SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Similar documents
51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

General Electricity Company of Libya

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Basic Principles and Operation of Transformer

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

OIL-IMMERSED ARC-SUPPRESSION COILS

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

Introduction. Centrado leading-edge transformer. Introduction

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

Reference Number PPS 05 - (RIC Standard: EP SP)

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

POTENTIAL TRANSFORMER

EARTHING TRANSFORMER

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

THREE-PHASE DISTRIBUTION TRANSFORMERS

DISTRIBUTION TRANSFORMER 11 / kv

PPC TECHNICAL SPECIFICATION D/ NCMD / THREE-PHASE DISTRIBUTION TRANSFORMERS

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

DISTRIBUTION TRANSFORMER kv

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

SECTION TRANSFORMERS

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY (PEDE) SPECIFICATIONS FOR

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Mechanical Design. Brian Brinson Mechanical Design Manager.

ELETTROMECCANICA. Since english OIL IMMERSED DISTRIBUTION TRANSFORMERS

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE

HOW TO SAFE GUARD THE TRANSFORMER..???

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Liquid-Filled Transformers

TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s

No. COA/BHL/2018/293 Dated: REQUEST FOR QUOTATIONS

Electrical Design Process

DISTRIBUTION TRANSFORMERS

PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT

SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

Technical Specification For 33 KV, Single Phase, Dead Tank Type Out Door Current Transformer Of Different Ratio

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

TRANSFORMER TECHNOLOGY GPT

Basic principles and operation of a transformer

TECHNICAL SPECIFICATION OF 630 KVA, 11/ KV DRY TYPE OUTDOOR TRANSFORMERS.

User s Manual For CT Model IMB

Power Transformers Basics

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

PS REV NO: 01 PAGE : 2 OF 22

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

Reactor and inductor are names used interchangeably for this circuit device.

TECHNICAL SPECIFICATION

SECTION VI TECHNICAL SCHEDULES

Cast resin transformers HARMONY TM

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX

CAPACITOR VOLTAGE TRANSFORMER

Howard Smart Transformer Specification Guide

NSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation

nical catalogue Tech

Arc Suppression Coils

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

Regional Technical Seminar SHORT CIRCUIT FORCES

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Distribution and Power Transformers

WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LTD.

SHARDA Make Harmonics Filter

Transformer Factory Testing

Transformers handling and transport

VI 3 - i TABLE OF CONTENTS

Single & Three Phase Transformers SAMPLE. Learner Workbook. Version 1. Training and Education Support Industry Skills Unit Meadowbank

WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED

SCHEDULE A SR. NO. 1 No.

(TECHNICAL SPECIFICATIONS & GTP FORMATS) 11KV METERING UNITS

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

CAST RESIN DRY TRANSFORMER

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

Transcription:

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor and shall be designed, manufactured and tested as per IEC 60076 and this specification. 2. The transformer shall be free breathing type provided with a conservator and a dehydrating breather (cobalt free). The conservator shall be in such a position as not to obstruct the electrical connections to the transformer and shall have oil gauge at one end marked with oil levels. The conservator shall have a feed valve. 3. The complete transformer shall be painted and protected against corrosion, and the final colour of the exterior surface shall be Dark Admiralty Grey colour No. 632 as per BS 381C. The inside of the tank shall be coated with oil resisting varnish or paint so that oil cannot come into contact with tank or metal at any point. 4. Each transformer shall be suitable for ground mounting (on a plinth). 5. Drawings and documentation for the transformer offered shall be given, clearly detailing important dimensions, clearances, accessories, fittings, internal assembly, material details and any special features of the offered design. Tank 1. The transformer tank shall be constructed of mild steel plates. Tank thickness shall be stated in the Technical Particulars (Annex A & B). 2. The transformer tank shall be sealed by means of suitable gasket and be fitted with earthing terminals. Eight (8No.) non-standard shearing bolts to deter unauthorized opening shall be used on bolted corners and centres of sides of the top cover. All bolts, nuts and washers shall be hot dip galvanized to BS729. Core 1. The cores shall be constructed of high quality low loss grain oriented electrical steel laminations. The design shall ensure no hot sections due to over fluxing or circulating currents across the laminations. The flux density at any point shall not exceed 1.65 Tesla.

