CHAPTER-E-21. T1 Column With Beam Arrangement in Substation. T2 Column With Beam Arrangement in Substation

Similar documents
LIST OF DRAWINGS. 1. C/ENGG/NEPAL/DANA/SLD/01 (2 SHEET) Single Line diagram of 220/132/33kV Dana Substation

SLD FOR 132/33 KV DUB STATION, SOMANATHPUR

SCHEDULE OF WORK. Balmer Lawrie Co. Ltd. PRICED BID (PART-II) MMLH

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV

List of Item Codes of Various Materials Purchased by Materials Management Cell(H.O.,Mumbai) through e-tender website

Substation Preventive Maintenance

Single Line Diagram of Substations

Fatima Michael college of Engineering and Technology

KENYA ELECTRICITY GENERATING COMPANY LTD

Unit 2. Single Line Diagram of Substations

PROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured)

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

GENERAL TECHNICAL SPECIFICATION

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

VOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS)

Underground System Design TADP 547

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

Manual: Distribution Substation Manual (DSM) Section D: Substation Drawing Revision List

POTENTIAL TRANSFORMER

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Cables

SAUDI COMMITTEE FOR PALESTINIAN RELEIF

GENERAL TECHNICAL SPECIFICATION (Turnkey Work)

MV network design & devices selection EXERCISE BOOK

NISSAN NV200 CHEVY CITY EXPRESS WALL LINER KIT INSTALLATION INSTRUCTIONS

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

CUSTOMER MANUAL. General Installation Guide. Indoor/Outdoor RF Repeater Systems MARCH 1,

Ritz Instrument Transformers GmbH. Welcome

MERALCO Standards: Electrical Design. Engr. Eduard Mercado Electrical Design Team

NSP/007/028 Guidance On Substation Design: Drawing Submission Requirement

NSP/007/019 - Guidance on Substation Design: EHV Substation Drawing Policy

Welcome to the Session on. HT Distribution Network

Agenda. Earthing of Telecom Installations using Single Point Earthing. Reference Documents. How many earths? Earthing Issue...

METRIC LIGHTNING PROTECTION PRODUCTS

Standard Prices for Generators 2010

Click to edit Master title style. Click to edit Master title style. Northern Powergrid Asset Recording Guidance

RECORD GROUP NUMBER 156

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

WITHDRAWN JULY Manual: Distribution Substation Manual (DSM) Section I: Introduction

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

HOENER ASSOCIATES INC. ARCHITECTS

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES

kv AC substation

Quality Control Checklist - Design Drawings

CONTROL & RELAY PANEL

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

Fault location on power cables. Fault location on power cables

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

TYPICAL PATIO COVERS. OWNER: ADDRESS: PHONE:

Medium Voltage Power Cables

General Technical Specifications of Frequency Converters for Tokyo-Chubu Interconnection Project

PROGRAMMING SCHEMATIC DESIGN DESIGN DEVELOPMENT CONSTRUCTION DOCUMENTS. room) Scalable bubble diagrams schedules describing programmatic

ENERGY CORDAFLEX (SMK) (N)SHTOEU Low Voltage Reeling Cable

Introduction to Substation Design TADP 542

HV SYSTEMS. Prysmian HV Systems Product Range 66kV & 132 kv

PARALLEL GROOVE CLAMPS

LIST OF IS STANDARDS FOR ELECTRICAL PROJECTS

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

DA - DISTRIBUTION AUTOMATION

XLPE CABLE (33KV) September Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

Kerman & Kavian Cable Industries ( KCI )

WINTER 15 EXAMINATIONS Subject Code: Model Answer- Building Drawing Page No- 01 /15

REGENCY TIMBER BUILDINGS

Collection of standards in electronic format (PDF) 1. Copyright

REPORT OF PERFORMANCE TIC

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

03/7/12 Issuance UTD Section Page 1 of 5 Electrical General

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations

Lecturer: Dr. J B E AL-ATRASH No. of Pages: 4

RESTORATION OF DAVID SASSOON LIBRARY AND READING ROOM

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

BP Brine Pro Brine Maker. Parts List. This Parts List is for BP-2000 brine makers with serial numbers beginning with and higher.

SYARIKAT BEKALAN AIR SELANGOR SDN BHD

WEBS-MT/R Tower Installation Instructions

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

G. KOEPPL Koeppl Power Experts Switzerland

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

Panels, Panel Mounting & Other Accessories

With Illustrations, Drawings & Step By Step Details. Click Here To Download 12,000 Shed Plans. 1 P a g e Download 12,000 More Shed Plans

Premoulded cable joint SMPGB

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

Cable Data Collector (CDC): Application Guide

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.

