DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

Similar documents
ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Cast resin transformers HARMONY TM

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

VI 3 - i TABLE OF CONTENTS

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Electrical Description

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

Distribution transformers Part 2 Ground mounted transformers not closecoupled

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Basic Principles and Operation of Transformer

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

CAST RESIN DRY TRANSFORMER

General Electricity Company of Libya

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

(

Substation Preventive Maintenance

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

Reference Number PPS 05 - (RIC Standard: EP SP)

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

K Factor Power Transformers

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

Technical Specifications SECTION C

ECP HV INSULATION TESTING

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED

Technical Specifications

TMC Transformers TMC

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

50-SDMS-01 SPECIFICATIONS FOR

NSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation

OIL-IMMERSED ARC-SUPPRESSION COILS

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

Introduction. Centrado leading-edge transformer. Introduction

EI HIGH VOLTAGE INSULATION TESTING POLICY

Test description for dry-type transformers chapter for special tests

.1 Provide dry type cast-resin 11kV/0.420kV transformers in accordance with the Contract Documents.

ECP HV INSULATION TESTING

7. INSPECTION AND TEST PROCEDURES

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

SHORE TO SHIP FREQUENCY

Convincing technology creates compact performance

TS RES - OUTSTANDING ISSUES

Cast Resin Transformers

GENERAL TECHNICAL SPECIFICATION (Turnkey Work)

DISTRIBUTION TRANSFORMERS

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

SECTION 16322B SUBSTATION TRANSFORMERS DRY-TYPE

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

MODULOBLOC TRANSFORMERS

About us. Vision. To lead our field in innovation, quality and customer service.

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

PPC TECHNICAL SPECIFICATION D/ NCMD / THREE-PHASE DISTRIBUTION TRANSFORMERS

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

CEYLON ELECTRICITY BOARD SRI LANKA. Procurement of Plant

siemens.com/transformers Convincing technology creates compact performance The GEAFOL Basic: the optimum foundation for power distribution

SECTION PANELBOARDS

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

Tesar s.r.l. Installation and maintenance manual. Installation, use and maintenance. Manual. Page :1\20

Ritz Instrument Transformers GmbH. Welcome

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

SECTION TRANSFORMERS

MV network design & devices selection EXERCISE BOOK

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

Dry-type Transformer. High Reliability Maintenance-free Environmentally Friendly

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

KENYA ELECTRICITY GENERATING COMPANY LTD

Reference Number PDS 04 (RIC Standard: EP SP)

Transcription:

DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date Stage 27 th Jan 2014 Draft DELHI METRO RAIL CORPORATION LTD. 7 th Floor, B-Wing, Metro Bhawan, Fire Brigade Lane, Barakhamba Road, New Delhi 110 001 Page 1 of 15

Contents 1. 33 kv / 415 V, 3 PHASE Auxiliary transformers...3 1.1 General...3 1.2 Characteristics...4 1.3 Accessories...5 1.4 Temperature Protection...5 1.5 Transformer Values...5 1.6 Transformer Cubicle...5 1.7 Description...6 1.8 Terminal arrangements...7 1.9 painting...7 1.10 Nuts & bolts...7 2. DATA SHEET...8 2.1 AUXILIARY S...8 2.1.1 AUXILIARY 200 A...8 2.1.2 AUXILIARY 630 A...9 2.1.3 AUXILIARY 1600 A... 10 2.1.3 AUXILIARY 2000 A... 12 2.1.4 AUXILIARY 2500 A... 13 2.1.5 AUXILIARY 3000 A... 14 3. TEST SHEET... 15 3.1 AUXILIARY S... 15 Page 2 of 15

