TEST REPORT IEC Uninterruptible power systems Part 3: Method of specifying the performance and test requirements

Similar documents
Amendment to Test Report

TEST REPORT IEC Electromagnetic Compatibility (EMC)

TEST REPORT IEC Audio, video and similar electronic apparatus - Safety requirements

TEST REPORT IEC Safety of Transportable Motor-Operated Power Tools

TEST REPORT DIN V VDE V :2006 Automatic disconnecting device

Technical Data Sheets

TEST REPORT IEC Information technology equipment Safety Part 1: General requirements

TEST REPORT IEC Information technology equipment Safety Part 1: General requirements

TEST REPORT IEC Information technology equipment Safety Part 1: General requirements

TEST REPORT IEC Low-voltage switchgear and controlgear - Part 2: Circuit-breakers

TEST REPORT. IEC DC or AC supplied electronic control gear for LED modules Performance requirements

TEST REPORT IEC Information technology equipment Safety Part 1: General requirements

TEST REPORT IEC60950_1F. Information technology equipment - Safety - Part 1: General requirements

TEST REPORT IEC Safety of laser products - Part 1: Equipment classification and requirements

TOSHIBA International Corp

IfYcSXY]W!F^fUa!Id [h! IUU!FQWU!,! IB!FEM;H!;B;8JHED?8I!

Technical Data Sheet. Uninterruptible Power Supply On-line VH Series UPS. Critical Power UL / 208V

TECHNICAL DATA SHEET B9600FXS kva

Page 2 of 69 VDE Report No.: / DC - DC Converter for building in. TDK Innoveta Inc. iba - Series (see model matrix appendix 1)

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

TEST REPORT IEC Information technology equipment - Safety - Part 1: General requirements

IfYcSXY]W!F^fUa!Id [h! IUU!FQWU!,! IB!FEM;H!;B;8JHED?8I! 8J<!IcQWU!+!

CB Testing Laboratory...:EZÚ Address...:Pod Lisem Praha71-Trója Testing location/ procedure...: CBTL RMT SMT WMT TMP IEC60947_2C

TEST REPORT IEC Information technology equipment - Safety - Part 1: General requirements


TEST REPORT IEC Information technology equipment - Safety - Part 1: General requirements

Gutor PxW AC UPS Designed for North American Market

page 2 of 86 Report reference No:

ETSI EN V1.2.1 ( )

UL International Demko A/S

ZITARES NCD FX-30 Non-SELV (isolated), constant current control gear, 1-channel, dimmable

Report no GZU-001. Growatt 30000TL3-S, Growatt 30000TL3-SE. Max. input current: 34A/34A 38A/38A

TEST REPORT IEC Adjustable speed electrical power drive systems Part 5-1: Safety requirements Electrical, thermal and energy

TEST REPORT IEC : 2005 (2nd Edition) and/or EN :2006 Information technology equipment Safety Part 1: General requirements

GESS Industrial UPS System. Overview

TEST REPORT IEC Safety requirements for electrical equipment for measurement, control, and laboratory use Part 1: General requirements

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM

ZITARES NCD FX-30 Non-SELV (isolated), constant current control gear, 1-channel, dimmable

TEST REPORT EMC. 1, Mikhaila Kotzubinskogo St., Kyiv, Ukraine, IECCISPR14_1&2_IEC61000_3_2&3B

DE Total. American Inc. IEC Test Report Form. If this. and appended to General disclaimer: the NCB, VDE File. No VDE File.

UL International Demko A/S

Page 1 of 28. Ingo Röhr. Frank Hesmer

TEST REPORT IEC Information technology equipment - Safety - Part 1: General requirements

StatiVolt. Inverter UPS Systems. Features. Contents

PROTECT 8 INDUSTRIAL UPS. Protect 8.31 Single Phase output 10 kva 80 kva. Protect 8.33 Three Phase output 10 kva 120 kva. Engineering is our business

TEST REPORT IEC Information technology equipment - Safety - Part 1: General requirements

Australian Standard. Electricity metering equipment (AC) Particular requirements. Part 22: Static meters for active energy (classes 0.2 S and 0.

Orbital GFI Inverter Series

TEST REPORT IEC Information technology equipment Safety Part 1: General requirements

MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS

ZITARES CCD FX-20 25W SELV (isolated), adjustable functions and current, 1-channel, dimmable

Liebert Hipulse-U. Fully Digital Dual DSP Controlled Transformer Based UPS

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

MINI-PS AC/24DC/1.3

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL

TS RES - OUTSTANDING ISSUES

IGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards

TEST REPORT IEC Information technology equipment Safety Part 1: General requirements

Est Static Frequency Converter. SFX 10kVA - 10MVA

NEMA Standards Publication ICS Adjustable Speed Electrical Power Drive Systems

QUINT-PS/ 3AC/24DC/10

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

TEST REPORT IEC Information technology equipment - Safety - Part 1: General requirements

ETSI TS V1.3.1 ( )

TEST REPORT IEC Information technology equipment Safety Part 1: General requirements


PRODUCTS FOR ELECTRICAL SUB-STATIONS UPS, DC-AC INVERTERS, BATTERY CHARGERS, DC-DC CONVERTERS, 1-PHASE TO 3-PHASE CONVERTERS

ZITARES LCS Non-SELV, Constant current control gear, 1-channel, non-dimmable

MERLIN GERIN KNOW HOW. THM filtering and the management of harmonics upstream of UPS

LED Driver Linear / area fixed output

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO E

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

Auftrags-Nr.: Order No.:

High precision measurement system for current and voltage IHC-A/B-RM01/03

TEST REPORT IEC Safety requirements for electrical equipment for measurement, control, and laboratory use Part 1: General requirements

CB TEST CERTIFICATE. Uninterruptible Power Supply. Additional Information on page 2 BK500...

