Page 1 of 5 Application Engineering Note Proc. 001 Interlock Armor and Corrugated Steel Tape Cables Pulling Grip Installation Procedure Rev.

Similar documents
14 AWG 2 AWG: 600 Volt

C-L-X ARMOR REMOVAL PROCEDURES

Fiber Splice Box (FSB-D) Installation Instructions

Ø 1250 * 688 mm 93 kg ± 105m

TONGFENG FLEXIBLE CONDUIT TONGFENG FLEXIBLE CONDUIT

features and benefits

Technicians of Terror. This is the air valve we make to use with our air

UPC-LL Power Connection Kit

MIL-STD B (SH) UPDATE

Instructions for Preparing AFL OPTICAL GROUND WIRE CABLE (ALUMACORE CABLE DESIGNS) FOR BPA

Datasheet Outside Plant Cable

GUXW. Mini-Breakout Cables (Distribution) Universal Indoor/ Outdoor, Steel Wire Armor (SWA) A/I-VQ(ZN)HBH Full Rodent Protection v5.

HES HACILAR ELEKTRİK SANAYİ VE TİC.A.Ş.

Times Microwave Systems Hermetically Sealed Assemblies

Fiber Optic Outside Plant Cables (4-144 Fibers)

Loose Tube Cable End Preparation for Splicing For Series 11D, 1GD, 12D, 1AD, 1DD, 1CD, 11, 1G, 12, 12L, 1A, 1D, 1C, 1NY, 13, 1H, HZD and HZA

Flex Fence Instruction Manual

UNITED STATES MARINE CORPS PROGRAM MANAGER INFANTRY COMBAT EQUIPMENT (ICE) 2200 LESTER STREET QUANTICO, VIRGINIA

Optical Cable Entry Facility (OCEF) Installation Instructions

Stair Mounting Kit. Installing safety gates in modern homes can be very challenging, especially for stairs.

Instruction Manual. Banner Grip -banner stretching frame. Manual Version Sept27, Any size made: by Graphic size, OD Size, Live Area -1 or 1,000!

Single-Armored Cables, Fibers

Spiderbeam Balun Construction Guide

NAIMA. Insulation Between (filling) Purlins and Over Purlins. What Does Metal Building Insulation Do? Installation Instructions for New Construction

Constructing Wire Fences

Installation Instructions. for AFL Dead Ends Installed on. CTC Composite Core Conductor

Instruction Manual. Banner Grip -banner stretching frame. Manual Version Feb 14, Any size made: by Graphic size, OD Size, Live Area -1 or 1,000!

Installation Instructions for New Construction. Installation Instructions for New Construction

Water Line and Water Line Assembly Gasket

Jabiru Installation instructions

ALTOS Lite Gel-Free, Single-Jacket, Single-Armored Cables, Fibers

Shannon s CCR Spiral Tree

Stub Height Uses: Number to use for bender take-up.

Read Below! Read Below! Read Below! Read Below! Read Below! Read Below! STOP READ TIPS BELOW TO MAKE ASSEMBLY MUCH EASIER

Required and optional* components/fastener torque spec

400A 40113V, 401A 40120V, & 401AL 40120VL ALUMINUM VERTICAL 4000 LB LIFT INCLUDES SCREW LEG ASSEMBLY INSTRUCTIONS

12'W x 10'H RoundTop Frame Assembly Please read and understand instructions completely before assembly.

VSOF-BS403A. Splice Closure for Fiber Optic Cable User Manual Rev.3

1.0 Tool Components and Operation Instructions

0200 Half Slotted Container (HSC) Same as Regular Slotted Container (0201) without one set of flaps.

Termination of D-621 Triaxial Connectors to Shielded Twisted Pair Cable for MIL-STD-1553B Applications

Women's Travel Toiletry Bag

OWNER'S MANUAL Issue 2 - December 14, 2000

ELK EXCLUSION USING WOVEN WIRE FENCING

Pack Mount Instructions:

K20 & L120 LSZH Armoured F/FTP Cat6 Cables

TABLE OF CONTENTS 7.0 CABLE INSTALLATION IN UNDERGROUND STRUCTURES

Set Part # Rev

Installation Instructions. for AFL Compression Joint Installed on. CTC Composite Core Conductor

Mount to the Wall INSTALLATION MANUAL

User Guide. 7ft x 10ft JumpPOD Oval

ClampStar Safe-T-Link Tether Installation Instructions for Deadends

Cable Hanging Instruction Manual

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

FIBERLIGN Suspension: Double & Spread Double

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Make your railing view friendly with the original stainless steel cable infill for wood, metal, and composite-sleeved wood railing.