MV Power Cable Testing Training

Temperature Sensor model TS-1/PS

Electric cables. Cranes

8 x 10 Timber-frame Garden Shed

WEBS-MT/R Tower Installation Instructions

NATIONAL INSTITUTE OF NUTRITION, HYDERABAD (UPGRADATION OF EXTERNAL ELECTRICAL WORKS)

MEDIUM VOLTAGE

5/2 Introduction. Unequipped Distribution Boards 5/4 Modular distribution boards 5/5 Add-on parts

Substation: From the Outside Looking In.

General Requirements. Technical Specification LVAC Systems

GROUP OF COMPANIES. MERLIN STEALTH Electric Fence Energizer INSTALLERS MANUAL

E S T I M A T E Name of Work : Estimate of Electric & Air Conditioned Work for Union Bank of India, Saral Branch, Dist. Rajkot.

Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED

Complex Solution for the Distribution Substation REF 542plus. Application and Setting Guide

Transcription:

CHAPTER-E-21 Sl No Drawing Name Drawing Number 1 Single Line Diagram (GIS S/s) ODSSP/SS/SLD/1-REV-C 2 Single Line Diagram (Outdoor S/s) ODSSP/SS/SLD/3 3 Sub- station Layout for GIS Type ODSSP/SS/SLY/1 4 Sub- station Layout for Outdoor Type ODSSP/SS/SLY/2 5 T1 Column With Beam Arrangement in Substation ODSSP/SS/3/ REV-A 6 T2 Column With Beam Arrangement in Substation ODSSP/SS/4/ REV-A 7 G3 For 33 kv Incomer in Substation ODSSP/SS/5 8 33 kv V Cross Arm for RS Joist in Substation ODSSP/SS/6 9 33 kv SI Structure (Outdoor) in Substation ODSSP/SS/7 10 33 kv CT Structure (Outdoor) in Substation ODSSP/SS/8 11 Earthmat Flat Jointing ODSSP/SS/9 12 Cable Trench for 1500 mm ODSSP/SS/10-REV-B 13 4 Bolted Tension Clamp ODSSP/SS/11-REV-B 14 15 16 17 18 33 kv 1250A Double Tandem Double Break Centre Rotating Isolator With one Earth Switch 11 kv 1250A Double Tandem Double Break Centre Rotating Isolator With one Earth Switch 33 kv 1250A Double Tandem Double Break Centre Rotating Isolator Without Earth Switch 11 kv 1250A Double Tandem Double Break Centre Rotating Isolator Without Earth Switch Structural Detail of 33kV Tower Type- T8 & T9 in Substation ODSSP/SS/12 ODSSP/SS/13 ODSSP/SS/14 ODSSP/SS/15 ODSSP/SS/16 19 Structural Detail of Girder Type G-4 ODSSP/SS/17 20 Structural Detail of Girder Type G-6 ODSSP/SS/18

21 22 23 Structural Detail of 33kV Single Isolator without Earth Switch (OPTCL Sub-Station) Structural Detail of 33kV Double Isolator with & without Earth Switch (OPTCL Sub-Station) Structural Detail of 33kV CT & PI (OPTCL Sub- Station) ODSSP/SS/19 ODSSP/SS/20 ODSSP/SS/21 24 H type Pole Design ODSSP/SS/22 25 Foundation of H type Pole ODSSP/SS/23/REV-A 26 Cross Sectional View of 33kV Cable, Un- Armoured, Single Core & 11kV Cable, Armoured, Three Core ODSSP/SS/24-REV-C 27 Cable Trench for 750 mm ODSSP/SS/25 28 Cable Trench for 500 mm ODSSP/SS/26 29 3 ½ C LT Power Cable ODSSP/SS/27-REVA 30 31 32 T1A & T2A Column With Beam Arrangement in Substation T3 Column With Beam Arrangement in Substation Bolt Arrangement for 33kV Outdoor Substation. ODSSP/SS/28 ODSSP/SS/29 ODSSP/SS/30 33 G1, G2 & R1 For 33 kv Incomer in Substation ODSSP/SS/31 34 DP structure used for 11kV Gantry at S/s ODSSP/SS/32 35 DP structure for 33/0.4kV Station Transformer ODSSP/SS/33 36 DP structure in S/s and Line ODSSP/LINE/1- REV-B 37 300kg 10 Mtr PSC Pole ODSSP/ LINE /3 38 11kV V Cross arm for RS Joist Pole ODSSP/LINE /4 39 11kV V Cross arm for PSC Pole ODSSP/ LINE /5-REV-A 40 Earthing Device ODSSP/LINE/6 41 Arrangements of Spikes with Column Structure ODSSP/LINE/7 42 Tension Assembly for Earth wire ODSSP/LINE/8 43 Suspension Assembly for Earth wire ODSSP/LINE/9