1. 33 / 415 V, 3 PHASE AUXILIARY S The Auxiliary Transformers, also referred to as Auxiliary Station Transformers are required to supply the power requirement at 415 / 230 V of various electrical equipments, systems and appliances. Mainly these comprise of power required for lighting, fans, air-conditioning, control and monitoring circuits, battery chargers, space heaters in the switchgear / panels etc. 1.1 GENERAL This specification defines the main technical characteristics required for the 33000 / 415-240 V dry type transformers to be used in Auxiliary Substations (ASS), Auxiliary Main Substations (AMS) or as required. This specification is applicable for the transformers of power rating of following capacity: Transformer Capacity AN (Air Natural) AF (Air Forced) 200 kva N/A 500 kva N/A 630 kva N/A 1000 kva N/A 1600 kva N/A 2500 kva 3000 kva 3000 kva 3500 kva The transformer offered shall be complete in all respects with all parts and accessories necessary for their efficient operation in sub stations. All such parts & accessories shall be deemed to be within the scope of this specification whether specifically mentioned or not. The transformer shall satisfy the following requirements and shall also comply with standards in force when the transformers are manufactured, particularly which are in the following table Standard # IEC 60076 IEC 60726 IS 2026 IS 11171/1985 BS 171 Description Power transformers - Insulation levels, dielectric tests and external clearances in air Dry-type power transformers Power transformers: Terminal marking,tappings and connectioins, Ability to Withstand Short Circuit Dry-Type Power Transformers Power transformersspecification for insulation levels and dielectric tests IEC publication No. 1963 or latest and IE Rules and BEE Guidelines applied in the manner altered, amended or supplemented by this specification, wherever applicable. In all cases, latest revision to these specifications referred to above shall apply. The transformer shall be dry type. Page 3 of 15

1.2 CHARACTERISTICS - Climatic conditions: indoor operation - Operation: continuous - Windings: Aluminium - Primary line voltage (across phases): 33 kv - Secondary voltage, off-load : 415 V - Secondary voltage at full load and p.f. 0,8: 400 V - Insulation rated voltage: 36 kv - Frequency: 50 Hz - Withstand at industrial frequency: 70 kv - Voltage surge withstands: 170 kv - Coupling: Dyn11 - Cooling: Air natural/ Air forced - Off load tap changer: 0, ±2.5% and ±5% - Class of insulation F Class The voltage shall be adjusted by a 5 positions switch which can be used dead and provides -5%, - 2.5%, 0, + 2.5%, and + 5% settings. The magnetic circuit shall be in low-loss oriented-grain silicon steel sheet. The primary and the secondary windings shall be capable of withstanding a syetrical three-phase short-circuit regardless of the tapping selected., that is to say a short circuit current, at secondary side, of 7000 A. The short Circuit level at secondary side for various ratings of transformers shall be as follows: 630 A 21.9 KA 800 A 22.6 KA 1000 A 24 KA 1600 A 37.1 KA 2000 A 43-46.4 KA 2500 A 58 KA 3150 A 73 KA The terminals shall be of the 36 kv type. Conductors insulated at 36 realize delta connection on primary side. The secondary neutral shall be solidly earthed The medium and low voltage connections shall be made using braids whose cross-section is suited for the current level to be transmitted and which are very easy to disconnect so as to enable very quick replacement of the transformer in the event of breakdown. This equipment shall satisfy all the requirements for interchangeability, interlock ability and functional servo-control applicable to this type of equipment. It shall use a technology and components identical to those of the equipment to be installed in the Auxiliary stations. Page 4 of 15

