Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Similar documents
Research Article Transformer Winding Deformation Profile using Modified Electrical Equivalent Circuit

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

GIS Disconnector Switching Operation VFTO Study

LIGHTNING IMPULSE MODELING AND SIMULATION OF DRY-TYPE AND OIL-IMMERSED POWER- AND DISTRIBUTION TRANSFORMERS

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

FAULT IDENTIFICATION IN TRANSFORMER WINDING

Generation of Sub-nanosecond Pulses

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

Research Article Survey of Induced Voltage and Current Phenomena in GIS Substation

Electric Stresses on Surge Arrester Insulation under Standard and

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

Ferroresonance Experience in UK: Simulations and Measurements

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

Simulation Study of Voltage Surge Distribution in a Transformer Winding

High Frequency Modeling of Two Limb Series Loop Winding for Partial Discharge Localization

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

Chapter 1. Overvoltage Surges and their Effects

HF Resonators for Damping of VFTs in GIS

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS

Improved Method for Winding Deformation Detection Sensitivity in Transformer

Power Quality and Reliablity Centre

A Literature Survey on Frequency Response Analysis for Detection of Transformer Winding Fault

(2) New Standard IEEE P (3) Core : (4) Windings :

Chapter 7 Conclusion 7.1 General

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

RESONANT TRANSFORMER

Design of Integrated LC Filter Using Multilayer Flexible Ferrite Sheets S. Coulibaly 1, G. Loum 1, K.A. Diby 2

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

Transformer Winding Deformation Analysis using SFRA Technique

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

High-Voltage Test Techniques

Optimized Modeling of Transformer in Transient State with Genetic Algorithm

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

Shunt Reactor Switching

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Comprehensive modeling of Dry type foil winding transformer to analyse inter turn insulation under Lightning Impulse Voltage

Filter Considerations for the IBC

Modeling insulation in high-voltage substations

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Study of Design of Superconducting Magnetic Energy Storage Coil for Power System Applications

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

FRAX Series Sweep Frequency Response Analyzers

Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA)

Electrical Power and Energy Systems

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Tab 2 Voltage Stresses Switching Transients

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

Electromagnetic Interference in the Substation Jose up 400/115 kv

A Study on Ferroresonance Mitigation Techniques for Power Transformer

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

MATEFU Insulation co-ordination and high voltage testing of fusion magnets

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

High voltage engineering

Design and Construction of a150kv/300a/1µs Blumlein Pulser

CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS

Effect of Shielded Distribution Cable on Very Fast Transients

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Design and performance analysis of transmission line-based nanosecond pulse multiplier

the Mega Hertz. Two real PD power the and is the

Computation of Inter-turn Voltages in Transformer Windings with Interconnected Distribution Cable

INTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER

ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER TRANSFORMER

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

DETECTING SHORTED TURNS

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

The various factors influencing the VFTO levels in 500kV and. 750kV GIS have been discussed by developing the simulink models which

DC current interruption tests with HV mechanical DC circuit breaker

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

EFFECT OF RADIAL AND AXIAL MOVEMENT OF WINDING ON COHERENCE FUNCTION IN A 220/132 KV, 100 MVA, AUTO TRANSFORMER

متلب سایت MatlabSite.com

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

Resonances in Collection Grids of Offshore Wind Farms

Insulation Co-ordination For HVDC Station

Sources of transient electromagnetic disturbance in medium voltage switchgear

ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER

PCB Crosstalk Simulation Toolkit Mark Sitkowski Design Simulation Systems Ltd Based on a paper by Ladd & Costache

AORC Technical meeting 2014

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

Rogowski Coil Based Digital Energy Meter

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

Lightning transient analysis in wind turbine blades

Transcription:

Research Journal of Applied Sciences, Engineering and Technology 10(10): 1102-1107, 2015 DOI: 10.19026/rjaset.10.1879 ISSN: 2040-7459; e-issn: 2040-7467 2015 Maxwell Scientific Publication Corp. Submitted: January 19, 2015 Accepted: February 14, 2015 Published: August 05, 2015 Research Article A Simplified High Frequency Model of Interleaved Transformer Winding K. Usha and S. Usa Division of High Voltage Engineering, College of Engineering Guindy, Anna University, Chennai-600025, Tamil Nadu, India Abstract: Disconnector or breaker switching operations generates Very Fast Transient Overvoltages (VFTO) in Gas Insulated Substations (GIS). These VFTO have their rise-times in the range of a few nanoseconds and is followed by high frequency oscillations which can endanger the insulation of transformer winding. Hence it is necessary to develop appropriate models to study these transients. In this study, a simplified transformer circuit model capable of simulating the high frequency range from 100 khz to several MHz is proposed to simulate the high frequency surge over voltages generated in an actual system. A 22 kv interleaved transformer winding is considered for the analysis. Resonant frequencies for different transformer models are obtained in circuit simulation package and compared with measured frequencies obtained from Sweep Frequency Response Analyser (SFRA). The results of the proposed model demonstrate better agreement with the measured values. Keywords: Circuit model, gas insulated substations, impedance characteristics, sweep frequency response analysis, very fast transient overvoltages INTRODUCTION Gas Insulated Substations has gained a wide range of acceptance in power system for its compactness, high reliability and low maintenance (Matsumara and Nitta, 1981). GIS units with sulphur hexafluoride as the insulating gas, has been functioning for more than 30 years (Naidu, 2008). In spite of these merits GIS has its unique problems, among which the susceptibility of the insulation system under VFTO is of major concern. These VFTO s stress the equipment in GIS as well as the secondary equipment (Meppelink et al., 1989). Due to very short rise time, VFTO can cause an unbalance in voltage distribution in transformer windings (Shibuya et al., 1997). Under these circumstances, the turn-to turn voltage can arise close to the transformer BIL. Another problem is the occurrence of resonance in transformer winding when the frequencies of the incoming VFTO match some of the resonance frequencies of the transformer. Most of the time, resonant overvoltages can cause a flashover from the windings to the core or between the turns leading to insulation failure of Transformer. Hence, there is a need to estimate the magnitudes of VFTO generated at the Transformer terminal during switching operations in GIS. Often, the transformer is simulated by a single lumped capacitance called a surge intrusion capacitance. Since high frequency surge overvoltages which ranges from several khz to several MHz are generated in an actual system, the development of a new transformer model for the frequency range of several KHz to MHz is desirable (Okabe et al., 2011). A simple high frequency electric model is used for the analysis of the re-ignition surges at interruptions of the reactor of a model substation (Okabe et al., 1999). To precisely simulate the winding up to the high frequency range, a detailed equivalent circuit is required that provides the inductance and capacitance for each turn of the conductor. However, such a detailed model is far too complicated for the whole transformer if its purpose is not to clarify the electric potential distribution within a winding but to obtain the voltage generated at the transformer terminal through surge analysis of the substation or overall system. In this study a simplified and lumped high frequency circuit model is developed for an interleaved transformer winding. The efficacy of the model is verified by comparing the resonant frequencies with the measurement values. METHODOLOGY Materials: Winding under study: A prototype 22 kv interleaved transformer winding is considered for analysis. The winding comprises of 40 sections with 12 turns/section. The main parameters and constants of the winding are shown in Table 1. The values of inductance and capacitance for different models are calculated from the physical parameters. Corresponding Author: K. Usha, Division of High Voltage Engineering, College of Engineering Guindy, Anna University, Chennai-600025, Tamil Nadu, India This work is licensed under a Creative Commons Attribution 4.0 International License (URL: http://creativecommons.org/licenses/by/4.0/). 1102