44 +6M Extension to PC Tower Structure (River Crossing) ODSSP/LINE/10 45 Jointing of GI R.S Joist Pole ODSSP/LINE/11 46 33 & 11 KV Danger Board ODSSP/LINE/15 47 PC Tower Structure Top ODSSP/LINE/16 48 PC Tower Structure Template ODSSP/LINE/17 49 PC Tower Structure Bottom ODSSP/LINE/18 50 Foundation of PC Tower Structure ODSSP/LINE/19 51 Single Tension Hardware Assembly ODSSP/LINE/20 52 Double Tension Hardware Assembly ODSSP/LINE/21 53 Cross Sectional View of 33kV Cable, Un- Armoured, Single Core & 11kV Cable, Armoured, Three Core ODSSP/LINE/25-REV-C 54 33kV Single Circuit Laying Arrangement ODSSP/LINE/26-REV-A 55 11kV Single Circuit Laying Arrangement ODSSP/LINE/27-REV-A 56 Foundation for PSC Pole ODSSP/ CIVIL /1-REV-A 57 Foundation for RS Joist Pole ODSSP/ CIVIL /2-REV-B 58 Foundation For T1 & T2 Columns (Sub- Station) ODSSP/CIVIL/3- REV-A 59 Foundation for Power Transformer ODSSP/CIVIL/4- REV-C 60 Foundation for 100 KVA Station Transformer ODSSP/CIVIL/5- REV-B 61 Retaining Wall for Switchyard ODSSP/CIVIL/6- REV-A 62 Drain ODSSP/CIVIL/7- REV-A 63 Foundation Plan for T1,T2,T1A, T2A, T3 Column with Foundation Bolt ODSSP/CIVIL/8 64 Foundation for 33kV VCB with CT (Outdoor) ODSSP/CIVIL/9 65 Road Inside Sub-Station ODSSP/ CIVIL /11-REV-B 66 Layout Plan of Compound Wall ODSSP/ CIVIL /12 67 68 Structural Design & Detailing of Compound Wall (Pile Foundation) Structural Design & Detailing of Compound Wall (Open Foundation) ODSSP/ CIVIL /13, Sheet-1/2 ODSSP/ CIVIL /13-REV-A, Sheet-2/2

69 Culvert Drawing ODSSP/ CIVIL /14 Left Side & Front Side Elevation Drawing of ODSSP/ CIVIL /15-REV-A, 70 Control Room Building for Flood Zone Sheet-1/5 71 Rear Side & Right Side Elevation Drawing of Control Room Building for Flood Zone ODSSP/ CIVIL /15, Sheet-2/5 72 73 74 75 76 77 78 79 80 Architectural Drawing for First Floor & Terrace Plan of Control Room Building for Flood Zone Architectural Drawing for Ground Floor and Sectional Plan of Control Room Building for Flood Zone Architectural Drawing for Lower Floor Plan of Control Room Building for Flood Zone First Floor Roof Beam Reinforcement Details of Control Room Building for Flood Zone Ground Floor Roof Beam Reinforcement Details of Control Room Building for Flood Zone Lower Floor Roof Beam and Lintel Reinforcement Details of Control Room Building for Flood Zone Staircase and other Misc. details of Control Room Building for Flood Zone Column & Foundation Reinforcement Details of Control Room Building for Flood Zone (Pile Foundation) Pile, Pile Cap & Grade Beam Reinforcement Details of Control Room Building for Flood Zone (Pile Foundation) 81 Column & Foundation Reinforcement Details of Control Room Building for Flood Zone (Open Foundation) ODSSP/ CIVIL /15, Sheet-3/5 ODSSP/ CIVIL /15, Sheet-4/5 ODSSP/ CIVIL /15, Sheet-5/5 ODSSP/ CIVIL /16, Sheet-1/4 ODSSP/ CIVIL /16, Sheet-2/4 ODSSP/ CIVIL /16, Sheet-3/4 ODSSP/ CIVIL /16, Sheet-4/4 ODSSP/ CIVIL /17, Sheet-1/2 ODSSP/ CIVIL /17, Sheet-2/2 ODSSP/ CIVIL /18, Sheet-1/2

