Moxley Siemens USA

Transmission System Phase Backup Protection

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Protective Relaying for DER

NERC Protection Coordination Webinar Series July 15, Jon Gardell

Figure 1 System One Line

Switch-on-to-Fault Schemes in the Context of Line Relay Loadability

Protective Relaying Philosophy and Design Guidelines. PJM Relay Subcommittee

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

IMPACT OF SERIES COMPENSATION ON THE PERFOMANCE OF DISTANCE PROTECTION ON ESKOM TRANSMISSION GRID. Sihle Qwabe

Agenda Notes for 4 th Meeting of Sub Group in respect of Preparation of Reliability Standards for Protection System and Communication System

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

Protection Introduction

Power systems Protection course

Distance Relay Response to Transformer Energization: Problems and Solutions

Power System Fundamentals

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME

Introduction. Disclaimer

(Circuits Subject to Requirements R1 R5) Generator Owner with load-responsive phase protection systems as described in

Teleprotection function

Relaying 101. by: Tom Ernst GE Grid Solutions

Standard Development Timeline

Defining and Measuring the Performance of Line Protective Relays

Innovative Solutions Improve Transmission Line Protection

Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? What Is a Distance Protection Element?

Standard Development Timeline

Power System Protection Where Are We Today?

Ground Fault Protection of Pilot Schemes: Basics and Applications

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)

Distance Element Performance Under Conditions of CT Saturation

Time-current Coordination

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

Power Plant and Transmission System Protection Coordination Fundamentals

Relay Communication Misoperations. Southwest Power Pool System Protection and Control Working Group

NEW DESIGN OF GROUND FAULT PROTECTION

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Protection of Microgrids Using Differential Relays

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK

Generator Protection GENERATOR CONTROL AND PROTECTION

Line protection REL 100

Setting Generic Distance Relay UTP-100#WPSC1. in the. Computer-Aided Protection Engineering System (CAPE)

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 9

70 TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS TEXAS A&M UNIVERSITY COLLEGE STATION, TEXAS APRIL 3 APRIL 6, 2017

4.2.1 Generators Transformers Transmission lines. 5. Background:

Using a Multiple Analog Input Distance Relay as a DFR

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng.

Busbars and lines are important elements

Transmission Line Applications of Directional Ground Overcurrent Relays. Working Group D24 Report to the Line Protection Subcommittee January 2014

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

PG&E 500 kv Series-Compensated Transmission Line Relay Replacement: Design Requirements and RTDS Testing

Digital Line Protection System

Line Differential Protection Under Unusual System Conditions

Protecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved.

NERC Protection Coordination Webinar Series June 30, Dr. Murty V.V.S. Yalla

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A

EE Lecture 14 Wed Feb 8, 2017

An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability using Park s Transformation

A short introduction to Protection and Automation Philosophy

Directional Elements in L-PRO 4000

APPLICATION OF A SINGLE POLE PROTECTION SCHEME TO A DOUBLE-CIRCUIT 230 KV TRANSMISSION LINE

Analog Simulator Tests Qualify Distance Relay Designs to Today s Stringent Protection Requirements

Power Plant and Transmission System Protection Coordination

Centralized busbar differential and breaker failure protection function

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

Voltage dip mitigation for motor starters using an adaptive high speed relay protection on the high voltage transmission system

CARRIER-AIDED PROTECTION OF TRANSMISSION LINES

OUT-OF-STEP PROTECTION FUNDAMENTALS AND ADVANCEMENTS

REL 300 (MDAR) Numerical Transmission Line Protection

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan

Phase Comparison Relaying

POWER SYSTEM II LAB MANUAL

A Transfer Trip Scheme to Supervise Zone 3 Operation

A Distance Based Protection Scheme for Distribution Systems with Distributed Generators

S.A.Soman. Power Swing Detection, Blocking and Out of Step Relaying. Department of Electrical Engineering IIT Bombay. Power System Protection

Communications Assisted Islanding Detection

REL301/302 Firmware Version 1.23 (08/19/03) Addendum to Instruction book V1.20, F

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There?

