Power Flow Redistribution in Croatian Power System Network using Phase- Shifting Transformer

Similar documents
Tatjana Šimović a *, Marko Stanić a, Laurenc Kirchner b

Dietrich Bonmann, ABB Monselice Transformer Days, May 5, 2010 Optimized AC transmission solutions with phase-shifting transformers and shunt reactors

The power transformer

Coordination of protective relays in MV transformer stations using EasyPower Protector software

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Impact Assessment Generator Form

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Regional Technical Seminar TAP CHANGERS

Phase Shifting Transformers. Presented by

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

Embedded Generation Connection Application Form

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur

Power Quality enhancement of a distribution line with DSTATCOM

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

EH2741 Communication and Control in Electric Power Systems Lecture 2

Embedded Generation Connection Application Form

Effects of Harmonic Distortion I

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:

, ,54 A

JRC MODIFIED VOLTAGE CONTROL LAW FOR LOW FREQUENCY RAILWAY POWER SYSTEMS

Relay-assisted commissioning

86 chapter 2 Transformers

Grid Impact of Neutral Blocking for GIC Protection:

Transient Stability Improvement Of Power System With Phase Shifting Transformer

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation

Fatima Michael college of Engineering and Technology

Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)

SRI VIDYA COLLEGE OF ENGG AND TECH

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS

ELECTRICAL POWER ENGINEERING

Exercises on overhead power lines (and underground cables)

Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)

QUESTIONNAIRE for Wind Farm Power Stations only

Application of a thyristor-controlled series reactor to reduce arc furnace flicker

Digital Simulation of Thyristor Controlled Interphase Power Control Technology (TC- IPC) to limit the fault currents

Initial Application Form for Connection of Distributed Generation (>10kW)

Incorporation of Self-Commutating CSC Transmission in Power System Load-Flow

In Class Examples (ICE)

Single-Core Symmetrical Phase Shifting Transformer Protection Using Multi-Resolution Analysis

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

ELEMENTS OF FACTS CONTROLLERS

School of Engineering. College of Agriculture, Engineering and Science. Reentseng Majara Molapo. Supervisor: Dr Nhlanhla Mbuli

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Embedded Generation Connection Application Form

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Electrical Power Systems

CHAPTER 4. Distribution Transformers

Regional Technical Seminar

AS the power distribution networks become more and more

Long lasting transients in power filter circuits

El-Hawary, M.E. The Transformer Electrical Energy Systems. Series Ed. Leo Grigsby Boca Raton: CRC Press LLC, 2000

Design and Simulation of Passive Filter

148 Electric Machines

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

Synchrophasor Applications in the Croatian Power System

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Partial Power Operation of Multi-level Modular Converters under Subsystem Faults

Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL

Improving Passive Filter Compensation Performance With Active Techniques

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Example of Transformer Connections and Ground Currents

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

ENHANCEMENT OF POWER FLOW USING SSSC CONTROLLER

GMD Impacts on Generators

Analysis of Power System Oscillation Damping & Voltage Stability Improvement Using SSSC in A Multimachine System

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Basic Operating Principles of Transformers

PROTECTION of electricity distribution networks

PAPER-II (Subjective)

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Spring 2000 EE361: MIDTERM EXAM 1

Company Directive POLICY DOCUMENT: SD4/7. Relating to 11kV and 6.6kV System Design

Keywords: Power Transformer, On-load Tap Changer, AVR, Low Voltage Variation, Change Positions, OLTC Control.

Chapter 10: Compensation of Power Transmission Systems

EL 403 MODEL TEST PAPER - 1 POWER SYSTEMS. Time: Three Hours Maximum Marks: 100

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation

Phase Shifter Application Workshop. Siemens Energy, Inc.