Res. J. App. Sci. Eng. Technol., 10(10): 1102-1107, 2015 Table 1: Constants of 22 kv interleaved winding Sections per coil 40 Turns per sections 12 Size of conductor 4.5*1 Mean diameter 319.5 Height of section axial 313 Depth of windings (radial) 19.5 Axial and radial spacing 3 Section clearance 3 Dielectric constant of insulation (εr) 2.08 Conductor conductivity (σ) 5 10 7 S/m Inductance per turn 0.8264 µh Total series capacitance 40.645 pf Total stray capacitance 467 pf G.I. sheet is placed inside the windings to act as a core. All dimensions are in mm Methods: The different circuit models for an interleaved transformer winding are considered for analysis. The resonant frequencies obtained for various models using PSpice are compared with measured frequencies through SFRA. Fig. 1: Detailed circuit-model A (Okabe et al., 2011) Detailed models: Two discs constitute a single structural unit, which comprise the whole winding when collectively stacked (Okabe et al., 2011). The detailed transformer models are used to predetermine the over voltages, to study the resonance behaviour of transformer winding and the distribution of electrical stresses along the transformer winding. Detailed model (Okabe et al., 2011) and RLC Ladder network model (Hosseini et al., 2008) referred as model A and B respectively are discussed in this section. Figure 1 shows the Detailed model (Model A) for an interleaved double disc coil. Each turn is expressed by one inductance element. C a represents the section-tosection capacitance, C r represents the turn-to-turn capacitance and C g represents the ground capacitance per turn whose values are obtained from the finite element method simulation of the actual transformer winding with the accurate physical dimensions. To simulate a single double disc interleaved winding with circuit Model A, the number of nodes required is 20. This circuit model can be simplified which holds in the low frequency range with the parallel combination of L 0 and C 0. Here, L 0 is the self inductance of the whole coil with 2n turns, which is about (2n) 2 times the value of the inductance per turn. The series capacitance of an interleaved disc winding can be obtained using the stored energy method and is given by equation: = (1) where, C 0 in equation is given as the capacitance for two sections in Fig. 2 to structure the circuit of the whole winding. Figure 3 shows the RLC ladder network model (Hosseini et al., 2008) -Model Bfor an interleaved double disc coil. Each turn is expressed by one inductance element and a series capacitance C s and a ground capacitance C g. Fig. 2: High frequency model up to 2 nd order-model C (Okabe et al., 2011) Fig. 3: RLC ladder network model-model B (Hosseini et al., 2008) The series capacitance comprises of inter turn capacitance alone and is given by equation: = () where, E = Order of interleaving C t = Inter turn capacitance N = Number of discs n = Number of turns per section Similarly, to simulate a single double disc interleaved winding with circuit Model B, number of nodes required is 18. 1103 (2)

High frequency circuit model: When the wave front time of the voltage applied to the winding is short relative to the charging time of the inter turn capacitance, the potential of the turns in the section is not linearly distributed and so the capacitance obtained by the stored energy method is not applicable. Pedersen (1963) has assumed each section of an interleaved disc winding to be a spirally wound parallel plane capacitor and considered that the winding responded to steep front waves like a transmission line of capacitance C and inductance L per section. Here, C is given by equation: Res. J. App. Sci. Eng. Technol., 10(10): 1102-1107, 2015 =( 1) / (3) where, = Relative permittivity of the turn-to-turn insulation = Vacuum permittivity D = Average winding diameter b = Axial conductor width d = Turn-to-turn insulation thickness The value L is given by the inductance of the parallel conductors consisting of the conductors in Groups A and B with the length of the parallel conductor in one section equivalent to n/2 turns. Inductance L is given by equation: = / (4) where, µ 0 = Vacuum magnetic permeability When a surge reflects at that part of a section which extends on the inner side to the next section, oscillation of a frequency corresponding to the reciprocating time of the section occurs and its fundamental oscillation frequency is given by: order with Cg- Fig. 4: High frequency model up to 5 th model D =2 =2 1 (5) In order to express an oscillation circuit of resonance frequency f 1 identical to this oscillation using the LC parallel circuit with a lumped constant, its inductance L 1 and capacitance C 1 is given by: = = (6) Hence, = ; = (7) The L 1 C 1 parallel circuit, consisting of the inductance L 1 and capacitance C 1 is serially connected to the L 0 C 0 parallel circuit. This circuit has a parallel resonance point at frequency f 1. To simulate higher order resonance frequencies up to the second order, the L 2 C 2 parallel circuit given by equation L 2 = L 1 /L 2 and = is connected. 1104 Fig. 5: Lumped high frequency model up to 5 th order with Cg-model E