2. The cores shall be clamped effectively with metal cross-arms and be fitted with core lifting lugs. The manufacturer shall demonstrate experimentally or via a previous test report, that the whole structural frame-work supporting the transformer windings and the core can definitely withstand repeated transformer short-circuits. Windings 1. The windings shall be of electrolytic copper capable of sustaining short circuit forces on the transformer. 2. The primary windings shall be of electrolytic copper coils or copper foils and the secondary windings shall be full coil copper wires as opposed to segmented winding. 3. The HV and LV windings shall be separated so as to allow for cooling and ease of repair. Insulating sleeves for the transformer tapping s shall be in crepe paper or better. Tapping 1. The secondary windings (11kV & 33kV) shall have tapping s at 2 X 2.5% operated by an off-circuit self-positioning tapping switch with marked position indicators. Tapping details shall be included on the transformer name plate. 2. Switch position No. 1 shall correspond to maximum plus tapping. The make contacts of the tap changer shall be robust and of sufficient surface area. Vector Group 1. The three-phase transformer shall be wound to IEC vector reference dyn. 2. The star point of the secondary winding shall be brought out to a neutral bushing. Cable Boxes, Bushings and Clearances 1. The transformer shall be fitted with cable box on the primary side (LV) and have open bushings on the secondary side (11kV and 33kV). 2. The LV cable box shall be suitable for terminating up to 7No. Single core PVC cables of 600 mm 2 on a clamp pad, cables entry from bottom.

3. The 11 kv and 33kV bushings shall be open and shall have outdoor brown glazed weatherproof bushings provided with external stud for conductor sizes from 7.8 mm to 18.2 mm diameter mounted on the tank top cover. a) Clamp connector shall be provided on each bushing. b) The bushings shall be constructed, arranged and fitted in such a manner as to be changed without opening the transformer. c) Each bushing shall be fitted with adjustable double-gap arcing horns set at 2 X 25mm gaps for 11kV and 2 X 55mm gaps for 33kV. d) The minimum external electrical clearances and minimum creep age distances of the 11kV bushings and 33kV bushings shall be as indicated below: Nominal System Voltage between Phases 11kV 33kV Minimum clearances between phase to mm 300 480 earth Minimum Clearances between phases mm 250 435 Creep age distance mm 350 900 Oil and Cooling 1. Cooling of the transformer shall be by natural circulation of oil and natural circulation of air (ONAN). Loading will be as per IEC 60354. 2. Each transformer shall be dispatched filled with oil to the correct level and ready for service. The oil shall be new (unused), uninhibited mineral insulating oil class I as per IEC 296. Fittings and Accessories 1. No drain valve shall be fitted. 2. Oil gauge shall be provided on each transformer and shall be of dial or floater type. The oil gauge shall be clearly readable by an operator standing at a distance of 5 meters away from the transformer. The maximum and minimum oil level marks shall fall within 50% of the full range of the gauge with the nominal oil level being at the centre of the range. 3. Each transformer shall be complete with an oil temperature thermometer in a visible and secure position.

4. Each transformer shall be complete with a pressure relief device fitted in a visible and secure position. No part of the pressure relief device shall extend to a height greater than the HV bushings. Rating 1. The transformer shall be capable of carrying its full normal rated current continuously under the tropical conditions stated (maximum ambient temperature of 40 C) and at any tapping s without the temperature rise in the hottest region exceeding 55 C and 60 C in oil and winding respectively. Documents to support this shall accompany the tender. 2. The transformer shall be capable of sustaining a three-phase symmetrical short circuit on the secondary side with power maintained on the primary side without damage or distress for 2 seconds. 3. The transformers shall be in the following sizes: (a) 0.415/11kV: 630 kva and 1000kVA (b) 0.415/33kV: 630 kva and 1000kVA 4. The rated withstand voltages for the transformers shall be as follows: Rated short duration power frequency withstand voltage (r.m.s.) 38kV 0.415/11kV Transformers 0.415/33kV 95kV 200kV Impedance Voltage Rated lightning impulse withstand voltage (peak) 95kV 1. The impedance voltage measured at the principal tap shall not exceed 5.0%. Losses and Capitalization 1. The guaranteed transformer losses, measured at full load operation, unity power factor and rated voltage shall be submitted with the tender. The loss measurements (no-load and full-load) shall be adjusted to 75 degree Celsius and submitted for evaluation. 2. Evaluation will be carried out to establish the capitalized values of no-load losses and load losses at nominal rating of a transformer. This cost will be added to the bid price (landed cost) of the tender. Transformer losses shall be capitalized at the following rates:

Full load (winding) Losses No load (core) Losses US$ 1902 per kw for 15 years US$ 4504 per kw for 15 years Where tenders are being compared, losses will be capitalized at the above rate and added to the bid price according to the formula below: Gep = Gbp + G ($), Gep = Bid evaluation price, Gbp = Bid price G ($) = Adjustment for the cost of the operation and maintenance for 15 years And is obtained by using the following formula G ($) = 1902 X full load winding losses (kw) + 4504 X no load losses (kw)