1 st Langaroud, s Conference On Electrical Engineering (LCEE2015) Mohammad Azimi Ashpazi University of Tabriz Tabriz, Iran

Power systems 2: Transformation

MODELLING AND ANALYSIS OF THE ENHANCED TAPP SCHEME FOR DISTRIBUTION NETWORKS

Harnessing of wind power in the present era system

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO

Real-time Decentralized Voltage Stability Monitoring and Protection against Voltage Collapse

Target Mchunu and Themba Khoza Eskom Transmission Division, System Operator Grid Code Management

HV AC TESTING OF SUPER-LONG CABLES

CONTENTS. 1. Introduction Generating Stations 9 40

THE INFLUENCE OF GROUNDING TRANSFORMER ON GROUND FAULT CURRENT IN MV NETWORKS

Transcription:

Power Flow Redistribution in Croatian Power System Network using Phase- Shifting Transformer Ivica Pavić Faculty of Electrical Engineering and Computing Zagreb, CROATIA Sejid Tešnjak Faculty of Electrical Engineering and Computing Zagreb, CROATIA Tomislav Špoljarić Technical Polytechnic in Zagreb, CROATIA

1. Introduction Transformer, observed as an element of the power system, is usually used to transport electric power between two different voltage levels. One of these voltage leves can be regulated by magnitude, and this method of regulation is called voltage magnitude regulation. Besides the voltage magnitude, the voltage phase angle can be regulated. This method of regulation is called phase angle regulation, and is used when there is a need for regulating not only the voltage magnitude, but also the phase angle between two different voltage levels. Transformers, who have the ability to control the phase angle between primary and secondary side are called phase-shifting transformers (PST). By using voltage magitude regulation, the reactive power flows can be controled. However, phase angle regulation can be used if the active power flows are to be controlled. Electricity market deregulation has given a significant role to PST's. PST, as an element of a power system, can be used to control power flows, therefore the power system containing such elements can provide its maximum efficiency. The use of PST's in the power system can also solve major problems that come together with deregulation of electric market, like power transit or uneven loading. The transmission network is used to transport power from producer to consumer, who have a concealed contract in which is stated that producer produces a certain amount of electrical energy and consumer buys this energy. Hence, the contractual path of the electricity is straight from producer to consumer. However, the physical path is a group of parallel paths, some of which lead through regions (countries) that are not involved in the contract. In a situation like this, uncontrolled power flows can occur in the transmission system of a region involved in the contract and overload its lines, when regions or paths not involved, are to be avoided. As for the uneven loading, it is necessary to state that the distribution of the power flow between two parallel lines is dictated by their impedances. The line with the smallest reactance carries the largest part of the load. In most situations, one of the two lines will be operating well below its nominal rating because otherwise the parallel line would be overloaded. Solution to problems like these is using the active power control. This is where the PST's have a significant role, because a phase angle regulation can be used to redirect active power flows and manage the loading of transmission paths, thus the losses in transmission network are minimal and the efficiency of such network is enhanced.

2. Voltage phase angle regulation 2.1. Principles od phase angle regulation Active power flow along a transmission line or transformer is determined mainly by the angle difference of the terminal voltages. It is also inversely proportional to the transmission line or transformer reactance which is placed between these two sides. Controling of active power flows can be made mainly by changing voltage phase angles and line reactances. Altering the voltage magnitudes affects significantly the reactive power flows and therefore it is not effective for active power flow control. Reactance can be altered by placing a series capacitor along the line to compensate the inductance of the line. Besides increased power flow, switching the capacitors at an appropriate time can be used to dampen oscillations. Flexible alternating current transmission systems (FACTS devices) can be used to alter the total line reactance very dinamically. The most common used method for effective active power flow control is a change of voltage phase angles. Because of their proportionality, the active power flow through the transmission line can be increased by adding the angle shift to the existing phase angle. This angle shift is controllable within certain limits. According to the angle between phase and adding voltage there are two types of phase angle regulation: phase angle and voltage magnitude regulation an angle between phase and adding voltage varies between 0 and 90 degrees phase angle regulation only an angle between voltages is 90 degrees Principles of both types of phase angle regulation, along with voltage magnitude regulation are shown in fig. 2.1.