82 Plinth Beam & Lintel Reinforcement Details of Control Room Building for Flood Zone (Open Foundation) 83 All Side Elevation & Sectional Drawing of Control Room Building for Non-Flood Zone 84 Ground Floor & Terrace Plan for Non-Flood Zone 85 Roof Beam Reinforcement Details of Control Room Building for Non-Flood Zone 86 Plinth Beam & Lintel Reinforcement Details of Control Room Building for Non-Flood Zone 87 Staircase and other Misc. details of Control Room Building for Non-Flood Zone 88 Column & Foundation Reinforcement Details of Control Room Building(Open Foundation) for Non-Flood Zone 89 Column & Foundation Reinforcement Details of Control Room Building(Pile Foundation) for Non-Flood Zone 90 Pile, Pile Cap & Grade Beam Reinforcement Details of Control Room Building(Pile Foundation) for Non-Flood Zone ODSSP/ CIVIL /18, Sheet-2/2 ODSSP/ CIVIL /19, Sheet-1/5 ODSSP/ CIVIL /19, Sheet-2/5 ODSSP/ CIVIL /19, Sheet-3/5 ODSSP/ CIVIL /19, Sheet-4/5 ODSSP/ CIVIL /19, Sheet-5/5 ODSSP/ CIVIL /20-REV-A ODSSP/ CIVIL /21, Sheet-1/2 ODSSP/ CIVIL /21, Sheet-2/2

PROPOSED SINGLE LINE DIAGRAM FOR 2X5/8 MVA, 33/11 kv GIS INDOOR S/S (33 kv GIS INDOOR, 11 kv AIS INDOOR) 33 kv INCOMER-II (WHERE REQUIRED) 33 kv INCOMMER-I DP (H pole) 33kV INDOOR GIS O/C & E/F METER SPARE 33 kv OUTDOOR ISOTOR 1250A/25kA for 3 Sec 33kV INDOOR CT 400-200/1-1-1 A 35 sq. mm UG CABLE 100 mtr. IVT 33kV VCB 630A/25kA for 3 Sec 33kV PROTECTION METERING 33/ 3 kv/ 110/ 3/ 110/ 3V DISCONNECTOR 630 A 33kV DISCONNECTOR 630 A 33kV VCB 630A/25kA for 3 Sec 33kV BUS S 33kV AB SWITCH ON DP 200A/25kA for 3 Sec FUSE DIFFRENTIAL PROTECTION 33kV INDOOR CT 400-200/1-1-1A METER O/C & E/F 100kVA,33 kv/0.433 kv STN. TRF DP 5/ 8 MVA POWER TRF NCT 5/ 8 MVA POWER TRF NCT 11kV INDOOR AIS DP 11kV BUS COUPLER VCB 11kV CT 400-200/1-1-1A 11kV VCB DP DIFFRENTIAL PROTECTION METER O/C & E/F 11kV BUS IVT PROTECTION METERING 33/ 3 kv/ 110/ 3/ 110/ 3V 11kV VCB 630A/25kA for 3 Sec 11kV INDOOR CT 400-200/ 1-1-1 A 11kV ISOTOR 1250A/25kA for 3 Sec DP 11kV FEEDER I 11kV FEEDER II 11kV FEEDER III 11kV FEEDER IV DRAWING NO - ODSSP/ SS/ SLD/1-REV-C

PROPOSED SINGLE LINE DIAGRAM FOR 2X3.15/ 5/ 8 MVA, 33 kv OUTDOOR & 11kV INDOOR S/S 33 kv INCOMER-I 33 kv INCOMMER-II 33kV OUTDOOR CT Second Feeder installed in requirement of two incoming feeder 33KV VCB IVT 33KV VCB CT 33/ 11KV TRF 11kV INDOOR AIS DP 11kV BUS COUPLER VCB 11kV CT 400-200/1-1-1A 11kV VCB DIFFRENTIAL PROTECTION METER O/C & E/F IVT PROTECTION METERING 11/ 3 kv/ 110/ 3V- 110/ 3V 11kV BUS 11kV VCB 630A/25 ka for 3 Sec O/C & E/F METER SPARE DP 11kV CT 400-200/ 1-1-1 A 11kV ISOTOR 1250A/25kA for 3 Sec 11kV FEEDER I 11kV FEEDER II 11kV FEEDER III 11kV FEEDER IV DRAWING NO - ODSSP/ SS/ SLD/ 3

