This document covers common questions concerning the design of an effectively grounded system.

Similar documents
Babak Enayati National Grid Thursday, April 17

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

ECE 528 Understanding Power Quality

Grounding Recommendations for On Site Power Systems

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Protective Relaying for DER

Table of Contents. Introduction... 1

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Summary of the Impacts of Grounding on System Protection

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection

Fuseless Capacitor Bank Protection

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

Upgrading Your Electrical Distribution System To Resistance Grounding

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

E N G I N E E R I N G M A N U A L

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

Our Brands. Where we are?

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Utility Interconnection and System Protection

Understanding Harmonic Suppression Systems

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

2 Grounding of power supply system neutral

889 Advanced Generator Protection Technical Note

Bus Protection Fundamentals

ECE 528 Understanding Power Quality. Paul Ortmann (voice) Lecture 6

TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM

Transformer Protection

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

1% Switchgear and Substations

SHUNT CAPACITOR BANK DESIGN AND PROTECTION BASICS

Ferroresonance on Transformer 13-kV Ungrounded Tertiary at Arab

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

Busbars and lines are important elements

FERRORESONANCE SIMULATION STUDIES USING EMTP

Harmonic control devices

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Implementation Plan Project Modifications to PRC Reliability Standard PRC-025-2

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Figure 1. Two- and Three-phase MagneX Interrupter.

Transformer Protection Principles

Two- and three-phase MagneX interrupter

Catastrophic Relay Misoperations and Successful Relay Operation

Harmonic control devices. ECE 528 Understanding Power Quality

Ground Fault Location. Turbo Sleuth. Instruction Manual

EE Lecture 14 Wed Feb 8, 2017

Ground Fault Detection using Zigzag Grounding Transformer in Ungrounded System

Overvoltage and undervoltage. Dr Audih 1

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

Generator Protection GENERATOR CONTROL AND PROTECTION

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

Single Line Diagram of Substations

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

ANALYSIS OF LIGHTNING ARRESTER OVERLOADING IN FUTURE DISTRIBUTION SYSTEMS WITH DISTRIBUTED GENERATION. A Thesis JONATHAN MICHAEL SNODGRASS

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES

Earth Fault Protection

Industrial Electrician Level 3

> the power to protect. Ground Fault Protection on Ungrounded and High Resistance Grounded Systems. Application Guide.

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

System Protection and Control Subcommittee

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority

Wisconsin Contractors Institute Continuing Education

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

ECE 528 Understanding Power Quality

Microgrid Protection

BUS2000 Busbar Differential Protection System

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition

The Connecticut Light and Power Company

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Information and Technical Requirements For the Interconnection of Distributed Energy Resources (DER)

Experiences in Integrating PV and Other DG to the Power System

Unit 2. Single Line Diagram of Substations

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources

Embedded Generation Connection Application Form

Education & Training

1

Embedded Generation Connection Application Form

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER

Grid Radar Installation Manual

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

GUIDE FOR GENERATOR INTERCONNECTION THE WIRES OWNER DISTRIBUTION SYSTEM

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME

Do Capacitor Switching Transients Still Cause Problems?

Transcription:

This document covers common questions concerning the design of an effectively grounded system. To prevent against temporary overvoltage conditions when a line-to-ground fault occurs on the power grid. Effective grounding maintains voltages within specified limits during a line-to-ground fault (short-circuit condition), typically through the use of a grounding bank. While maintaining voltage, the grounding bank generates a neutral current during the fault which is monitored to trip protective devices, turning the generation facility off. This prevents damage to customer and utility equipment from overvoltage or the grounding bank s neutral current. Effective grounding utilizes a grounding bank, typically a shunt-connected zig-zag or wye-delta transformer 1, connecting the phase wiring to the neutral wire of the system. The grounding bank needs to have certain impedance characteristics to balance the symmetrical components of the system during a fault in order to achieve effective grounding. Please see Appendix A for details on the impedance requirements. A B C Zig-zag Grounding Bank A B C Wye-delta Grounding Bank 1 Effective arch 1, 2018, only zig-zag transformers will be accepted for shunt-connected grounding banks in effective grounding systems.