High speed bus transfer function block description Operation Manual

Summary Paper for C IEEE Guide for Application of Digital Line Current Differential Relays Using Digital Communication

Automatic reclosing function for high voltage networks

What s New in C TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines

Transcription:

Transmission Line Protection Objective General knowledge and familiarity with transmission protection schemes

Transmission Line Protection Topics Primary/backup protection Coordination Communication-based schemes Breaker failure protection Out-of-step relaying Synchronism checking

Primary Protection Function Trip for abnormal system conditions that may Endanger human life Damage system equipment Cause system instability

Protection Zones Primary protection first line of defense Backup protection operates when primary fails

How Can A Protection System Fail? Current or voltage signal supply Tripping voltage supply Power supply to the relay Protective relay Tripping circuit Circuit breaker

Two Types of Backup Remote backup Located at different station No common elements Local backup Located at same station Few common elements Separate relays Independent tripping supply and circuit Different current and voltage inputs

Remote vs Local Backup Speed Remote is slower Selectivity Remote disconnects larger part of the system Price Local requires additional equipment

Primary and Backup Coordination Best selectivity with minimum operating time Backup achieved through settings Pick up values Time delays

Coordination Types Considered Time-Overcurrent Time-Stepped Distance Communication-Aided Schemes

Time-Overcurrent Relays Definite-Time Overcurrent Operate in a settable time delay when the current exceeds the pickup value Instantaneous operation no intentional time delay Inverse-Time Overcurrent Operating curve chosen as a function of the damage curve of the primary equipment

Time-Overcurrent Coordination Inverse-Time Overcurrent Pickup of relay A set low enough to see the fault shown and backup relay C Pickup should be above emergency load conditions (phase relays) Time delay of relay A should allow relay C to clear the fault first

Time-Overcurrent Coordination S - Selectivity time delay (aka CTI): Breaker operating time Overtravel (impulse) time (E/M relays) Safety margin 0.2s CTI 0.4s

Time-Overcurrent Coordination Looped Systems Directionality required for most relays 1-2-3-4-5 a-b-c-d-e Relays at 5 and e can be nondirectional

Instantaneous Overcurrent Protection Inverse-Time O/C coordination may result in long time delays Instantaneous O/C relays set to trip for faults for ~80% of the line section Significantly reduced tripping times for many faults

Time-Stepped Distance Protection Coordination similar to that of inverse-time O/C Relay at A set to trip instantaneous for faults in its Zone 1 (reaching ~80% of the line section) Relay at A backs up relay at C after Zone 2 timer times out Faults at the end of the line also cleared in Zone 2 time

Communication-Based Protection Rationale Distance protection can clear faults instantaneously for 60% to 80% of the line length Protection speed may be critical to maintain system stability High-speed autoreclosing application

Communication-Based Protection Communication Mediums Power Line Carrier Microwave Fiber-Optics Pilot Channels (Private and Leased)

Communication-Based Protection Scheme Types Permissive Overreaching Transfer Trip (POTT) Permissive Underreaching Transfer Trip (PUTT) Directional Comparison Blocking (DCB) Directional Comparison Unblocking (DCUB) Direct Underreaching Transfer Trip (DUTT) Direct Transfer Trip (DTT)

Permissive Overreaching TT Protective Zones

Permissive Overreaching TT Permissive signal must be detected from the remote end for the communicationaided trip Absence of communication channel disables the accelerated tripping

Permissive Overreaching TT Complications and Concerns Desensitization due to infeed Dependability issue failure to trip high speed Current reversal Occurs in parallel lines with sequential tripping Security issue coupled with long channel reset times may cause trip of the healthy parallel line

Current Reversal All Sources In Z2 at Breaker 1 picks up and sends permissive signal to Breaker 2 Z2 at Breakers 3 and 4 send permissive signals to each other Z1 at Breaker 4 trips instantaneously

Current Reversal System After Breaker 4 Opens Current reverses through the healthy line Z2 at Breaker 2 picks up If the permissive signal has not reset, Breaker 2 trips on POTT

Current Reversal Possible Solution Timer with instantaneous pickup and time delayed dropout, initiated on reverse Z3 Delay trip with POTT until the timer drops out

Permissive Underreaching TT Similar to POTT but permissive signal sent by underreaching Z1 elements At the receiving end, Z2 elements qualify the permissive signal No problems with current reversal since Z1 doesn t overreach

Directional Comparison Blocking Protective Zones Zone 2 elements cover the entire line Reverse Zone 3 elements must reach further than the opposite Zone 2 overreach