TEST REPORT AS :2005 and AS :2005 Grid connection of energy systems via inverters Grid protection requirements

QUINT-PS AC/24DC/40

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

MODULAR DC POWER SUPPLIES & SYSTEMS. DC Power Systems DC/AC Inverters Static Switches DC/DC Converters. GAMATRONIC, A SolarEdge Division

NAME OF (VENDOR/MANUFACTURER) Clause No. Clause Description Comments, if any Remarks, if any

Output Voltage* (nom.)(adjustable)

ZITARES CC Constant current control gear, 2-channel, dimmable

STATIC UNINTERRUPTIBLE POWER SYSTEM Revised 4/30/ Electrical Systems

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors.

LED Driver Constant voltage

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

QUINT-PS/ 1AC/24DC/20

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

UNINTERRUPTIBLE POWER SUPPLY SPECIFICATIONS MODEL 1100B SERIES

UNO-PS/1AC/24DC/150W. Primary-switched power supply unit. Data sheet. 1 Description

TEST REPORT IEC Information technology equipment - Safety - Part 1: General requirements

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

MINI-PS AC/2X15DC/1

ZITARES NCD 2 nd Generation Non-SELV, constant current control gear, 1-channel, dimmable

Page 2 of 8 Report No.:

Type CP-S, CP-C & CP-A Switch mode

Transcription:

Test Report issued under the responsibility of: TEST REORT IEC 62040-3 Uninterruptible power systems art 3: Method of specifying the performance and test requirements Report reference No...: 11-EL-0026.06 Date of issue...: 2012-07-05 Total number of pages...: 48 CB Testing Laboratory...: Address...: Applicant s name...: Electrosuisse Luppmenstrasse 1, CH-8320 Fehraltorf Switzerland Newave SA STS 001 Address...: Via Luserte Sud 9, 6572 Quartino, Switzerland Test specification: Standard...: Test procedure...: Non-standard test method..: Test Report Form No...: Test Report Form(s) Originator...: IEC 62040-3 (1 st Edition):1999 CB Scheme N/A IEC62040_3A Electrosuisse Master TRF...: Dated 2011-05 Copyright 2010 Worldwide System for Conformity Testing and Certification of Electrotechnical Equipment and Components (IECEE), Geneva, Switzerland. All rights reserved. This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's interpretation of the reproduced material due to its placement and context. If this Test Report Form is used by non-iecee members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall be removed. This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02. Test item description...: Newave US System Trade Mark...: Manufacturer...: Model/Type reference...: Ratings...: Newave Newave SA, Via Luserte Sud 9, 6572 Quartino, Switzerland Model: owerscale Type: 2S 0262 Cab.C Input: 3N400/230V~E, 75.9A, 35-70Hz Output: 3N400/230V~E, 45kW, 50kVA, 72.2A, 50Hz

age 3 of 48 Report No. 11-EL-0026.06 List of Attachments (including a total number of pages in each attachment): See basic test report No: 11-EL-0026.04 Summary of testing: The equipment complies with this standard. Tests performed (name of test and test clause): Complete test performed Testing location: Newave SA Via Luserte Sud 9, CH-6572 Quartino Summary of compliance with National Differences List of countries addressed: EN 62040-3:2001 + A11:2009 Copy of marking plate The artwork below may be only a draft. The use of certification marks on a product must be authorized by the respective NCBs that own these marks. Copy of marking plate see basic test report 11-EL-0026.04 detailed information to other models stated in basic test report 11-EL-0026.04

age 4 of 48 Report No. 11-EL-0026.06 Test item particulars...: Classification of installation and use...: Class I and indoor use Supply Connection...: Terminal provided...: ossible test case verdicts: - test case does not apply to the test object... : N/A - test object does meet the requirement... : (ass) - test object does not meet the requirement... : F (Fail) Testing... : Date of receipt of test item... : 2011-06-06 Date (s) of performance of tests... : 2011-06-06 to 2012-07-05 General remarks: The test results presented in this report relate only to the object tested. This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory. "(see Enclosure #)" refers to additional information appended to the report. "(see appended table)" refers to a table appended to the report. Throughout this report a comma / point is used as the decimal separator. Manufacturer s Declaration per sub-clause 6.2.5 of IECEE 02: The application for obtaining a CB Test Certificate includes more than one factory location and a declaration from the Manufacturer stating that the sample(s) submitted for evaluation is (are) representative of the products from each factory has been provided...: Yes Not applicable When differences exist; they shall be identified in the General product information section. Name and address of factory (ies)...: CMA Electronics Srl Via Guiseppe de Vitorio 3 20020 Arconate Italy General product information: owerscale is a transformerless Uninterruptible ower System (US). It is a true online, continuous duty, double conversion, solid state, three-phase system, providing conditioned and uninterruptible AC power to protect the customer s load from all nine power failures.

age 5 of 48 Report No. 11-EL-0026.06 IEC 62040-3 Clause Requirement Test Result Remark Verdict 5 ELECTRICAL SERVICE CONDITIONS AND ERFORMANCE 5.1 General 5.1.1 Complies with annexes A, B and C 5.1.2 Equipment ratings and instructions 5.1.2.1 Rating information Input supply requirement Output ratings Rated voltage(s) or Voltage range(s): 3N400/230V Symbol for the nature of supply: Rated frequency or frequency range: 35-70Hz Rated current: 75.9A Number of phases: 3 + N Rated output active power: 45kW Rated output apparent power: 50kVA Stored energy time Manufacturer s name, trademark or identification mark Tested without battery, battery is an option Newave Model or type reference 2S 0262 Cab-C Symbols comply with ISO 7000 and IEC 60417 5.1.2.2 Safety instructions and documentation Competence necessary for installation: a) operator installable N/A b) service personnel installable User manual, chapter 1.2.7 Competence necessary to operate the US: a) no precious experience N/A b) with previous training Disconnecting device not incorporated in the US Disconnecting device is incorporated in the US a) permanently connected US b) pluggable US N/A Warning label for pluggable US-type B and permanently connect US without automatic backfeed isolation No pluggable US 5.1.3 Equipment safety 5.1.3.1 US designed for use in operator accessible areas and/or operator installable 5.1.3.2 Additional protection for pluggable US-type A N/A N/A N/A N/A N/A N/A