Figure 2.1. Basic principles of regulation: a) voltage magnitude regulation; b) phase angle and voltage magnitude regulation; c) phase angle regulation only When a phase angle and voltage magnitude regulation is used, not only does a phase angle of a secondary voltage alter in comparison to the primary side, but there is an altering in magnitude of secondary voltage compared to the primary voltage also. This type of regulation can be obtained by connecting the end of one regulation winding in a series with previous phase, i.e. phase C voltage is added to the phase A voltage, as shown in fig. 2.1. Second type of phase angle regulation (phase angle regulation only) is a method of regulating the phase angle shift of a secondary voltage, where magnitudes of both voltages are equal. 2.2. Mathematical modelling of PST A per-unit model of ideal transformer with tap changing is used to describe the phase angle regulation [1]. This model is shown in fig. 2.2. Figure 2.2. Basic equivalent circuit of a PST for coupling between primary and secondary coils with both primary and secondary off-nominal turns ratio of and, in p.u. To describe the phase shift, the model of a transformer has to be provided with a complex turns ratio. Besides, the invariance of the product representing the apparent power across the ideal transformer requires the distinction to be made between the turns ratio for current and voltage:

The circuit shown in fig. 2.2 has a turns ratio of. Solving equations for terminal currents of the modified circuit one can get next relations: Therefore, the matrix of a general single phase admittance of a phase-shifting transformer model described above is: The network described in fig. 2.1 is not bilinear, as can be seen in an asymmetrical diagonal form in an admittance matrix described above. Hence, the equivalent circuit of a single phase shifting transformer is of limited value and the best way to describe this transformer is analytically by its admittance matrix. 2.3. General classification of phase-shifting transformers Phase-shifting transformers can be classified by these characteristics: - direct PST's are based on one 3-phase core. The phase shift is obtained by connecting the windings in an appropriate manner. - indirect PST's are based on a construction with two separate cores. One variable tap exciter (often called the booster) is used to regulate the magnitude of a quadrature voltage. Then the one series transformer is used to inject the quadrature voltage in an appropriate phase.

- asymmetrical PST's create an output voltage with altered phase and magnitude in comparison with an input voltage. - symmetrical PST's create an output voltage with altered phase compared to the input voltage. The magnitude of an output voltage remains unaltered. The combination of the first two types with the two last types described above results in 4 main categories of PST's: direct asymmetrical, direct symmetrical, indirect asymmetrical and indirect symmetrical PST's [2,3].

3. Phase angle regulation in Croatian power system Because of the role of electricity trade and transit between Southeast and Western Europe, a need for a phase angle regulation in Croatian power system appeared. A results of preliminary analysis have shown that the small change in phase angle has a significant impact on power flow between 400, 220 and 110 kv levels and, depending on a shift, energy exchange is expected in both directions. A PST was installed in TS Žerjavinec, where the operation of a phase angle regulation was expected to be most effective in satisfying the needs for controlling the trade and transit. Main task for this PST is controlling and redirecting power flows on 400, 220 and 110 kv voltage levels. Selection of a PST in TS Žerjavinec included observing the needs and thus searching for a most economical solution, not requiring significant increase in investment and spatial projects changing. 400 MVA autotransformer, with the ratio of transformation 400/231 kv and the possibility to alter both magnitude and phase angle, was selected. Voltage magnitude or phase angle regulation can be selected in the unloaded condition only. For the turns ratio lesser than two, it is better to choose the autotransformer [4]. It is easier, cheaper and has less losses. From the perspective of efficiency and investment, it has more advantages than two-winding transformer. The type of phase angle regulation was on-load tap changing with three-phase tap changer, where regulating winding has 25 possible tap positions with the regulation step of 16 bends, having overall 192 bends and is made in neutral point. Made in this way, a PST has a wanted impact on both HV and LV levels of the trasformer. However, this type of phase angle regulation is nonlinear, and regulation range is asymmetric, varying from -4.48 (negative phase angle shift) to +6.76 (positive phase angle shift) in the loaded condition. Voltage magnitude regulation selected for this transformer is also on-load tap changing, because of its flexibility and efficiency. For the possibility of adjusting both levels, a regulation in neutral point is selected. Autotransformer scheme is shown in fig. 3.1, and regulating winding is shown in fig. 3.2. By changing the position of three-phase switch shown in fig. 3.1 in the unloaded condition phase angle regulation can be selected instead of a voltage magnitude regulation.

