Pinhook 500kV Transformer Neutral CT Saturation

Similar documents
Using a Multiple Analog Input Distance Relay as a DFR

Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA

Catastrophic Relay Misoperations and Successful Relay Operation

Verifying Transformer Differential Compensation Settings

Testing Numerical Transformer Differential Relays

PROTECTIVE RELAY MISOPERATIONS AND ANALYSIS

Transformer Protection

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Generator Protection GENERATOR CONTROL AND PROTECTION

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME

PROTECTION OF TRANSFORMERS M-3311A TEST PLAN

Differential Protection with REF 542plus Feeder Terminal

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

Forward to the Basics: Selected Topics in Distribution Protection

Improving Transformer Protection

Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System

Transformer Protection Principles

Earth Fault Protection

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

GMD Impacts on Generators

IV/IV B.Tech (Regular) DEGREE EXAMINATION. Electrical &Electronics Engineering

Problems connected with Commissioning of Power Transformers

Overcurrent Elements

Transformer protection IED RET 670

Detecting and Managing Geomagnetically Induced Currents With Relays

System Protection and Control Subcommittee

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Substation Monitoring with TESLA

Optimizing HV Capacitor-Bank Design Protection & Testing

What s New in C TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component

Solving old problems with new technology: How to monitor and measure GIC and OPD currents

Effect of Geomagnetically Induced Currents on Protection Systems

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

Visualization and Animation of Protective Relay Operation

Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current

Performance Analysis of Traditional and Improved Transformer Differential Protective Relays

Optimizing HV Capacitor Bank Design, Protection, and Testing Benton Vandiver III ABB Inc.

ISSN: Page 298

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

HV SHUNT REACTOR SECRETS FOR PROTECTION ENGINEERS

Distance Relay Response to Transformer Energization: Problems and Solutions

889 Advanced Generator Protection Technical Note

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

Event Analysis Tutorial

Waterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology

Static Breaker Back-up Relay Type SBC Relay SBC231B

Fundamentals of Power Quality

Working Group I21, Relaying Practices Subcommittee IEEE PES Power System Relaying Committee

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

ATP modeling of internal transformer faults for relay performance testing

Distance Element Performance Under Conditions of CT Saturation

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

Relaying 101. by: Tom Ernst GE Grid Solutions

PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS

Beyond the Knee Point: A Practical Guide to CT Saturation

Turn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Unit Protection Differential Relays

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

Impact of Incipient Faults on Sensitive Protection

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

Relay-assisted commissioning

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Transmission Interconnection Requirements for Inverter-Based Generation

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

Impact Assessment Generator Form

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

Power systems 2: Transformation

CURRENT TRANSFORMER CONCEPTS

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3

Introduction to Harmonics and Power Quality

Performance of Relaying During Wide-area Stressed Conditions

ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT

Phase Comparison Relaying

Protective Relaying for DER

Digital Line Protection System

BED INTERCONNECTION TECHNICAL REQUIREMENTS

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

Tom Ernst GE Digital Energy Craig Talbot Minnesota Power

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security

2015 Relay School Bus Protection Mike Kockott March, 2015

Transcription:

Russell W. Patterson Tennessee Valley Authority Presented to the 9th Annual Fault and Disturbance Analysis Conference May 1-2, 26

Abstract This paper discusses the saturation of a 5kV neutral CT upon energization of a 13MVA transformer bank. The event resulted in the misoperation of a restricted earth fault element protecting the bank and capacitor bank protection on grounded wye capacitor banks in the surrounding system remote from this station. The merits of the simple directional overcurrent restricted earth fault scheme will be discussed as well as the analysis of the capacitor bank protection misoperations. Introduction On May 31, 23 TVA energized the 13MVA Pinhook bank from the 5kV side with the 161kV breakers open and 13kV tertiary winding unloaded. The bank tripped by 5kV winding restricted earth fault (REF) protection located in the B-set microprocessor transformer protection relay. On a subsequent energization of the bank, 161kV capacitor banks remote from this station misoperated by solid-state residual overcurrent protection (SFC relays). Figure 1 below shows the transformer bank configuration and the secondary CT wiring to one of the microprocessor bank protection relays. Dual primary bank protection relays are used and both A and B set relays are wired identical but from different CT windings with the exception of the neutral CTs (one per neutral). 5kV:161kV:13kV Yn-yn-d Transformer Bank 528 3:5 MR 5kV 161kV 5:5 MR 136 1148 524 2/4:5 4/8:5 5:5 MR 3:5 MR 13kV 12,:5 MR 4-1PH (ABB) 269/358/448MVA S-1344MVA W-1394MVA 5:165:13.2kV All CTs are WYE connected. 87 Figure 1. One-line of Pinhook bank differential protection circuit. Page 2 of 1