age 6 of 48 Report No. 11-EL-0026.06 IEC 62040-3 Clause Requirement Test Result Remark Verdict 5.1.3.3 Backfeed protection switching device See UM chapter 10.9 and sub-clause 6.3.11 5.1.3.4 luggable US-type B and permanently connected US ermanently connected US 5.1.3.5 US designed for use in electrical switch rooms N/A 5.2 US input specification 5.2.1 Normal service conditions: a) Input voltage variation: +/- 10% b) Input frequency variation: +/- 2% c) three phase input d) input voltage distortion factor : THDu < 2% at 100% load 5.2.2 Rated values and characteristics: See User Manual, chapter 10.3 a) Rated a.c. input voltage: 400/230V b) AC input voltage tolerance: -23% /+ 15% c) Rated input frequency: 35-70Hz d) input frequency tolerance: (calculated: - 30% / + 16%) e) Number of phases: 3 ph + N f) Rated input current: see UM, chapter 10.3 g) Max. continuous input current: see UM, chapter 10.3 h) input current total harmonic distortion: (see appended table) i) Input current individual harmonic current levels j) max input current: N/A k) Input power factor: See UM, chapter 10.3 l) Input neutral requirements: N/A m) Inrush current requirements See UM, chapter 10.3 n) Earth leakage current N/A o) Three phase inputs p) ower system configuration 5.2.3 US input conditions to be identified by the purchaser: a) Supply impedance and system configuration b) Voltage in excess N/A c) Frequency in excess N/A d) Superimposed high-frequency voltages N/A e) Existing voltage harmonics N/A f) Transient voltage N/A g) rotective device characteristics N/A h) Requirements for all-pole isolation N/A i) Stand-by generator characteristics N/A

age 7 of 48 Report No. 11-EL-0026.06 IEC 62040-3 Clause Requirement Test Result Remark Verdict 5.3 US output specifications 5.3.1 Steady-state and dynamic output voltage characteristics -a) Change of operating mode -b) Application of increasing/decreasing load step 5.3.1.1 Output characteristic- Sinusoidal output voltage 5.3.1.2 Output characteristic- Non-sinusoidal output voltage N/A 5.3.2 Following rated values and characteristics shall be specified in all modes of operation by the manufacturer/supplier (if applicable): See User Manual, chapter 10.5 a) Rated output voltage: See UM chapter 10.5 b) Output voltage tolerance: See UM chapter 10.5 c) Number of phases: 3 d) Rated output current (linear load): See UM chapter 10.5 e) Rated output current (non-linear load) See UM chapter 10.5 f) Nominal frequency: See UM chapter 10.5 g) Max relative harmonic: See UM chapter 10.5 h) Maximum synchronized frequency range: See UM chapter 10.5 i) US nominal inverter frequency: See UM chapter 10.5 j) Rate of change of frequency: See UM chapter 10.5 k) ermissible load unbalance: See UM chapter 10.5 l) Relation between load unbalance und voltage unbalance See UM chapter 10.5 m) hase angle displacement tolerance: See UM chapter 10.5 n) ermissible range of load power factor: See UM chapter 10.5 o) Output voltage transient deviation: N/A p) US efficiency of rated load: See UM chapter 10.5 q) US output fault clearing capability: See UM chapter 10.5 r) Overload capability: See UM chapter 10.5 s) Current limit identification: See UM chapter 10.5 and UM 10.12.2 5.3.3 Single US and parallel US with bypass Ratings shall be in accordance with 5.3.2 and in addition, the ^following shall be added for the transfer switch: See user manual a) Transfer switch voltage rating: See user manual b) Continuous current rating: See user manual c) load power factor: See user manual d) Interruption time rating: See user manual e) Total system transfer time and interruption time: 0s

age 8 of 48 Report No. 11-EL-0026.06 IEC 62040-3 Clause Requirement Test Result Remark Verdict f) Rated US output fault clearing capability no bypass: g) Output voltage transient deviation and recovery time on transfer: short circuit capability (no bypass) UM chap. 10.5 up to 3 * In for 40ms 5.3.4 erformance requirements to be identified by the purchaser The purchaser shall identify any special US performance requirements if these deviate form 5.3.2 and 5.3.3 a) Max. load step and load profile versus time: N/A b) A load which is not balanced between phases: N/A c) Loads generating harmonic currents: THDi < 3% d) Loads generating circulation of a d.c. current: N/A e) Earth conditions of the output neutral required: See UM, chapter 1.5.1 f) rotective device(s) characteristic with which the US output is required to co-ordinate: See UM, chapter 10.5 g) Type of load(s) to be connected: Linear and non-linear load h) Output relative harmonic content: With linear load: < 2% with non-linear load: < 4% 5.3.4.1 Special performance requirements the following items should be specified by the purchaser: a) Output voltage stabilization and phase angle tolerance a) Output voltage stabilization and phase angle tolerance See UM, chapter 10.5 b) Frequency stability c) Synchronization and rate of change of frequency during synchronization d) Efficiency e) Load distribution f) Future extension N/A g) Degree of redundancy Full with redundancy (DA decentralize parallel architecture) h) Output overvoltage protection Electronic protection and IA2 5.4 US intermediate d.c. circuit and/or battery circuit specification Rated value and characteristics specified by the manufacturer/supplier (if applicable): See UM, chapter 10.4 a) Nominal d.c. voltage: See UM, chapter 10.4 b) Nominal d.c. currant: See UM, chapter 10.4 c) Isolation of d.c. link: N/A d) Earth conditions of d.c. link: See UM, chapter 1.5 e) Type of batteries: VRLA or NiCd N/A