1.3 ACCESSORIES - Installed on rollers/ base channels - Lifting rings - Nameplate - Grounding terminal The connection with different terminals of transformer shall be through C type or suitable connector for sufficient clearances from transformer windings. HV connections of transformer shall be connected through insulated cables. HV terminals shall have suitable arrangement to provide sufficient clearance to 33 cables from transformer windings. 1.4 TEMPERATURE PROTECTION Transformers shall be fitted with a temperature protection system that allows winding temperatures to be monitored. This shall consist of two sensors placed on each low-voltage winding, i.e. three alarm sensors and three trip out sensors. An indicator shall be installed on the front door of the bay to indicate continuously the winding temperature. This shall be installed on the middle low voltage winding. 1.5 VALUES The contractor shall confirm the following characteristics for each power distribution transformer: Short-circuit voltage, No-load losses, Full-load copper losses Efficiency at different load conditions: 1/4 - load: power factor = 1 (Minimum: 98.95%) power factor = 0.8 (Minimum: 98.7%) 1/2 - load: power factor = 1 (Minimum: 98.87%) power factor = 0.8 (Minimum: 98.59%) 3/4 - load: power factor = 1 (Minimum: 98.67%) power factor = 0.8 (Minimum:98.34%) Full load: power factor = 1 (Minimum: 98.4%) power factor = 0.8 (Minimum: 98%) 1.6 CUBICLE Transformers shall be installed in dismountable cubicle, wire-mesh type. Alternatively, the transformers may be supplied in a cubicle with enclosure having a degree of protection of not less than IP-31 and without any HV portions exposed. The door shall be provided with a mechanical interlocking system, to ensure that it is possible to open the door only when the protection circuit breakers on the HV side as well as LV side of the transformer are in open Page 5 of 15

position. Also transformer should trip if somebody tries to open the door with its key without opening the HV & LV side breakers. Enclosure shall have inspection windows to view primary & secondary sides. Temperature monitoring devices with two thresholds (alarm and tripping) must be provided and located on the upper part of the secondary windings. The cubicle shall provide protection against direct contact with the power transformer. It shall include connections for the MV lines from the protection bay and connections for the low voltage circuit. Cable arrangement shall facilitate the exchange of the either of the transformers without any difficulty, i.e. the cables shall be laid along each side and connected to the transformer in such a way that it will not block the passage for removal of any of the transformer during service. The contractor will provide suitable size stiffeners in enclosure for connection of bus duct and to ensure that the enclosure does not deform due to Bust duct connection. The cubicles shall be protected against fire by means of an automatic fire detector and extinguisher system, Fire trace type or equivalent, complete with CO 2 Gas cylinder, approved by Chief Controller of Explosives, valve, flexible detection and delivery system in the form of a flexible tube made of special polymer, capable of withstanding a normal pressure of 12 bar and a maximum pressure of 20 bar, suitably routed inside the panel for detection of fire. The CO 2 gas cylinder shall be suitably mounted on the panel and shall be capable of flooding the cubicle with CO 2 gas, within the shortest response time, not more than 10 seconds after the fire is sensed by the flexible detector tube. The contractor shall submit the complete technical data of the system and shall obtain the approval of DMRC before ordering for manufacture of transformer enclosure. The bimetallic strip required for connection in any case shall be provided by the contractor. 1.7 DESCRIPTION Two doors containing two windows to allow observation of the transformer accessories shall be provided in the front face. These doors shall be closed and locked to prevent access to the transformer while either the MV or the LV side is live. Consequently, ventilation louvers shall be installed at the bottom of the front doors and in the bay rear panel and roof. A metal sheet shall be installed at 10 to 15 cm from the top grating to provide protection against any falling water. Page 6 of 15

1.8 TERMINAL ARRANGEMENTS The terminal arrangement for high voltage side shall be suitable for required size of cables with FRLS/FRLSOH outer sheath. Suitable arrangements shall be available for cable terminations so that the cable weight doesn t come on the terminals. The terminal on HV & LV shall be suitable for receiving XLPE cable and termination with cable gland and anodized hard wire for the cable termination. The terminals on the primary side shall be of the 36 type. 1.9 PAINTING All steel surfaces shall be painted which shall be suitable for polluted atmosphere and has to comply with ICE-60072-2-5 standard. After baring of all metal surfaces, an Intel two coat of rust proofing and anti corrosive paint shall be applied then they will be covered with three coatings of glossy oil & weather resistance non fading paint. 1.10 NUTS & BOLTS The threads and hexagons of all nuts, bolts and stud shall confirm to relevant IS or BS. No Bolt or stud shall project through its nut(s) more than 6 (or) four threads, except when otherwise approved for terminating stud/bolts. All the bolts and nuts shall be so placed that they are inaccessible by means of ordinary spanners. All terminals should be provided with suitable cadmium plated and passivated high tensile steel hard wires to facilitate cables termination. Page 7 of 15