Parallel resistors are connected in the second and third stage LC circuits. The damping resistance of this high frequency wave is expressed as k* (L/C) 1/2 and the value of k is approximately equal to 10. The high frequency circuit model comprises of three stages of LC parallel circuit is shown in Fig. 2. In this case, the number of nodes reduces to 7. The number of three stages of LC parallel circuit equals the number of double disc coil in the entire winding. High frequency circuit model up to fifth order models the high frequency oscillations in addition to the fundamental component. The circuit model is same as that of three stage LC circuit with another three stages cascaded to it accounting for the higher frequencies as shown in Fig. 4. Inclusion of Capacitance to ground (Cg) is necessary since it has a predominant effect in the higher frequency range in the range of MHz. The cascaded LC parallel circuits are the integral multiples of the L 1 C 1 parallel circuit given by equations: = ; = and = ; = Proposed high frequency model: The proposed circuit model (Model E) comprises of two sections of fifth order high frequency model with C g as shown in Fig. 5 which models the entire winding. Model E is obtained from Model D, where the distributed high frequency sections for each and every double disc is converted into only two high frequency sections representing the entire winding. The stray capacitance of the winding is connected in between the two sections. The major advantage of this model is that, the complexity of the model is reduced by reducing the number of nodes required for the whole winding to 13 irrespective of the number of sections, turns and dimensions of the winding. RESULTS AND DISCUSSION Initially, the entire 22 kv interleaved winding is modeled for analyzing the voltage distribution of the inding. Input source is taken as sinusoidal source (50 Hz), lightning impulse and steep wave front 32 nsec surge for voltage distribution studies, as these sources cover the wide frequency range from khz to several MHz. Figure 6 shows the voltage distribution along the winding for different source voltages. The voltage distribution is not linear when the input surge is of very high frequency range (several MHz). A graph showing intersection voltage along Y axis and corresponding sections along X axis is plotted is shown in Fig. 7. The section to section voltage difference is found as constant for sinusoidal supply and a small deviation is seen for lightning impulse. If the wavefront duration is in nano second range, the section to section voltage Res. J. App. Sci. Eng. Technol., 10(10): 1102-1107, 2015 1105 Table 2: Comparison of various models based on nodal requirement Model Nodes required for time domain simulations For 40 disc sections Model A 400 Model B 360 Model C 80 Model D 140 Model E 13 Voltage (V) 100 75 50 25 0 Sinusoidal 50 Hz 32 ns 1.2 us 0 10 20 30 40 Sections Fig. 6: Voltage distribution of 22 kv interleaved transformer winding Inter section Voltage (V) 40 35 30 25 20 15 10 5 Sinusoidal 50 Hz 1.2 us surge 32 ns surge 0 0 8 16 24 32 40 Location in the section-to-section direction Fig. 7: Relationship between location in the section-to-section direction and inter-section voltage difference is not constant. A deviation occurs at the earth terminal and in the middle sections of the winding. Hence, a single transformer model cannot be used for the whole frequency range to obtain the overvoltage at the transformer terminal. A comparison of various models on the basis of nodal requirement is given in Table 2. Model E requires minimal number of nodes for modelling the transformer winding for a wide range of frequencies when compared to other transformer models, thereby conforms the model validity. With AC sweep analysis through PSpice, the resonant frequencies for Model C, D and E of the transformer winding are obtained. Measurement using SFRA: SFRA is designed to detect winding displacements in power transformers or faults in the magnetic core based on the comparison of their resonant frequencies with that of the frequencies corresponding to the healthy winding. The system provides attenuation signature curves that can easily be