age 9 of 48 Report No. 11-EL-0026.06 IEC 62040-3 Clause Requirement Test Result Remark Verdict f) Number of batteries and Ah rating: See UM, chapter 10.10 g) Stored energy time: See UM, chapter 10.6 h) Restored energy time: N/A i) Nominal d.c. battery charging voltage and tolerance band: See UM, chapter 10.4 j) Charging current limit value or range: See UM, chapter 10.4 k) Battery ripple current or voltage: See UM, chapter 10.4 l) Battery undervoltage and/or overvoltage charging protection levels: Adjustable due to battery manufacturer s specification m) Battery charging regime: See UM, chapter 10.4 (IU, DIN 41773) n) Battery protective device ratings and type and number: Battery fuse. See UM 10.12.2 o) Battery protection requirements: Electronic protection for over charging and deep charging p) Battery cable voltage drop recommendations: N/A 5.5 US switches, rated values and performance 5.5.1 General Switches specified by the manufacturer: See user manual a) Normal service conditions: See user manual b) Continuous duty: See user manual 5.5.2 US switches: specified with (if appropriate): a) Voltage and its tolerance band: N/A b) Number of poles/number of phases: 4 c) Continuous current capability: N/A d) Short-circuit making capability: N/A e) Short-circuit breaking capability: N/A f) Overload current capability: N/A g) Make time: N/A h) Break time: N/A i) Circuit repetitive peak off-state voltage: N/A j) Circuit non-repetitive peak off-state voltage: N/A k) Leakage current: N/A l) Max. permissible rate of rise of the off-state voltage: m) Losses at rated load: N/A n) Isolation capability: N/A o) Load power factor limits: See user manual, chapter 10.3 p) frequency and its tolerance band See user manual, chapter 10.5 N/A

age 10 of 48 Report No. 11-EL-0026.06 IEC 62040-3 Clause Requirement Test Result Remark Verdict q) Rate of rise of current at closing N/A 5.6 Redundant and parallel US systems 5.6.1 Standby redundant US 5.6.1.1 Without bypass shall be stated: With bypass N/A a) Total number of US units N/A b) US ratings and performance N/A c) US switch losses N/A d) US switch ratings N/A 5.6.1.2 With bypass shall be stated: a) Total number of US units Two or more b) US ratings and performance Bypass has the same value as input c) US switch losses See user manual d) US switch ratings Bypass switch rating according to max. US output power Bypass ratings as defined in 5.3.3 5.6.2 arallel redundant US N/A 5.6.2.1 Without bypass shall be stated: N/A a) Total number of equal US units working normally in parallel: b) Total number of US units in parallel needed to supply specified max. continuous load:: c) US switch and transfer performance: N/A d) Continuous rating with all US units in operation: N/A e) Continuous rating with minimum required number of US units in operation 5.6.2.2 With bypass a) Total number of equal US units working normally in parallel: b) Total number of US units in parallel needed to supply specified max. continuous load:: Two or more c) US switch and transfer performance: N/A d) Continuous rating with all US units in operation: yes Bypass rating and performance in accordance with B.2 5.7 Electromagnetic compatibly Complies with IEC 62040-2 See TR-No: Ber111025_2 5.8 Signalling circuits Complies with IEC 60950 See TR-No: 11-EL-0026.05 N/A N/A N/A N/A 6 ELCTRICAL TESTS FOR US

age 11 of 48 Report No. 11-EL-0026.06 IEC 62040-3 Clause Requirement Test Result Remark Verdict 6.1 General 6.1.1 Type tests 6.1.2 Routine tests 6.1.3 Test conditions: erformed in electrical conditions 6.2 US functional unit tests 6.2.1 US rectifier tests comply with IEC 60146-1-1 clauses 4.1.3 to 4.2 6.2.2 US Inverter tests comply with IEC 60146-2 if applicable 6.2.3 US switch tests comply with IEC 60146-1-1 and IEC 60146-1-2 if applicable See TR-No: Ber111025_2 See TR-No: Ber111025_2 See TR-No: Ber111025_2 6.2.4 Monitoring and control equipment tests Tests comply with IEC 60146-1-1 Comply with IEC 62040-1 see TR-No: 11-EL-0026.04 6.2.5 Battery tests 6.3 Type tests of manufacturer s declared characteristics as a complete US If complete US testing is not performed at the factory, a functional unit test in accordance with 6.2 shall be completed prior to testing on side 6.3.1 Control and monitoring signals 6.3.2 US input tests 6.3.2.1 Steady-state input voltage tolerance 6.3.2.2 Input frequency variation 6.3.3 Input inrush current (see appended table) 6.3.4 US output characteristics-static conditions 6.3.4.1 Output normal mode no load 6.3.4.2 Output normal mode full load (see appended table) 6.3.4.3 Output stored energy mode no load (see appended table) 6.3.4.4 Output stored energy mode full load (see appended table) 6.3.4.5 US rated output fault clearing capability normal mode (see appended table) 6.3.4.6 DC components in the output 6.3.5 US output characteristics Overload and short-circuit 6.3.5.1 Output normal mode - overload 6.3.5.2 Output - stored energy mode overload 6.3.5.3 Output normal mode short-circuit (see appended table) 6.3.5.4 Output stored energy mode - overload (see appended table) 6.3.5.5 US rated output fault clearing capability normal mode 6.3.5.6 US rated output fault clearing capability stored energy mode

age 12 of 48 Report No. 11-EL-0026.06 IEC 62040-3 Clause Requirement Test Result Remark Verdict 6.3.6 US output dynamic tests 6.3.6.1 Change of operating mode normal to stored energy linear load 6.3.6.2 Change of operating mode stored energy to normal linear mode 6.3.6.3 Change of operating mode stored energy to normal mode 6.3.6.4 Change of operating mode normal to bypass mode (see appended table) (see appended table) (see appended table) (see appended table) 6.3.7.1 US output load steps linear load (see appended table) 6.3.8.1 Reference non-linear load output distortion normal mode 6.3.8.2 Reference non-linear load output distortion stored energy mode 6.3.8.3 Reference non-linear load change of operating mode 6.3.8.4 Reference non-linear load steps normal load < 4kVA rating 6.3.8.5 Reference non-linear load steps normal mode > 4kVA rating 6.3.8.6 Reference non linear load steps stored energy mode (see appended table) (see appended table) (see appended table) (see appended table) The used Test equipment non linear load is in a certain way constructed, that the load steps are selectable, but the connection to the US Load side is performed with a global automatic contactor. Before a load step change will be active and released, the total nonlinear load is disconnected from the US and with a time delay reconnected with the preselected step again. In this way the equipment is not able to proceed in steps as described in clause 6.3.8.5. The reason for this control of the non linear load bank is made to ensure that the inside used DC capacitors are precharged and discharged in a secure way. (see appended table) 6.3.9 Stored energy and restored energy tests 6.3.9.1 Stored energy time 6.3.9.2 Restored energy time 6.3.10 Efficiency and input power factor (see appended table) (checked with linear and non-linear load) N/A