A B C magnitude regulation phase angle regulation UA UB UC ma mb mc three-phase switch which selects a voltage magnitude or phase angle regulation in the unloaded condition regulating winding x y z a b c x Figure 3.1. Autotrasformer scheme with voltage magnitude and phase angle regulation Figure 3.2. Regulating winding scheme for PST in TS Žerjavinec When operating with a regulating winding, one can affect the turns ratio of both sides of the transformer, the HV and the LV side. The advantage of such operation is a possibility to alter voltages according to needs, whether it is positive or negative energy exchange (upper or lower switch position regarding the turns ratio). The type of regulating winding is reversible. 3.1. Voltage magnitude regulation in TS Žerjavinec Described autotransformer has the ability to alter voltage magnitude if a proper position of a three-phase switch is selected, as shown in fig. 3.1. When the tap changer switch is in upper position (the "u" designation on the fig. 3.2), number of windings is increased, the turns ratio is lowered, and the decreasing of the HV side voltage, or increasing of the LV side voltage is provided, depending on the type of transformation. Tap changer positions are from 13 to 25,

respectively, as shown in fig. 3.2. If the tap changer switch is in lower position, number of windings is decreased, the turns ratio is increased, thus the increasing of the HV side voltage, or decreasing of the LV side voltage is provided. Tap changer positions are from 1 to 13, respectively, as shown in fig. 3.2. According to this, positions 1 and 25 are ending positions, and position 13 is a neutral point position. When a descending transformation type is used, and a tap changer switch is in position 25 (designation "u"), the voltage magnitude is 91% of the HV side nominal voltage. If a tap changer switch is in position 1 (designation "d"), and a regulating winding is in a reversed state, with descending type of transformation, HV voltage magnitude is 115,5% of the nominal HV voltage magnitude. In ascending transformation type autotransformer is adjusting the voltage on a LV side. Tap changer position 25 therefore fits the LV voltage magnitude level on 109,9% of the nominal LV voltage magnitude, and a position 1 fits the level of 86,6% of the nominal LV voltage magnitude. Figure 3.3. Autotransformer scheme (phase A only) and phasor diagram, when a regulating winding is set to alter voltage magnitude, with the tap changer switch set on upper position UA EA EA A UA EmA UmA EmA -ErA UmA three-phase switch 1 tap changer switch d 13 ErA C B

Figure 3.4. Autotransformer scheme (phase A only) and phasor diagram, when a regulating winding is set to alter voltage magnitude, with the tap changer switch set on lower position Designations on the schemes and diagrams are: E A electromotive force inducting in the non-regulating HV winding of phase A E ma electromotive force inducting in the non-regulating LV winding of phase A E ra electromotive force inducting in the regulating winding of phase A E rc electromotive force inducting in the regulating winding of phase C U A voltage potential of the phase A terminal towards the earthing point (HV terminal) U ma voltage potential of the phase A terminal towards the earthing point (LV terminal) 3.2. Phase angle regulation in TS Žerjavinec By changing the position of three-phase switch shown in fig. 3.1, phase angle regulation can be selected instead of a voltage magnitude regulation. If a phase A is observed, regulating winding voltage of phase C is added to the phase A voltage. Resulting voltage is such that the voltage on the LV side of the transformer is moved to an angle φ, which is not angle due to load, but an angle shift due to phase angle regulation. If a tap changer switch is set on lower position (tap changer position of regulating winding is between 1 and 13) the angle will be negative. Autotransformer scheme for one phase and a phasor diagram are shown in fig. 3.6, when operating in negative phase angle shift mode.