2. DATA SHEET 2.1 AUXILIARY S 2.1.1 AUXILIARY 200 A INDICATIONS U VALUES Required Manufacturer Place of manufacture Port of embarkation Manufacturer drawing reference Standards IEC 60076 Insulation type Cast resin Rated power kva 200 Cooling mode AN Primary rated insulation voltage kv 36 Primary operating voltage kv 33 Secondary rated operating voltage V 415/240 Rated short duration power frequency withstand voltage kv 70 for primary winding Rated lightning impulse withstand voltage for primary kv 170 winding Short-circuit voltage % 4 Voltage setting % +5.0, +2.5, 0, -0.25, -5.0 Vector Group Dyn11 Maximum noise level dba 70 Maximum iron loses W 450 10% Maximum load loses W 2300 10% Dimensions (maximum)* - Length - Width - Height 2000 1500 2250 Weight (maximum)* kg 1700 *Dimensions shown are indicative only Page 8 of 15

2.1.2 AUXILIARY 630 A INDICATIONS U VALUES Required Manufacturer Place of manufacture Port of embarkation Manufacturer drawing reference Standards IEC 76 Insulation type Cast resin Rated power kva 630 Cooling mode AN Primary rated insulation voltage kv 36 Primary operating voltage kv 33 Secondary rated operating voltage V 415/240 Rated short duration power frequency withstand kv 70 voltage for primary winding Rated lightning impulse withstand voltage for kv 170 primary winding Short-circuit voltage % 4 Voltage setting (Off load Tap changer) % +5.0, +2.5, 0, -2.5, -5.0 Vector Group Dyn11 Maximum noise level dba 65 db at 1.5 metres Maximum iron loses W As per Manufacture (Efficiency required is defined in Specifications) Maximum load loses W As per Manufacture (Efficiency required is defined in Specifications) Dimensions (maximum)* - Length - Width - Height 2000 2000 2250 Weight (maximum)* kg 3000 *Dimensions shown are indicative only Page 9 of 15

2.1.3 AUXILIARY 1600 A INDICATIONS U VALUES Required Type Dry Type Cast Resin Standards IEC 76, IS 2026 and IS 11171/985 Insulation type Cast resin No. of Phases 3 Rated frequency Hz 50 Rated power (Air Natural) MVA 1.6 Cooling mode AN System Highest Voltage Primary Voltage side Secondary voltage V 36 Kv 460 V Impulse Withstand Voltage Secondary Voltage winding Power frequency Voltage Secondary Voltage winding 170 Kv rms 3.5 kv rms 70 Kv 3 kv Impedence at normal Voltage and frequency % 6.0% Voltage setting (Off load Tap changer) % +5.0, +2.5, 0, -.2.5, -5.0 Vector Group Winding material HV Side LV Side Winding Connection Primary Voltage Winding Secondary Voltage Winding Whether Neutral Terminal are to be brought out Secondary Voltage Winding Type of Live Terminals Secondary Voltage Winding Dyn11 Aluminium Aluminium Delta Star No Yes Cable sealing ends Bus Duct entry Maximum noise level dba 65 db at 1.5 metres Class of Insulation F Enclosure & Housing IP-31 Maximum iron loses W As per Manufacture (Efficiency required is defined in Specifications) Maximum load loses W As per Manufacture (Efficiency required is defined in Specifications) Dimensions (maximum)* V Page 10 of 15

- Length - Width - Height 2000 2000 2250 Weight (maximum)* kg 8000 *Dimensions shown are indicative only Page 11 of 15