age 13 of 48 Report No. 11-EL-0026.06 IEC 62040-3 Clause Requirement Test Result Remark Verdict 6.3.11 Backfeed tests ermanent connection option: - K1: rectifier - K2: output - K4: bypass 6.3.12 EMC test See TR-No: Ber111025_2 6.6 Factory witness tests/on-site tests 6.6.1 US tests 6.6.2 Test specifications: With and without bypass, linear and non-linear load 6.6.3 Light load test: Output voltage, output frequency, maintenance bypass switch 6.6.4 US auxiliary device(s) test N/A 6.6.5 Synchronization test N/A 6.6.5.1 Output frequency slew rate test N/A 6.6.6 AC input failure test (see appended table) 6.6.7 AC input return test (see appended table) 6.6.8 Simulation of parallel redundant US fault test (see appended table) 6.6.9 Transfer test (see appended table) 6.6.10 Full load test 6.6.11 US efficiency test (see appended table) 6.6.12 Unbalanced load test 6.6.13 Balanced load test 6.6.14 Test of current division in parallel or parallel redundant US (see appended table) 6.6.15 Rated stored energy time test 6.6.16 Rated restored energy time 6.6.17 Battery ripple current measurement 6.6.18 Overload capability test (see appended table) 6.6.19 Short circuit test: (see appended table) a) operation of protective devices or circuits N/A b) peak output short-circuit current c) output steady-state short-circuit current and length of time 6.6.20 Short-circuit protection device test 6.6.21 Restart test 6.6.22 Output overvoltage test 6.6.23 eriodic output voltage variation test (see appended table) 6.6.24 Frequency variation test See TR-No: Ber111025_2 6.6.25 Radiofrequency interference and conducted noise test See TR-No: Ber111025_2 6.6.26 Harmonic components measurement (see appended table)

age 14 of 48 Report No. 11-EL-0026.06 IEC 62040-3 Clause Requirement Test Result Remark Verdict 6.6.27 Earth fault test TN-S system N/A 6.6.28 On-site ventilation test 6.6.29 Standby generator compatibility test N/A 6.7 US switches testing procedure 6.7.1 Testing schedule 6.7.2 Test specification: 6.7.3 Interconnection cable check 6.7.4 Light load test a and b 6.7.5 Full load test 6.7.6 Transfer test 6.7.7 Overload capability test (see appended table) 6.7.8 Short-circuit current capability test (see appended table) 6.7.9 Overvoltage test (electronic power switches) See TR-No: Ber111025_2 -a) Circuit repetitive peak off-state voltage See TR-No: Ber111025_2 -b) Circuit non-repetitive peak off-state voltage See TR-No: Ber111025_2 6.7.10 Radiofrequency interference and conducted noise See TR-No: Ber111025_2 6.7.11 Audible noise Refer to data sheet 6.7.12 On-site ventilation test 6.7.13 Earth fault test TN-S system N/A 6.7.13 Additional tests (agreement between the purchaser and the supplier 7 NON-ELECTRICAL TEST 7.1 Environmental and transportation test methods N/A 7.1.1 transportation N/A 7.1.1.1 Shock test N/A 7.1.1.2 Free fall test N/A 7.2 Environments storage and operating test methods N/A 7.2.1 Storage condition tests: N/A 7.2.2 Operating condition tests: 40 C 7.3 Acoustic noise due to UM, chapter 10.6

age 15 of 48 Report No. 11-EL-0026.06 5.2.2.h / 6.6.26 TABLE: - Input current total harmonic distortion - Harmonic components measurement Description of test conditions / test construction: Each single input current phase is measured @ 100 % load and the 3rd, 5th, 7th and 9th current harmonics are measured to achieve the total harmonics distortion of current THDi on the input Note that THDI is strictly related to Input voltage value and Input Distribution Impedance, therefore measured values may vary according to mentioned characteristics. Load (%) Harmonic No. hase 1 (db) hase 2 (db) hase 2 (db) Remark 100 3 36.4 35.6 35.3 Cab. C 100 5 44.8 43.1 43.4 Cab. C 100 7 40.2 37.9 37.3 Cab. C 100 9 61.5 56.4 53.5 Cab. C THD see formula to THD below Distortion at phase 1 Distortion at phase 2 Distortion at phase 3 Expected value due to the specification of the manufacturer 1.90% 2.21% 2.30% < 3.0% Verdict THD 100 10 3 20 2 10 5 20 2 10 7 20 2 10 9 20 2

age 16 of 48 Report No. 11-EL-0026.06 Measured graph: yellow: input voltage, green: output current THDi at L1 THDi at L2 THDi at L3

age 17 of 48 Report No. 11-EL-0026.06 6.3.3 / 6.3.6.2 & 6.6.7 TABLE: - Inrush current test - Change of operating mode Stored energy to normal mode linear load - AC input return test Description of test conditions / test construction: urpose of test: Demonstrate the reaction of the US in case of loss and return of mains. rocedure: US running normally with load. The input switch (Mains) is switched ON and OFF. Output voltage will be recorded using input current as trigger for the detection of the mains failure. Note: measure taken with 100% load IA1 current AC/DC Bypass DC/AC IA2 L O A D voltage Measured graph: 1. Loss of mains: yellow: input voltage; green: input current; purple: output voltage 2. Return of mains: yellow: input voltage; green: input current; purple: output voltage

age 18 of 48 Report No. 11-EL-0026.06 6.3.4.2 / 6.6.26 TABLE: - Output Normal mode Full load - Harmonic components measurement Description of test conditions / test construction: rocedure: Load the unit at 100 % of its nominal capacity. The output voltages as well the output voltage distortion per phase (3, 5, 7, 9 harmonics) are measured Note: output harmonic distortion Load (%) Harmonic No. hase 1 (db) hase 2 (db) hase 2 (db) Remark 100 3 40.9 40.3 41.0 Cab. C 100 5 55.1 54.9 54.6 Cab. C 100 7 58.9 58.5 55.0 Cab. C 100 9 58.1 59.4 58.6 Cab. C THD see formula to THD below Distortion at phase 1 Distortion at phase 2 Distortion at phase 3 Expected value due to the specification of the manufacturer 0.94% 1% 0.94% < 2% verdict THD 100 10 3 20 2 10 5 20 2 10 7 20 2 10 9 20 2