Figure 3.5. Autotransformer scheme (phase A only) and phasor diagram, when a regulating winding is set to alter negative phase angle shift Setting the same switch on upper position (tap changer position is between 13 and 25) results in the positive phase angle. Autotransformer scheme for one phase and a phasor diagram are shown in fig. 3.6, respectively. Figure 3.6. Autotransformer scheme (phase A only) and phasor diagram, when a regulating winding is set to alter positive phase angle shift The advantages of a described PST are lower price compared to the PST with booster and regulating winding used for both types of regulation, which can provide descending and ascending transformation type depending on the regulating side of the autotransformer, HV side or LV side. The disadvantages include impossibility to alter the turns ratio when using the phase angle regulation and nonlinearity of neutral point position. When altering the positive phase shift to maximum (tap changer on position 25), the turns ratio matches the HV voltage of 416 kv (104% of U 1n ), if a descending transformation is observed. If, for some reasons the HV side voltage is much lower, phase angle regulation can be temporarily switched to voltage magnitude regulation. Nonlinearity of the neutral point position is manifested on the range of voltage magnitude regulation: from 15,5% to -9% with descending transformation type and from -13,4% to +9,9% with ascending transformation type. 4. Simulation results 4.1. Features of Croatian Transmission Network Geographical location and shape of Croatia influence the main features of the Croatian transmission network (fig. 4.1). One of the most important power corridors Heviz-Žerjavinec- Melina-Divača-Redipuglia connects Central and Eastern European power system with Italy, a

major importer of electric energy in the region. Other corridor Mladost-Ernestinovo- Žerjavinec represents the East-West connection between Eastern Europe (Bulgaria, Romania) and Western Europe (Slovenia, Italy). These two corridors are of great importance to the Southeast part of UCTE grid. Installed capacity of hydro and thermal power plants in Croatian power system is approximately the same, but their geographical distribution is not uniformed. Majority of hydro power plants are located in Southern part of the network, while thermal power plants are located in Central and Western part. This distribution of power plants has a major impact on the power flows in Croatian power system, but also in adjacent power systems. In the years of wet hydrology, majority of production is located in Southern part of Croatian power system, thus there is a large power flow through the 400 kv line Konjsko-Velebit-Melina. Another main characteristic of Croatian transmission system is a continuous power transit through interconnection lines Heviz-Žerjavinec and Mladost-Ernestinovo in direction East- West. Based on previous considerations it can easily be concluded that Transformer Station (TS) Žerjavinec with transformation levels 400/220 kv and 400/110 kv has a very important role in Croatian power system [5,6].

Figure 4.1. 400 kv and 220 kv transmission network of Croatian and adjacent power systems 4.2. Numerical examples Effect of phase-shifting transformer 400/220 kv installed in TS Žerjavinec was analyzed for a real situation in Croatian power system as it was this winter. The total consumption of Croatian power system was in that case 2850 MW, which is very close to the maximum load of about 3100 MW. The own production was 2150 MW and the rest (about 760 MW) has been imported from Eastern Europe through Hungary, Serbia and Bosnia and Herzegovina. The difference between total consumption and production with imports was the power losses in Croatian network (about 60 MW). In the observed case, the transit from Southeast Europe to Italy, which closes over the Croatian transmission network was about 600 MW. For the analysis of power flows and the impact of voltage angle regulation in TS Žerjavinec, the entire Croatian power system and 400 kv and 220 kv parts of adjacent power systems were modeled. The active power flows of the network in the immediate vicinity of TS Žerjavinec are shown in fig. 4.2. In this case, phase-shifting transformer was used for voltage magnitude regulation and its tap changer was in the middle position (13), which means the nominal turns ratio. This initial case, which is the basis for all further analysis is marked as Case 0. In order to determine the impact of voltage angle control, the transformer is transferred in voltage phase angle regulation mode and its tap changer is set at the upper end position (25) which corresponds to a positive angle of the 6.76 in unloaded condition. This variant is marked as Case 1 and the results of load flow calculation are shown in fig. 4.3. In the Case 2 the transformer tap changer is set at the lower end position (1) which corresponds to a negative angle of the 4.48 in unloaded condition and results are shown in fig. 4.4. From the given results it can be concluded that changing of transformer s turns ratio redistributes active power flows between 400 kv network and 220 kv and 110 kv network. In the Case 1, when tap changer is set at the upper end position, active power flow through phase-shifting transformer is increased for about 140 MW in direction from 400 kv bus to 220 kv bus, compared to the Case 0. Unlike the previous case, in the Case 2, when tap changer is set at the lower end position active power flow through phase-shifting transformer from 400 kv bus to 220 kv bus is decreased for about 100 MW compared to the Case 0. Based on the obtained results, it can be concluded that the voltage angle change of 1 in the unloaded condition causes a change of active power flow through the phase-shifting transformer to approximately 20 MW.