CABLE TRENCH BAFFLE WALL SUB-STATION YOUT(GIS) INCOMING-2 INCOMING-1 T-1 T-2 T-1 ISO DP USING 150X150 G.I RS JOIST CABLE TRENCH 100KVA, 33/0.4kV STATION TRF 33/11 kv TRF-2 1.6MX1.6MX2M OIL SUMP PIT 33/11 kv TRF-1 SERVICE PORTICO 3MX4M SECU RITY 2MX2M CABLE TRENCH GATE ROAD DOOR BATTERY ROOM 2X2M A B C D OFFICE ROOM 2X3M CABLE TRENCH TOWARDS 33 kv PANEL INCOMR-I TRF-I TRF-II INCOMR-II IVT IVT FDR-I FDR-II TRF-I 33kV PANEL 11kV PANEL B/C CONTROL ROOM CUM SWITCHGEAR BUILDING G.I.S TRF-II FDR-III FDR-IV IVT DOOR STORE ROOM 2X3M CUSTOMER CARE OFFICE 4X3M OFFICE TOILET TOILET 2X1.5 M 2X1.5 M 2350 mm SERVICE VARENDAH CUM STAIRCASE GATE TOWARDS 11kV PANEL CABLE TRENCH ISO ISO ISO ISO FEEDER-1 FEEDER-2 FEEDER-3 FEEDER-4 NOTE:- A-CHARGER,B-ACDB, C-RTCC-1 & RTCC-2, D-RTU DRG NO.- ODSSP / SS / SLY/ 1

BAFFLE WALL SUB-STATION YOUT(OUTDOOR) INCOMING-2 INCOMING-1 T-1 ISO PI T-2 T-1 CT CT CB CB T-1A T-2A T-1A AB SWITCH HG FUSE IVT 100KVA, 33/0.4kV STATION TRF T-1A T-2A T-1A CB CB CT CT T1 PI T2 PI T2 R1 33/11 kv TRF-2 33/11 kv TRF-1 SERVICE PORTICO 3MX4M T3 T3 SECU RITY 2MX2M GATE ROAD DOOR BATTERY ROOM 2X2M A B C D OFFICE ROOM 2X3M 33kV PANEL INCOMR-I TRF-I TRF-II INCOMR-II IVT FDR-I FDR-II TRF-I CONTROL ROOM CUM SWITCHGEAR BUILDING A.I.S B/C TRF-II FDR-III FDR-IV IVT DOOR STORE ROOM 2X3M CUSTOMER CARE OFFICE 4X3M OFFICE TOILET 2X1.5 M TOILET 2X1.5 M 2350 mm SERVICE VARENDAH CUM STAIRCASE GATE 11kV PANEL ISO ISO ISO ISO FEEDER-1 FEEDER-2 FEEDER-3 FEEDER-4 NOTE:- A-CHARGER,B-ACDB, C-RTCC-1 & RTCC-2, D-RTU DRG NO.- ODSSP / SS / SLY/ 2

DRG NO-ODSSP/SS/3/REV-A 620 620 7250 6970 125 100 150 205 770 75 300 150 290 T1 COLUMN WITH BEAM ARRANGEMENT

670 620 7250 6970 175x75x6 mm channel DRG NO-ODSSP/SS/4/REV-A 5278 125 100 150 205 770 400 390 75 165 T2 COLUMN WITH BEAM ARRANGEMENT

DRG. NO- ODSSP/SS/12

DRG. NO- ODSSP/SS/15

CROSS-SECTIONAL VIEW OF 33kV & 11kV CABLE FOR S/S AL.CONDUCTOR SEMICONDUCTING WATER SWELBLE TAPE CONDUCTOR SCREENING (EXTRUTED SEMICONDUCTING XLPE) INSUTION MATERIAL (TREE RETARDANT) INSUTION SCREENING (SEMICONDUCTING XLPE ) WATER SEALING TAPE METALIC SHEATH (CORRUGATED AL.) BITUMINOUS TAPE OUTER SHEATH(FR PVC TYPE ST-2) CONDUCTING YER (GRAPHITE COATING) CROSS-SECTIONAL VIEW OF 33 kv 1C, UN-ARMOURED CABLE AL.CONDUCTOR SEMICONDUCTING WATER SWELBLE TAPE CONDUCTOR SCREENING (EXTRUTED SEMICONDUCTING XLPE) INSUTION MATERIAL (XLPE TREE RETARDANT) INSUTION SCREENING (SEMICONDUCTING XLPE+COPPER TAPE ) WATER SWELBLE TAPE PVC FILLER INNER SHEATH (PVC ST-2 EXTRUDED) ARMOURING GALVANISED STEEL/WIRE OUTER SHEATH(FR PVC TYPE ST-2) CROSS-SECTIONAL VIEW OF 11kV 3C, ARMOURED CABLE Drg No.-ODSSP/SS/24/REV-C