Directional Comparison Blocking Basic Logic In-section faults will not key transmitter and both ends trip high-speed Out-of-section fault will key the transmitter at the nearest end to block the trip at the opposite end

Directional Comparison Blocking Complications and Concerns Coordinating time at fault inception Z3 faster than Z2, but channel delay time reduces the margin Z2 must be slowed down External fault clearing Z3 and Z2 race to drop out, if Z3 drops out first Z2 overtrips Z3 operates faster and drops slower Channel reset time helps Slower transmitter key dropout time helps

Directional Comparison Blocking Complications and Concerns External fault clearing failure Local backup provided by time-delayed Z3 or external BF relay clears the near bus Remote backup provided by Z2 clears the line Stop preference over start

Directional Comparison Blocking Complications and Concerns Current reversal Reach Margin Z3 reaches farther back than remote Z2 by at least 50% of Z2 overreach

Directional Comparison Unblocking Essentially the same as POTT Requires FSK In-section fault may impede communication In case of channel loss, a 150 ms window is open when permissive signal is bypassed and Z2 allowed to trip high speed

Direct Underreaching TT Underreaching Z1 elements send direct transfer trip Noisy channel can cause false trip Very secure channel required

Pilotless Accelerated Trip Schemes Communication equipment not justifiable in lower voltage transmission applications In-section faults may be uniquely determined by system conditions Detecting these conditions is all that is needed for high speed tripping

Pilotless Accelerated Trip Schemes Faulted System with Breakers Closed After Breaker 2 opens the only current that can flow is the fault current

Pilotless Accelerated Trip Schemes Faulted System with Breaker 2 Open Tripping conditions: Three-phase load was present before the fault Three-phase current was lost Current above the threshold detected in at least one phase

Breaker Failure Relaying Minimize the damage when a breaker fails to clear a fault Trips all sources locally within the critical clearing time to maintain system stability

Breaker Failure Relaying Common Causes of Breaker Failure Main breaker poles failed to clear the fault due to inadequate insulating medium Open trip coil or trip coil circuit Loss of tripping dc Mechanical failure of the breaker trip mechanism

Breaker Failure Relaying Operating Philosophy Activated only when a trip signal is issued from protective relay If current is above threshold after a pre-set time period, breaker failure condition is declared

Breaker Failure Relaying Considerations Timer settings must take into account the clearing time of the slowest breaker and the reset time of the fault detector The effect of CT subsidence current on the apparent current dropout time Substation bus configuration must be taken into account to trip minimum number of breakers In multi-breaker schemes, possible transfer trip to the remote end

Out-of-Step Detection and Blocking Causes of Out-of-Step Power swings result from faults, switching, or big changes in load or generation Magnitude of the swing depends on the system impedance change during such conditions Swings can be stable or unstable

Power Transfer Equation where:, sin P power transferred from the sending to the receiving end V V S R P P P sending end voltage receiving end voltage angle by which V S S R leads V VV X total reactance between the sending and receiving end R S X R

Power Transfer Curves,

Electrical Quantities During Swing Apparent Impedance Trajectories

Electrical Quantities During Swing Apparent Impedance Trajectories Apparent impedance during power swings can enter into the reach of distance relays If the apparent impedance stays longer than the time delay in a given zone, that distance element will trip as for a fault To prevent such tripping, out-of-step blocking schemes are employed

Out-of-Step Blocking Distance Elements If the timer expires between the two zones, out-of-step condition is declared and selected distance elements are blocked

Synchronism Checking After clearing a fault, one end of the line will reclose to test the line If the test is good, the other end can be closed but only if voltages are close enough and there is a small phase angle difference If the conditions are not right, the system will undergo a mechanical and electrical shock with a possible unstable swing

Synchronism Checking Monitored Quantities Voltage magnitudes Phase angle difference Slip frequency

Synchronism Checking Synchronizer Window

Synchronism Checking Conditions Both voltage phasors are above 59V setting Phase angle difference is small The above conditions are maintained for at least a short time, ensuring that the slip frequency is small enough and measurements are valid

Synchronism Checking Relay Phasor difference setting 25DV Timer setting 2 59V sin 25T 360 f The measured phasor difference should be below the setting for the given time Different than a synchronizing relay

Questions?