Neutral CT Saturation Figure 2 shows the 5kV currents during the May 31, 23 energization of the Pinhook bank. B-phase has a large DC offset and the CT experiences some degree of saturation as can be seen by the inrush current waveform transitioning below the axis. The 5kV neutral CT experiences significant saturation around the 2ms point. May 31, 23 Energization 6 IA IB IC IN 4 Amps (primary, 5kV side) 2-2 -4 1 2 3 4 Figure 2. 5kV Phase Currents and 5kV Neutral Current. Figure 3 below shows the 5kV neutral current along with the 5kV residual of the phase currents. Initially all CTs reproduce well but around the 2mS point the neutral CT experiences heavy saturation. The 5kV neutral CT is a 25kV, 2/4:5 (set on 4:5), T2 on full winding, T9 on tap, type KOR- 15. May 31, 23 Energization 1 Residual (IA+IB+IC) 5kV Neutral Amps (primary, 5kV side) -1-2 4:5 neutral CT experiences heavy saturation -3 1 2 3 4 Figure 3. 5kV Neutral CT Saturation. Page 3 of 1

Affect on a Restricted Earth Fault Protection Element Figure 4 shows the differential current resulting between the 5kV residual and 5kV neutral CT currents. 5 May 31, 23 Energization 5kV Residual minus 5kV Neutral Amps (primary, 5kV side) -5-1 -15 as 5kV neutral CT begins heavy saturation a large differential current appears -2 1 2 3 4 Figure 4. 5kV Ground Differential Current. The B-set transformer differential relay has an REF element that is implemented as a traditional differential element with slope. When the 5kV neutral CT saturated it produced a large REF differential current (Figure 4) causing this differential element to pickup. After a 6 cycle delay it tripped. The 5kV breaker disconnects the transformer bank 2 cycles later. May 31, 23 Energization 5 REF Differential Current REF Trip REF Picked Up Amps (primary, 5kV side) -5-1 -15 5kV REF element picks up. 5kV REF element operates. -2 1 2 3 4 Figure 5. B-set transformer relay initiates a trip. Page 4 of 1

The B-set relay was running an early version of the relay vendor s firmware which included a default slope setting of 1%. Subsequent versions of the firmware had a default slope of 4% as well as other enhancements to make the REF element more secure. The A-set relay implemented REF protection using a simple directional overcurrent principle 2 that is simple, secure and reliable. This method compares an operate quantity (residual of 5kV phase currents) with a polarizing quantity (5kV neutral current). The element won t allow operation unless the two currents are within 9º of each other and are of sufficient magnitude. The CT currents are wired to the relay such that normally these two currents are 18º out-of-phase with each other. Even under heavy saturation the two currents cannot migrate to within 9º of each other. Figure 6 shows a phasor plot of the two currents fundamental components before and after the 2ms point where heavy saturation starts. 1 2 3 9 9 135 neutral 45 residual 135 neutral 45 residual 18 18 225 315 225 315 27 27 Figure 6. Fundamental phasors before and during saturation. Even under heavy saturation the neutral current doesn t shift more than 45º leading from its previous position of 18º. The simple directional current approach to REF protection won t allow operation unless the two currents are within 9º of each other. This method appears very secure against misoperation due to neutral CT saturation. Page 5 of 1

Misoperation of Area Capacitor Banks The May 31, 23 bank energization only lasted about 16 cycles before the REF misoperation tripped off the bank. On June 11, 23 the bank was energized for a second time. This time the REF problems in the B-set relay had been overcome and the bank remained energized. Subsequent to this bank energization three area 161kV capacitor banks misoperated by SFC (obsolete static type) residual overcurrent relays. June 11, 23 Energization 1 IA IB IC IR 5 kamps (primary, 5kV side) -5-1 2 3 4 5 6 7 8 Figure 7. June 11 Energization of Pinhook Bank. The energization of the large Pinhook transformer bank was a significant unbalanced condition applied to the power system. The large currents in the transformer neutral were reflected in area 161kV capacitor bank neutrals. A sensitive residual overcurrent relay (SFC) applied on these capacitor banks misoperated for these currents. The SFC relay is a solidstate relay that operates on a true RMS value. TVA field test personnel have tested the SFC relay to ascertain its frequency performance 1. The relay was tested up to the 14th harmonic and was shown to have a flat frequency response. (i.e., the relay operates the same when it sees 5A at 84Hz as it does for 5A at 6Hz). Reference 1 describes misoperations of the SFC during geomagnetic storm events. The SFC was wired to see capacitor bank residual current and was set low (2-3A primary). It was supervised by a 3V relay designed to block its operation during normal system ground faults while allowing its operation for capacitor bank unbalance. The capacitor banks were excellent sinks for the inrush neutral current and the supervising relays were set based on system fault studies such that they did not pickup during this event. Note that these currents flowing in the capacitor bank neutrals would have been predominately 2nd harmonic. This is contrary to what we usually think flows in neutrals. For balanced harmonics (symmetrically created across all three phases) only triplen (3 rd, 6 th, 9 th etc.) harmonics flow in the capacitor bank neutrals 3. But, transformer energization is not a symmetrical event as is clearly seen by the 5kV residual current present during energization (Figure 8). Page 6 of 1