Res. J. App. Sci. Eng. Technol., 10(10): 1102-1107, 2015 Table 3: Comparison of resonant frequencies for different models of 22 kv interleaved winding Resonant frequency (MHz) ---------------------------------------------------------------------------------------------------------- Difference in resonant frequency (%) ----------------------------------------------------------------- SFRA measurement Model C Model D Model E Model C Model D Model E 0.24327 0.379 0.3789 0.261-55.80-55.76-7.29 2.95800 2.924 2.9700 2.960 1.15-0.41-0.07 3.89900 4.054 4.0500 4.017-3.98-3.88-3.03 6.18000 6.251 6.2100 6.210-1.15-0.49-0.49 8.05400 8.128 8.0900 8.016-0.92-0.45 0.48 9.57200-9.7700 9.638 - -2.07-0.69 11.91300-12.1600 12.050 - -2.08-1.16 12.76500-14.1200 13.960 - -10.62-9.37 16.64000-16.2900 16.220-2.11 2.53 18.66500-18.4500 18.320-1.16 1.85 21.43000-20.5100 20.420-4.30 4.72 Fig. 8: Experimental set up for SFRA measurement on a transformer winding Impedance (ohm) 10k 1k 100 Model E yields number of resonant frequencies which are in good agreement with the measured resonant frequencies. The difference in resonant frequencies with respect to measurement frequencies is calculated and shown in Table 3. This illustrates that percentage difference in resonant frequency with measured frequencies is less for the Model E when compared to that of other models. 10 100 1k 10k 100k 1M 10M Frequency (Hz) Fig. 9: Measured impedance-frequency response compared for deviations which indicate core movements, winding deformations and displacements, faulty core grounds and partial winding collapse etc. Impedance characteristics of winding is analyzed by FRAX 101 Sweep Frequency Response Analyzer (SFRA), Megger make. The instrument comprises of a sweep frequency voltage source of 10 V peak-to-peak. The experimental set up to carry out sweep frequency measurements is shown in Fig. 8. The impedancefrequency characteristics for the winding obtained through SFRA is shown in Fig. 9. 1106 CONCLUSION For accurate analysis of estimation of overvoltages generated at the transformer terminal in an actual system, the transformer has to be modelled as high frequency model instead of single lumped capacitance for electromagnetic transient simulations. In this study, a 22 kv interleaved transformer winding has been modelled using detailed and high frequency models. Resonant frequencies for these models are obtained using circuit simulation package and are compared with measured frequencies obtained from SFRA. The proposed high frequency model adequately simulates the impedance characteristics of the winding at frequencies up to 25 MHz with the average difference in resonant frequencies for simplified high frequency

Res. J. App. Sci. Eng. Technol., 10(10): 1102-1107, 2015 model (Model E) of 2.8% and also reduces the complexity of the model. REFERENCES Hosseini, S.M.H., M. Vakilian and G.B. Gharehpetian, 2008. Comparison of transformer detailed models for fast and very fast transient studies. IEEE T. Power Deliver., 23(2): 733-741. Matsumara, S. and T. Nitta, 1981. Surge propagation in gas insulated substation. IEEE T. Power Ap. Syst., 100(6): 3047-3054. Meppelink, J., K. Diederich, K. Feser and D.W. Pfaff, 1989. Very fast transients in GIS. IEEE T. Power Deliver., 4(1): 223-233. Naidu, M.S., 2008. Gas Insulated Substations. I.K. International Publishing House Pvt. Ltd. Okabe, S., M. Koto, G. Ueta, T. Saida and S. Yamada, 2011. Development of high frequency circuit model for oil-immersed power transformers and its application for lightning surge analysis. IEEE T. Dielect. El. In., 18(2): 541-552. Okabe, S., M. Koto, T. Teranishi, M. Ishikawa, T. Kobayashi and T. Saida, 1999. An electric model of gas-insulated shunt reactor and analysis of re-ignition surge voltages. IEEE T. Power Deliver., 14(2). Pedersen, A., 1963. On the response of interleaved transformer windings to surge voltages. IEEE T. Power Ap. Syst., 66: 349-356. Shibuya, Y., S. Fujita and N. Hosokawa, 1997. Analysis of very fast transient overvoltage in transformer winding. IEE P-Gener. Transm. D., 144(5). 1107