Ground / Jumper Assembly Tester Catalog No. 6714

Read Below! Read Below! Read Below! Read Below! Read Below! Read Below! STOP READ TIPS BELOW TO MAKE ASSEMBLY MUCH EASIER

APPENDIX A, UMC STANDARD 6-5 STANDARD FOR INSTALLATION OF FACTORY-MADE AIR DUCTS

Arched Top Lantern Pendant Assembly and Installation Instructions. Country of Destination: US/CN UK/EU/AUS Middle East

USG Structural Solutions USG STRUCTURAL PANEL CONCRETE SUBFLOOR REPAIR MANUAL. usg.com

How to Install EZ Snap Window & Skylight Shades

INDUSTRIAL ETHERNET CABLING SOLUTIONS. Control. Monitor. Process.

Termination for M29504/4, /5, /6 & /7, Style 2 (Tight)

SYSTIMAX 360 ipatch G2 Fiber Shelf with Faceplate Instructions

CORNING OPTICAL COMMUNICATIONS GENERIC SPECIFICATION FOR FlexNAP DISTRIBUTION SYSTEMS: DISTRIBUTION TRUNK, TAP, AND TETHER. July 2018.

Optical Ground Wires (OPGW)

1.0 Tool Components and Operation Instructions

Assembly Instructions Beta Prusa Standard & Deluxe

SKDG Cable Repair Kit Instructions

SYSTIMAX 360 ipatch Fiber Shelf with Faceplate Instructions

INSTALLATION RECOMMENDATIONS For The Con-Tech ODYSSEY Line Voltage Flexible Track System

Nash Chandelier Assembly and Installation Instructions

3,500/4,500lb. Vertical Cable Feighner Lift

Instructions for Prepping an Opening for SOSS Invisible Hinges

COMPONENTS INSTALLATION

ATLANTIS RAIL HandiSwage Installation Instructions ATLANTIS RAIL Contact Information Atlantis Rail Systems November, 2013

22'W x 13'H Peak Style Shelter Frame Assembly Instructions

N Male Right Angle Connector Clamp/Solder Attachment For 1/2 inch Annular, 1/2 inch Flexible, PE-1/2FAC. Cable Attachment Method (Shield/Contact)

DAEDALUS TECHNOLOGIES, INC. MAKING TECHNOLOGY MORE ACCESSIBLE

INSTALLATION TORSION SPRING FRONT OR REAR MOUNT LOW HEADROOM. 1 Cutting Vertical Track. 2 Fully Adjustable Jamb Brackets

BOB SLAY (assembly instructions)

KINECTRICS NORTH AMERICA INC. TEST REPORT FOR 3M TO DETERMINE THE SHEAVE CRITERIA FOR 774 KCMIL 3M TM COMPOSITE CONDUCTOR

Handle Length (in.) Ultimate Load (lbs.) Weight Each (lbs.)

Required and optional* components/fastener torque spec

CIRRUS AIRPLANE MAINTENANCE MANUAL

Ford Ranger / Bronco II Set Part # Rev B 5-04

Procedure for Constructing Housings for Passive Field Sampling

ADV. BEGINNER. Measures: 10x6x6.5H. Materials

R/L, AND LXE TYPE CABLE

INSTALLATION INSTRUCTIONS Small Flat Panel Mounts Model: F-Series

GAAG. Multi Loose Tube Cables Outdoor - ADSS A-DQ(ZN)2Y(T) v4.0. Ordering Information. Applications. Features & Benefits

Assembly Instructions: Bencher Skylark

Clearview Railing System Installation Instructions

How is vacuum measured? Vacuum is measured in inches of mercury. Our atmosphere will support a column of mercury 30 inches tall.

INSTRUCTIONS for fire lamps 1-8

3M No Polish SC/APC Angle Splice Connector Jacket for 2 x 3 mm FRP and 1.6 to 3.0 mm Cable 8802-T/APC/AS/1.6-3

Bounce Back How to install Plastic Coated Wire Fencing

Before returning this product to the store of purchase

Transcription:

Page 1 of 5 Scope: The scope of this procedure is to describe how to properly install a cable pulling grip on an Optical Cable Corporation interlocked armor (ILA) and corrugated steel tape (CST) fiber optic cable. Procedure: Optical Cable Corporation recommends using pulling grips, with or without swivel eyes, for all ILA and CST cables and using a breakaway swivel rated for the proper installation tensile load of the cable being installed. CAUTION: For interlocking armor cables (ILA), the installation tensile load must not exceed 300 lbs. Furthermore, the minimum bending radius during installation is greater for the interlocking armor cable (ILA) than for the inner cable. The pulling grip should be sized appropriately for the diameter of the cable. Kellems pulling grips are recommended. Listed below are the model numbers for the Kellems pulling grips with and without the swivel eyes and the corresponding cable diameters. Optical Cable Corporation recommends measuring the length of the grip (See Figures 1 & 2). Figure 1: Measure Pulling Grip Kellems Model # Cable Diameters With Swivel 033291007.10 -.22 inches 033291008.21 -.35 inches 033291009.32 -.48 inches 033291010.42 -.61 inches 033291011.53 -.74 inches 033291012.64 -.87 inches Without Swivel 033291193.10 -.22 inches 033291194.21 -.35 inches 033291195.32 -.48 inches 033291196.42 -.61 inches 033291197.53 -.74 inches 033291198.64 -.87 inches 033291199.75-1.00 inches When preparing an ILA or CST cable for pulling into a duct or tray, care must be taken to properly attach the pulling grip to the cable. Figure 2: Measure Pulling Grip Take the length measurement of the grip and multiply that number by either 1.5 or 1.75 in order to get the distance to cut back the ILA or CST (See Figure 3). Mark the cable at this location and remove this section of the ILA or CST. The extra distance takes into the account the length of the strength element needed to overlap the armor (see Figure 11).

Page 2 of 5 The larger the multiplier (1.5 to 1.75), the more the grip will overlap the inner cable and not the armor. The tensile strength of the cable is in the strength elements in the inner cable. The goal is to have approximately 75% of the grip attaching to the inner cable with approximately 25% of the grip attaching to the ILA or CST. This procedure allows the inner cable to take most of the tensile load. From the mark on the inner cable, measure the length of the grip and apply friction tape, 3M 88T Electrical Tape, or a suitable substitute (See Figures 5 & 6). 25% of this length measurement should include the ILA or CST. Make sure that this is correct. The tape should create a smooth diameter change from the inner cable to the interlocked armor. In some cases, the diameter of the inner cable may be notably smaller than the diameter of the outer cable. The diameter of the inner cable may need to be increased to couple well to the pulling grip. To increase the diameter, apply several wraps of tape to build up the diameter of the inner cable. Choose a tight fitting grip to reduce potential of loose fit over the inner cable. Figure 3: Measure Armor 1.75 times the length of the grip Once the ILA or CST has been removed, lay the grip beside the inner cable and mark the inner cable at the end of the grip (See Figure 4). Figure 5: Measure the length of the grip from the mark on the inner cable. 25% of length should include the ILA or CST Figure 4: Mark inner cable at end of grip

Page 3 of 5 protruding cable should be removed (See Figure 8). Figure 6: Apply tape from mark on inner cable to measured distance of the grip. At least 25% of the distance should cover the ILA or CST The grip should then be inserted onto the coupled cable assembly that is covered by the tape. The excess length on the inner cable should pass through the end of the grip up to where the tape wrap starts (See Figure 7). Figure 8: Outer jacket of inner cable is removed, exposing the strength elements and buffers The strength elements should be separated from the buffers and central strength member (See Figure 9). Figure 7: Pulling grip is inserted onto the cable assembly Once the coupled cable assembly has been inserted into the pulling grip, the jacket on the Figure 9: Strength elements separated from buffers and central strength member Cut off the excess buffers and central strength member leaving only the strength elements (See Figure 10).

Page 4 of 5 Figure 10: Strength elements The strength element should then be folded back onto the grip OR the strength element can be separated into two halves and placed 180 degrees apart (See Figures 11 & 12). If separated in two halves, the strength elements will require running one half of the strength elements back through the pulling grip mesh. Figure 12: Strength elements separated in halves separated 180 degrees. When the strength element has been folded back onto the grip or if the strength elements have been separated 180 degrees apart, 3M 88T Electrical Tape or a suitable substitute is then applied over the strength elements and grip (See Figure 13). Figure 11: Strength elements separated in halves. Figure 13: Tape applied over strength elements and pulling grip.

Page 5 of 5 A breakaway swivel should then be installed on the pulling grip before the cable is pulled. Optical Cable Corporation strongly recommends using a breakaway swivel on all pulling grips, whether the pulling grips have or do not have a swivel eye. The breakaway swivel must be rated no more than the maximum installation tensile load of the cable. CAUTION: For interlocking armor cables (ILA), the installation tensile load must not exceed 300 lbs. Once the cable has been installed, remove the pulling grip and cut off at least 3 feet of the end of the cable where the pulling grip was attached. ILA with Steel: Typical interlocking armor cables are made with aluminum. However, steel can be used as well and still maintain the mechanical, environmental, and UL ratings of a cable that uses aluminum for the armor. The pulling grip procedure listed above is still applicable for either aluminum or steel interlocking armor. However, it should be noted that a steel interlocking armor cable weights more than an aluminum interlocking armor cable. When installing an interlocking armor cable with steel, it is important that the cable tension should be monitored, with or without a breakaway swivel. If you have any questions, please contact the Optical Cable Corporation s Engineering Department at (540) 265-0690.