If the active power losses are compared for all three analyzed cases, it can be seen that changing of transformer s turns ratio does not affect significantly the amount of losses. In the Case 0, without the voltage phase angle shift, the total active power losses in Croatian transmission network are 62.8 MW and in the other two cases (Case 1, Case2) total active power losses are 63.6 MW and 64.2 MW, respectively. Since the changing of phase-shifting transformer s turns ratio also affects the reactive power flows in the surrounding network, active power losses are increased. To reduce these losses, turns ratio of the other transformers should be coordinated with phase-shifting transformer s turns ratio. It is the task of voltage magnitude and reactive power optimization but it is not a subject of this papers. Figure 4.2. Active power flow for Case 0, TAP position 13 (angle 0 ) NE Krško Cirkovce 700 MW 400 kv 220 kv 350 Tumbri 400 kv Slovenia 342 West Croatia 3x300 MVA Heviz 400 kv Hungary 220 260 266 214 400 kv 182 257 238 110 kv Network (Zagreb) 400 MVA Žerjavinec 2x300 MVA 110 kv 220 kv 95 3x150 MVA 98 159 32 25 Southern Croatia Ernestinovo 57 400 kv Bosnia and Herzegovina Mraclin 220 kv Serbia Eastern Croatia Bosnia and Herzegovina Figure 4.3. Active power flow for Case 1, TAP position 25 (angle +6.76 )

Figure 4.4. Active power flow for Case 2, TAP position 1 (angle -4.48 ) 5. Conclusion Phase-shifting transformers can be effectively used in electric energy transport, when used for redirection of active power flows. PST in TS Žerjavinec has proven useful in controling the active power flows in corridors placed in Southeast part of UCTE grid, thus guarding transmission assets from unscheduled use and unwanted overload. Employing the economical aspect, technical advantages and disadvantages, the autotransformer selected to operate in given conditions has proven to be the efficient solution in Croatian power system. Its possibilites to alter voltage magnitude and phase angle shift have met the needed requirements, and the advantages exceed the disadvantages of this installed autotransformer. References [1] J. Arrilaga, C. P. Arnold, "Computer Analysis of Power Systems", John Wiley & Sons Ltd, England, September 1994. [2] J.Verboomen, D. Van Hertem, P. H. Schavemaker, W. L. Kling, R. Belmans, "Phase Shifting Transformers: Principles and Applications", IEEE, June 2005. [3] J.H. Harlow et al., "Electric power transformer engineering", CRC Press LLC, USA, 2004.

[4] T. Kelemen, B. Ćućić, "Three-phase autotransformer 400 MVA, 400/231/(10,5) kv with voltage regulation in neutral point for TS Žerjavinec", Končar - Electrical Engineering Institute, Zagreb, February 2003. [5] S. Tešnjak, I. Pavić, "Load flow calculation with phase-shifting transformer 400/220 kv in TS Žerjavinec", FER, Zagreb, March 2003. [6] G. Jerbić, "Application of Phase-shifting Transformers in Croatian Power Supply System ", Energija Journal of Energy, vol. 56 (2007), no. 02/07, HEP d.d. Energija, Zagreb, May 2007., pp 216-231