age 19 of 48 Report No. 11-EL-0026.06 Measured graph: yellow: output voltage, green: output current THDu at L1 THDu at L2 THDu at L3

age 20 of 48 Report No. 11-EL-0026.06 6.3.4.3 / 6.6.26 TABLE: - Output Stored energy mode No load - Harmonic components measurement Description of test conditions / test construction: rocedure: Load the unit at 100 % of its nominal capacity. The output voltages as well the output voltage distortion per phase (3, 5, 7, 9 harmonics) are measured Load (%) Harmonic No. hase 1 (db) hase 2 (db) hase 2 (db) Remark 0 3 44.8 44.7 44.8 Cab. C 0 5 53.5 53.1 52.9 Cab. C 0 7 65.4 67.4 65.0 Cab. C 0 9 61.8 59.2 63.0 Cab. C THD see formula to THD below Distortion at phase 1 Distortion at phase 2 Distortion at phase 3 Expected value due to the specification of the manufacturer 0.62% 0.63% 0.62% < 2% Verdict THD 100 10 3 20 2 10 5 20 2 10 7 20 2 10 9 20 2

age 21 of 48 Report No. 11-EL-0026.06 Measured graph: Yellow: output voltage THDu at L1 THDu at L2 THDu at L3

age 22 of 48 Report No. 11-EL-0026.06 6.3.4.4 / 6.6.26 TABLE: - Output Stored energy mode Full load - Harmonic components measurement Description of test conditions / test construction: rocedure: Load the unit at 100 % of its nominal capacity. The output voltages as well the output voltage distortion per phase (3, 5, 7, 9 harmonics) are measured Load (%) Harmonic No. hase 1 (db) hase 2 (db) hase 2 (db) Remark 100 3 40.2 39.6 39.9 Cab. C 100 5 52.8 52.7 53.3 Cab. C 100 7 55.7 57.5 56.5 Cab. C 100 9 57.4 60.5 59.3 Cab. C THD see formula to THD below Distortion at phase 1 Distortion at phase 2 Distortion at phase 3 Expected value due to the specification of the manufacturer 1.03% 1.09% 1.05% < 2% Verdict THD 100 10 3 20 2 10 5 20 2 10 7 20 2 10 9 20 2

age 23 of 48 Report No. 11-EL-0026.06 Measured graph: yellow: output voltage, green: output current THDu at L1 THDu at L2 THDu at L3

age 24 of 48 Report No. 11-EL-0026.06 6.3.4.5 TABLE: Output voltage unbalance test Description of test conditions / test construction: rocedure: phases L1, L2 and L3 will be loaded with symmetric load. An asymmetric load will be additionally connected to L1 or L2 or L3 Measured graph: a) Asymmetric load additionally connected to L1 For all 3 graph: yellow: L1 Uout; green: Iout (asymmetric load); purple: L2 Uout; blue: L3 Uout b) Asymmetric load additionally connected to L2 b) Asymmetric load additionally connected to L3

age 25 of 48 Report No. 11-EL-0026.06 6.3.5.3 / 6.6.19. 6.7.8 TABLE: - Output Normal mode short circuit - Short circuit test - Short circuit current capability test Description of test conditions / test construction: urpose of the test: Demonstrate the operation of the US in case of short circuit on the load site. The inverter should supply the short circuit during 40ms with two times the nominal current. rocedure: US run online without bypass line (Bypass fuses open). Make a short circuit between the phases and the neutral on the output Record the output voltage and current Note: Measure taken without Bypass IA1 current AC/DC Bypass DC/AC IA2 L O A D voltage Fuse Measured graph: Cabinet C: I RMS = 186.8A yellow: output voltage green: output current

age 26 of 48 Report No. 11-EL-0026.06 6.3.5.4 / 6.6.19 TABLE: - Output Stored energy mode short circuit - Short circuit test Description of test conditions / test construction: urpose of the test: Demonstrate the operation of the US in case of short circuit on the load site. The inverter should supply the short circuit during 40ms with two times the nominal current. rocedure: US run online on battery without mains supply. Make a short circuit between the phases and the neutral on the output Record the output voltage and current Note: Measure taken without Bypass IA1 current AC/DC Bypass DC/AC IA2 L O A D voltage Fuse Measured graph: stored energy mode: short circuit Cabinet C: I RMS = 187.1A yellow: output voltage, green: output current

age 27 of 48 Report No. 11-EL-0026.06 6.3.6.1 / 6.6.6 TABLE: - Change of operating mode Normal to stored energy mode linear load (resistive) - AC input failure test Description of test conditions / test construction: urpose of test: Demonstrate the reaction of the US in case of loss of mains. rocedure: US running normally with load. The input switch (Mains) is switched OFF. Output voltage will be recorded using input current as trigger for the detection of the mains failure. IA1 voltage current AC/DC Bypass DC/AC IA2 L O A D voltage Measured graph: yellow: input voltage; green: Input current; purple: output voltage

age 28 of 48 Report No. 11-EL-0026.06 6.3.6.3 TABLE: - Change of operating mode Stored energy to normal mode Description of test conditions / test construction: urpose of test: Demonstrate the reaction of the US in case of loss and return of mains. rocedure: US running in stored energy mode with load. The input switch (Mains) is switched ON. Output voltage will be recorded using input current as trigger for the detection of return of mains IA1 voltage current AC/DC Bypass DC/AC IA2 L O A D voltage Measured graph: Synchrony: mains off (loss of mains) yellow: input voltage; green: input current; purple: output voltage

age 29 of 48 Report No. 11-EL-0026.06 Measured graph: Synchronization: Load transfer from stored energy to normal mode Load transfer from stored energy to normal yellow: input voltage; green: input current; purple: output voltage Synchonisation yellow: input voltage, green: input current, purple: output voltage yellow: input voltage, green: input current, purple: output voltage