2.1.3 AUXILIARY 2000 A INDICATIONS U VALUES Required Type Dry Type Cast Resin Standards IEC 76, IS 2026 and IS 11171/985 Insulation type Cast resin No. of Phases 3 Rated frequency Hz 50 Rated power (Air Natural) MVA 2.0 Cooling mode AN System Highest Voltage Primary Voltage side Secondary voltage V 36 Kv 460 V Impulse Withstand Voltage Secondary Voltage winding Power frequency Voltage Secondary Voltage winding 170 Kv rms 3.5 kv rms 70 Kv 3 kv Impedence at normal Voltage and frequency % 6.0% Voltage setting (Off load Tap changer) % +5.0, +2.5, 0, -.2.5, -5.0 Vector Group Winding material HV Side LV Side Winding Connection Primary Voltage Winding Secondary Voltage Winding Whether Neutral Terminal are to be brought out Secondary Voltage Winding Type of Live Terminals Secondary Voltage Winding Dyn11 Aluminium Aluminium Delta Star No Yes Cable sealing ends Bus Duct entry Maximum noise level dba 65 db at 1.5 metres Class of Insulation Enclosure & Housing Maximum iron losses & maximum Load losses Maximum iron loses Maximum load loses W W F IP-31 As per Manufacture (Efficiency required is defined in Specifications) Dimensions (maximum)* - Length - Width - Height V 2000 2700 2250 Weight (maximum)* kg 8000 Page 12 of 15

*Dimensions shown are indicative only 2.1.4 AUXILIARY 2500 A/3000 A INDICATIONS U VALUES Required Manufacturer Place of manufacture Port of embarkation Manufacturer drawing reference Standards IEC 76 Insulation type Cast resin Rated power AN kva 2500 Cooling mode AF A 3000 AN AF Primary rated insulation voltage kv 36 Primary operating voltage kv 33 Secondary rated operating voltage V 415/240 Rated short duration power frequency withstand kv 70 voltage for primary winding Rated lightning impulse withstand voltage for kv 170 primary winding Short-circuit voltage % 6 Voltage setting (Off load Tap changer) % +5.0, +2.5, 0, -2.5, -5.0 Vector Group Dyn11 Maximum noise level dba 65 db at 1.5 metres Maximum iron loses kw As per Manufacture (Efficiency required is defined in Specifications) Maximum load loses kw As per Manufacture (Efficiency required is defined in Specifications) Dimensions (maximum)* - Length - Width Height 2100 2900 2250 Weight (maximum)* kg 8000 *Dimensions shown are indicative only Page 13 of 15

2.1.5 AUXILIARY 3000 A / 3500 A INDICATIONS U VALUES Required Manufacturer Place of manufacture Port of embarkation Manufacturer drawing reference Standards IEC 76 Insulation type Cast resin Rated power AN kva 3000 Cooling mode AF A 3500 AN AF Primary rated insulation voltage kv 36 Primary operating voltage kv 33 Secondary rated operating voltage V 415/240 Rated short duration power frequency withstand kv 70 voltage for primary winding Rated lightning impulse withstand voltage for kv 170 primary winding Short-circuit voltage % 7 Voltage setting (Off load Tap changer) % +5.0, +2.5, 0, -2.5, -5.0 Vector Group Dyn11 Maximum noise level dba 65 db at 1.5 metres Maximum iron loses kw As per Manufacture (Efficiency required is defined in Specifications) Maximum load loses kw As per Manufacture (Efficiency required is defined in Specifications) Dimensions (maximum)* - Length - Width Height 2200 3000 2350 Weight (maximum)* kg 8500 *Dimensions shown are indicative only Page 14 of 15

3. TEST SHEET 3.1 AUXILIARY S INDICATIONS TYPE of TEST Type Routine On site Specials Temperature rise* X Lightning impulse withstand voltage test* X Separate-source voltage withstand test X Measurement of winding resistance X Measurement of voltage ration and check of phase displacement X Measurement of no load loss and current X Visual inspection X X * For these type tests, the Contractor could provide a report on similar equipment Page 15 of 15