The following system components are needed:. Typically a grounding transformer connected as a shunt to the system, with a connection to the system neutral (not ground). Specifications will be provided to size the transformer. ote: the grounding bank can be a three-phase unit or three individual transformers connected in the desired configuration. o The grounding bank will maintain the voltage within specified limits until the generation system and grounding bank are disconnected.. The inverters and the grounding bank need to have overcurrent protection between them and the service transformer. You can use a main breaker for the whole system, or you can use multiple breakers one for the grounding bank and one or more for the inverters. ultiple breakers provide better protection for your equipment in case one of the breakers fails. o The overcurrent protective device(s) (breaker) shall open simultaneously all ungrounded conductors connected to the generation system and grounding bank when it operates.. Typically a relay and a current transformer (CT) are used to monitor the neutral current of the grounding bank or system and trip the breakers when the neutral current limit is reached. The neutral current trip point will be supplied with the grounding bank specifications. o When a fault is detected, the relay system shall operate the overcurrent protective device(s) to disconnect the generation system and the grounding bank.. The relay and breakers must be operational any time the customer generation facility is energized. If the normal power supply to the relay is lost, there needs to be a means to power for the relay until it can open the breakers. o The continuous power supply needs to last long enough to power the relay until the breakers are opened. The relay can t be allowed to lose power while the inverter(s) and grounding bank remain connected to the system. If this were to happen during a line-toground fault on the system, the breakers wouldn t trip until after serious damage to your equipment (and possibly other people s equipment, too). o An alternative is to use a breaker scheme that requires an active signal from the relay to remain closed. If the relay loses power, the breakers would open. This would eliminate the need for a continuous power supply, but it could result in more breaker trips. Additional technical specifications can be found in Appendix A. If a main breaker is used upstream of the generation and grounding bank, the relay has to be operational before the breaker can be closed. An example system configuration is shown in Figure 2, below (note: all systems must be designed according to local codes, and will be subject to inspection by the Authority Having Jurisdiction).

Distribution System Distribution System Customer G eneration Service Transformer Utility eter elay System eutral Customer Generation Grounding Bank If you decide to go with a multiple-breaker system, the relay needs to control all breakers so that: When the neutral current trip-point is reached, the breakers are opened. If the inverter breakers opens, the grounding bank breaker needs to open within 2 seconds. If the grounding bank breaker opens, the inverter breakers need to open within 2 seconds. After a trip, the relay has to be operational before the breakers can be closed o Closing both breakers simultaneously is ideal, but if that s not possible: The grounding bank breaker must be closed first. The inverter breaker should be closed within 2 seconds of the grounding bank breaker being closed. An example system configuration is shown in Figure 3 below. Customer G eneration Service Transformer

Distribution System If your design requires a step-up or step-down transformer, this may be a great option for you. The inline wye-delta transformer provides the effective grounding, without the need for an additional shuntconnected grounding bank. The delta winding, however, must be on the generation side of the system as shown in Figure 4 below. Customer Step Up/ Service Transformer Down Transformer Customer Generation Using the information in this document, along with the sizing specs we ll provide for the grounding bank, we need an updated one-line drawing that shows: The grounding bank s connection to the system. The grounding bank specifications. Both the generation system and the grounding bank protected by the breaker(s) controlled by the relay system. The relay connections to the breaker(s), the CT on the neutral wire, and the continuous power supply connections. The relay control settings (including the neutral trip-point). If available, an export of the settings is preferred. Once received, we will review for completeness and provide any needed feedback. We want this to be a smooth and simple process but sometimes system complexities require adjustments. Working closely with you, we will do all we can to efficiently reach a design that protects both our system and your equipment. Once the installation is complete, a site visit may be required before your system is connected. We thank you for your interest in our customer generation program. We want this to be a smooth and efficient process for you and. If you have any questions, you can always reach us at CustomerGeneration@.com.

The following are technical specifications and guidelines for the effective grounding system. Please note that these specifications do not supersede applicable electrical code or ES requirements. An effectively grounded system will meet all applicable electrical code and ES requirements while achieving these technical specifications. The definition of effective grounding is taken from the ESC as defined by IEEE standards. The EC definition, taking the term effectively grounded as meaning well grounded does not apply. Grounding banks must meet the IEEE definition of effectively grounded: X 0 X 1 3 0 X 1 1 Additionally, requires the following ratio for the grounding bank to be satisfied: X g g 4 Copper windings in the grounding bank will typically accomplish this ratio. If necessary, a line reactor inserted into each phase, or between the neutral of the grounding bank and the neutral of the system, is an acceptable means of achieving the needed ratio. In addition to the requirements given in the main body of this document, the following guidelines should be observed in designing the effective grounding bank s connection to the system. In most cases the grounding bank should have a shunt (or parallel) connection to the system. o An exception to this is where an in-line wye-delta transformer is utilized. A low impedance neutral current path meeting the IEEE definition for effective grounding must exist, through all customer-owned equipment including transformers, from the distribution transformer to the effective grounding equipment. o The center point of the grounding bank shall not be bonded to ground, creating a separately derived system, but only have a path to the neutral bus of the service. Connecting inverters in a wye configuration (phase-to-neutral) will provide effective grounding without the need of a grounding bank. Balanced loads are required.