6.3.6.4 / 6.6.9 TABLE: - Change of operating mode Normal to bypass mode - Transfer test age 30 of 48 Report No. 11-EL-0026.06 Description of test conditions / test construction: urpose of the test: Demonstrate that the US will switch between bypass and inverter without any interruption on the output voltage. rocedure: Switch the US between bypass and inverter with full load. Record the voltage on the load and use the bypass current as trigger for the detection of the transfer current IA1 current IA1 current AC/DC Bypass DC/AC IA2 L O A D voltage AC/DC Bypass DC/AC IA2 L O A D voltage Load transfer from normal mode to bypass Measured graph: Load transfer from bypass to normal mode Load transfer from normal mode to bypass yellow: output voltage, green: bypass current Load transfer from bypass to normal mode yellow: output voltage, green: bypass current

age 31 of 48 Report No. 11-EL-0026.06 6.3.7.1 TABLE: Output load steps Linear load Description of test conditions / test construction: urpose of the test: Demonstrate the reaction of the inverter output voltage when the load of 80% is switched ON and OFF. rocedure: Switch ON and OFF the load of 80% supplied by the inverter and record the output voltage. The output current will be used as a trigger for the detection of the switch ON and OFF of the load of 80% Note: Output voltage dynamic variations caused by LOAD (20% to 100% and 100% to 20%) IA1 current AC/DC Bypass DC/AC IA2 L O A D voltage Measured graph: 3. Output load changes from 20% to 100% yellow: output voltage, green: output current

age 32 of 48 Report No. 11-EL-0026.06 Measured graph: 2. Output load changes from 100% to 20% yellow: output voltage, green: output current 3. Output load changes from 100% to 0% 4. Output load changes from 0% to 100% yellow: output voltage, green: output current

age 33 of 48 Report No. 11-EL-0026.06 6.3.8.1 TABLE: - Reference non-linear load output distortion Normal mode Description of test conditions / test construction: Description of test conditions / test construction: non-linear load (due to annex E) the unit at 100 % of its nominal capacity. The output voltages as well the output voltage distortion per phase (3, 5, 7, 9 harmonics) are measured Note: Output harmonic distortion Load (%) Harmonic No. hase 1 (db) hase 2 (db) hase 3 (db) remark 90 3 33.6 33.2 32.9 Cab.C 90 5 37.9 37.7 37.8 Cab. C 90 7 41.0 40.7 41.3 Cab. C 90 9 47.2 46.7 47.6 Cab. C THD see formula to THD below Distortion at phase 1 (%) Distortion at phase 2 (%) Distortion at phase 3 (%) Expected value due to the specification of the manufacturer (%) 2.63% 2.75% 2.77% < 4% (with non-linear load) Verdict THD 100 10 3 20 2 10 5 20 2 10 7 20 2 10 9 20 2

age 34 of 48 Report No. 11-EL-0026.06 Measured graph: Detail view of US output (Fourier represented graphically for 3 phase) Yellow: output voltage, green: output current THDu at L1 THDu at L2 THDu at L3

age 35 of 48 Report No. 11-EL-0026.06 6.3.8.2 TABLE: - Reference non-linear load output distortion Stored energy mode Description of test conditions / test construction: Description of test conditions / test construction: non-linear load (due to annex E) the unit at 100 % of its nominal capacity. The output voltages as well the output voltage distortion per phase (3, 5, 7, 9 harmonics) are measured Note: Output harmonic distortion Load (%) Harmonic No. hase 1 (db) hase 2 (db) hase 3 (db) remark 90 3 33.1 33.1 32.9 Cab. C 90 5 37.9 38.9 37.8 Cab. C 90 7 41.4 41.4 41.0 Cab. C 90 9 48.5 48.8 47.6 Cab. C THD see formula to THD below Distortion at phase 1 (%) Distortion at phase 2 (%) Distortion at phase 3 (%) Expected value due to the specification of the manufacturer (%) 2.71 2.65 2.78 < 4% (with non-linear load) Verdict THD 100 10 3 20 2 10 5 20 2 10 7 20 2 10 9 20 2

age 36 of 48 Report No. 11-EL-0026.06 Measured graph: Detail view of US output (Fourier represented graphically for 3 phase): Yellow: output voltage, green: output current THDu at L1 THDu at L2 THDu at L3

age 37 of 48 Report No. 11-EL-0026.06 6.3.8.3 TABLE: - Reference non-linear load Change of operating mode - Normal to stored energy mode Description of test conditions / test construction: urpose of test: Demonstrate the reaction of the US in case of loss of mains (with non-linear load). rocedure: US running normally with 100% non-linear load. The input switch (Mains) is switched OFF. Output voltage will be recorded using input current as trigger for the detection of the mains failure. IA1 AC/DC Bypass DC/AC IA2 L O A D voltage current Measured graph: Input mains failure Yellow: output voltage, green: input current

age 38 of 48 Report No. 11-EL-0026.06 6.3.8.4 TABLE: - Reference non-linear load steps Normal mode 4.0 kva rating Description of test conditions / test construction: Normal mode with 30% linear load of rated output apparent power as base load and additional reference non-linear load set to 70% of rated output apparent power. Measured the output voltage waveform transient deviation. Measured graph: Yellow: output voltage, green: input current Remarks: the output voltage is overdriven at the beginning. The output tried to adjust, the output voltage will be then stabilized.