SCADA Sequence of Event data during the June 11 Energization: 13:39:11 Pinhook 5/161kV intertie bank energized at 5kV 13:39:13 Smyrna 161kV cap bank trips by SFC ground relay 13:39:17 McMinnville 161kV cap bank trips by SFC ground relay 13:39:18 Murfreesboro 161kV cap bank trips by SFC ground relay Note: Wilson 161kV cap bank likely did not trip because it was tagged out. 2 June 11, 23 Energization 5kV Residual Current kamps (primary, 5kV side) -2-4 -6 2 4 6 8 1 Figure 8. Residual current present during June 11 th energization. The bank was energized a third time on June 12, 23 with a similar result. The bank stayed in and, once again, three area 161kV capacitor banks (two new ones this time) misoperated by SFC relay. The following is a quote from our Transmission Operator disturbance log: 1819: The Franklin 161-kV, Smyrna 161-kV and Murfreesboro 161-kV capacitor banks were interrupted by ground relay action. This interruption coincides with energizing the Pin Hook 5/161/13-kV transformer. Cause is under investigation. The SFC relay is poorly suited to protection of a capacitor bank for 6Hz fault duty. Capacitor banks are excellent sinks for harmonic energy. TVA has experienced significant simultaneous loss of 161kV capacitor banks (up to 8MVAR) due to misoperations of SFC relays during geomagnetic events 1. The geomagnetically induced currents (GIC) caused half-cycle saturation of 5kV transformers with the resulting harmonic currents finding a path down the capacitor bank neutrals. TVA has also experienced misoperation of an SFC residually connected relay protecting a 161kV capacitor bank when an electrically nearby 5kV transformer bank was energized with one phase on the wrong tap 1. To preclude the chances of significant loss of 161kV capacitor banks these relays have been replaced with microprocessor relays that operate on the fundamental (6Hz) component only. Page 7 of 1

Summary The simple directional overcurrent approach to Restricted Earth Fault (REF) protection provides excellent security during neutral CT saturation. Harmonic currents other than triplen (3 rd, 6 th, 9 th, etc.) can flow in capacitor bank neutrals if they are generated asymmetrically in the power system (such as during a transformer energization). History repeats itself. The GIC events of July 15, 2 uncovered a susceptibility to misoperation of SFC relays that resurfaced when the large Pinhook transformer bank was energized. Page 8 of 1

References 1. Patterson, R.W., Mathcad Analysis of Davidson Capacitor Bank Misoperation, paper presented to the 21 Georgia Tech Fault and Disturbance Analysis Conference. Available at http://webpages.charter.net/rwpatterson357/ 2. IEEE Standard C37.91-2 IEEE Guide for Protective Relay Applications to Power Transformers 3. Sankaran, C., Effects of Harmonics on Power Systems - Part I. EC&M, October 1995. pp. 33-42 4. IEEE Standard C37.11-1996 Guide for the Application of Current Transformers Used for Protective Relaying Purposes. 5. Walter A. Elmore, Protective Relaying Theory and Application. ABB. pp. 8-81. Software TOP The Output Processor. TOP reads data from a variety of sources and transforms it into high quality graphics for inclusion in reports and documents. TOP was developed by Electrotek Concepts to visualize data from a variety of simulation and measurement programs. It can be freely obtained at the following website: http://www.pqsoft.com/top/index.htm Page 9 of 1

Biographical Sketch Russell W. Patterson is Manager of System Protection & Analysis for the Tennessee Valley Authority (TVA, www.tva.gov) in Chattanooga, Tennessee. Prior to this he was manager of TVA s Advanced Network Applications group where he was responsible for the maintenace and expansion of the state estimators used by TVA. As Manager of System Protection & Analysis he is responsible for the setting of all protective relays in the TVA transmission system and at Hydro, Fossil and Nuclear generating plants. He is responsible for ensuring that TVA s protective relays maximize the reliability and security of the transmission system. This includes setting and ensuring the proper application and development of protection philosophy for the TVA. Prior to this role Russell was a Project Specialist in System Protection & Analysis and was TVA s Power Quality Manager responsible for field and customer support on PQ related issues and disturbances. Russell has performed transient simulations using EMTP for breaker Transient Recovery Voltage (TRV) studies including recommending mitigation techniques. Russell is an active member of the IEEE Power System Relaying Committee (PSRC) and a prior member of the Protection & Controls Subcommittee of the Southeastern Electric Reliability Council (SERC). Mr. Patterson earned the B.S.E.E. from the Mississippi State University in 1991. Russell is a registered professional engineer in the state of Tennessee and is a Senior Member of IEEE. Russell s website is http://webpages.charter.net/rwpatterson357/ and he can be e-mailed at rwpatterson@tva.gov. Page 1 of 1