age 39 of 48 Report No. 11-EL-0026.06 6.3.8.5 TABLE: - Reference non-linear load steps Normal mode 4.0 kva rating N/A Description of test conditions / test construction: Measured graph:

age 40 of 48 Report No. 11-EL-0026.06 6.3.8.6 (6.3.8.4) TABLE: - Reference non-linear load steps Stored energy mode Description of test conditions / test construction: test repeated according to sub-clause 6.3.8.4 Measured graph: Yellow: output voltage, green: input current

age 41 of 48 Report No. 11-EL-0026.06 6.3.8.6 (6.3.8.5) TABLE: - Reference non-linear load steps Stored energy mode N/A Description of test conditions / test construction: test repeated according to sub-clause 6.3.8.5 Measured graph:

age 42 of 48 Report No. 11-EL-0026.06 6.3.10 / 6.6.11 6.6.23 TABLE: - Efficiency and input power factor - US efficiency test - eriodic output voltage variation test Description of test conditions / test construction: at linear load Measured at Cabinet C Input power factor: total power of 3 phases Load (%) Active ower Apparent ower ower Factor Expected value due to the specification of the manufacturer 97 45.7kW 45.9kW 0.996 0.99 Verdict Load (%) Efficiency Input voltage (V) Output voltage (V) Expected value due to the specification of the manufacturer 25 95.0 233.5 232.8 94.5 52 95.6 233.3 232.7 95.0 77 95.2 233.1 232.6 95.5 * 97 95.1 233.1 232.5 95.5 * Verdict Description of test conditions / test construction: at apparent and active power Load (%) Active power at linear load Efficiency Input power Output power Expected value due to the specification of the manufacturer Verdict 25 95.0 12.1kW 11.5kW 94.5 52 95.6 23.5kW 24.6kW 95.0 77 95.2 36.3kW 34.6kW 95.5 * 97 95.1 45.7kW 43.5kW 95.5 * apparent power at linear load 25 95.0 13.1kVA 11.5kVA 94.5 52 95.6 25.1kVA 23.5kVA 95.0 77 95.2 36.6kVA 34.6kVA 95.5 * 97 95.1 45.9kVA 43.5kVA 95.5 * Note to *): Depending on power rating

age 43 of 48 Report No. 11-EL-0026.06 Description of test conditions / test construction: at reference non-linear load Load (%) Efficiency Input voltage (V) Output voltage (V) Expected value due to the specification of the manufacturer 25 ** 93.8 233.0 233.0 93.5 29 94.1 233.5 232.8 93.5 48 94.3 233.4 232.7 94.0 50 ** 94.3 233.0 233.0 94.0 75 ** 94.3 233.0 233.0 94.5 * 88 94.2 233.2 232.7 94.5 * 100 ** 93.8 233.0 233.0 94.5 * Verdict Description of test conditions / test construction: at apparent and active power Load (%) Efficiency (%) Input ower Output ower Expected value due to the specification of the manufacturer Verdict Active ower at non-linear load 25 ** 93.8 8.7kW 8.2kW 93.5 29 94.1 10.7kW 10.0kW 93.5 48 94.3 16.4kW 15.5kW 94.0 50 ** 94.3 17.9kW 16.9kW 94.0 75 ** 94.3 27.2kW 25.6kW 94.5 * 88 94.2 31.9kW 30.1kW 94.5 * 100 ** 93.8 36.4kW 34.3kW 94.5 *

age 44 of 48 Report No. 11-EL-0026.06 Load (%) Efficiency (%) Input ower Output ower Expected value due to the specification of the manufacturer Verdict Apparent ower at non-linear load 25 ** 93.8 9.9kVA 12.5kVA 93.5 29 94.1 11.8kVA 14.5kVA 93.5 48 94.3 18.3kVA 24.0kVA 94.0 50 ** 94.3 19.7kVA 25.0kVA 94.0 75 ** 94.3 29.6kVA 37.5kVA 94.5 * 88 94.2 34.6kVA 43.8kVA 94.5 * 100 ** 93.8 39.5kVA 50.0kVA 94.5 * Note to*) depending on power rating. **) Interpolated values. owerscale 50kVA (C-cab) - Efficiency=f(Load_percentage) - Non-Linear Load 100.0% 95.0% 94.1% 94.3% 94.3% 94.3% 94.2% 93.8% 94.3% 94.3% 93.8% Efficiency [%] 90.0% 85.0% 80.0% Measured Interpolated oli. (Measured) 75.0% y = -0.4425x 4 + 1.1148x 3-1.0221x 2 + 0.4019x + 0.8859 R 2 = 1 70.0% 0% 20% 40% 60% 80% 100% 120% Load percentage [%]

age 45 of 48 Report No. 11-EL-0026.06 6.6.8 TABLE: Simulation of parallel redundant US fault test Description of test conditions / test construction: measures at the system output, load bus-bars US1 US2 USn AC/DC AC/DC AC/DC DC/AC IA1 DC/AC IA1 DC/AC IA1 IA2 IA2 IA2 LOAD busbars Measured graph: yellow: output voltage; green: US#1 input current

age 46 of 48 Report No. 11-EL-0026.06 6.6.14 TABLE: Test of current division in parallel or parallel redundant US Description of test conditions / test construction: Redundant arallel System; LOAD sharing. Measures at the system output, LOAD bus-bars US1 US2 USn AC/DC AC/DC AC/DC DC/AC IA1 DC/AC IA1 DC/AC IA1 IA2 IA2 IA2 LOAD busbars Measured graph: yellow=output voltage; green=first US current yellow=output voltage; green=last US current

6.6.18 6.7.7 TABLE: Overload capability test age 47 of 48 Report No. 11-EL-0026.06 Description of test conditions / test construction: System will be overloaded with 110% and 135% of normal load. The time will be checked refer to the specified time interval of the manufacturer. Overload capability is software controlled. This table is valid for every owerscale US (A-cab, B-cab and C-cab). owerscale Overload time 20.00 15.00 10.00 Min 5.00 0.06min = 4s 0.11min = 7s 0.95min = 57s 0.00-5.00 104 106 108 110 112 114 116 118 120 122 124 126 128 130 132 134 136 138 140 142 144 146 148 150 % Load Load (%) 110 % @ F=1.0 135 % @ F=1.0 Input voltage (V) Input power (kva) (kw) Output voltage (V) Output power (kva) (kw) Specified time interval (s) 225V 52.0 kw 233V 49.50 kw 10min 225V 63.8 kw 233V 60.75 kw 1min Verdict

Object/part no. TABLE: List of critical components Manufacturer/ trademark See TR-No: 11-EL-0026.04 age 48 of 48 Report No. 11-EL-0026.06 Type/model Technical data Standard Mark(s) of conformity 1. Supplementary information: 1. An asterisk indicates a mark that assures the agreed level of surveillance.