Open Circuit (OC) and Short Circuit (SC) Tests on Single Phase Transformer

Similar documents
EQUIVALENT CIRCUIT OF A SINGLE-PHASE TRANSFORMER

Module 7. Transformer. Version 2 EE IIT, Kharagpur

86 chapter 2 Transformers

PROBLEMS on Transformers

Chapter 2: Transformers

Transformer & Induction M/C

Practical Transformer on Load

148 Electric Machines

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Spring 2000 EE361: MIDTERM EXAM 1

Chapter 2-1 Transformers

ECE 321 Experiment No: 4 Energy Systems Lab 1 Fall 2009 TRANSFORMERS-1

RESONANT TRANSFORMER

Transformers. gpmacademics.weebly.com

Code No: R Set No. 1

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad ELECTRICAL AND ELECTRONICS ENGINEERING

Comparison of Leakage Impedances of Two Single-phase Transformers

CHAPTER 2. Transformers. Dr Gamal Sowilam

ECG 741 Power Distribution Transformers. Y. Baghzouz Spring 2014

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

Dhanalakshmi Srinivasan Institute of Technology, Samayapuram, Trichy. Cycle 2 EE6512 Electrical Machines II Lab Manual

Experiment No. Experiments for First Year Electrical Engg Lab

Module 7. Transformer. Version 2 EE IIT, Kharagpur

VALLIAMMAI ENGINEERING COLLEGE

Code No: R Set No. 1

ME 269 Laboratory Session #5

SECTION 4 TRANSFORMERS. Yilu (Ellen) Liu. Associate Professor Electrical Engineering Department Virginia Tech University

EN Assignment No.1 - TRANSFORMERS

Downloaded From All JNTU World

Rarely used, problems with unbalanced loads.

BASIC ELECTRICAL AND ELCTRONICS ENGINEERING LABORATORY LAB MANUAL

, ,54 A

Chapter 11. Alternating Current

The power transformer

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)

Experiment 3. Performance of an induction motor drive under V/f and rotor flux oriented controllers.

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

1. THREE-PHASE TRANSFORMER. SHORT CIRCUIT TEST

Downloaded From JNTU World. B.Tech II Year II Semester (R09) Supplementary Examinations December/January 2014/2015 GENERATION OF ELECTRIC POWER

Hours / 100 Marks Seat No.

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

AUTO-TRANSFORMER. This is having only one winding; part of this winding is common to both primary and secondary.

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

EE 221 CIRCUITS II. Chapter 12 Three-Phase Circuit

DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING 1

Lab 4 Power Factor Correction

Transformer Waveforms

EXPERIMENT 4: RC, RL and RD CIRCUITs

AC Power Instructor Notes

Unit 8 Combination Circuits

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Basic Operating Principles of Transformers

1. (a) Determine the value of Resistance R and current in each branch when the total current taken by the curcuit in figure 1a is 6 Amps.

Electromagnetic Oscillations and Currents. March 23, 2014 Chapter 30 1

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

INSTITUTE OF AERONAUTICAL ENGINEERING (AUTONOMOUS) Dundigal, Hyderabad

CHAPTER 9. Sinusoidal Steady-State Analysis

Electrical Engineering Fundamentals

EE 340L EXPERIMENT # 5.1 SYNCHRONOUS GENERATOR (STAND-ALONE OPERATION)

Exercise 1: Series RLC Circuits

Manuals. Basic Electrical Engineering BE-104

Lab 1: Basic RL and RC DC Circuits

Exercise 2: Parallel RLC Circuits

Rony Parvej s EEE. Lecture 3 & 4: Transformer. Update: 30 April, fecabook.com/ronyiut

EXPERIMENT 4: RC, RL and RD CIRCUITs

REV NO EXPERIMENT NO 1 AIM: To perform open and short circuit tests on 1-phase transformer and to calculate efficiency. Apparatus required:

Module 4. AC to AC Voltage Converters. Version 2 EE IIT, Kharagpur 1

cos sin XqIq cos sin V X Consider a simple case ignoring R a and X l d axis q axis V q I q V d I d Approximately, the second item can be ignored:

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Electrical Machines I : Transformers

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

not to be republished NCERT ALTERNATING CURRENT Chapter Seven MCQ 1

ELECTRICAL ENGINEERING ESE TOPIC WISE OBJECTIVE SOLVED PAPER-II

AC Excitation. AC Excitation 1. Introduction

Chapter 33. Alternating Current Circuits

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

Department of Electrical and Computer Engineering Lab 6: Transformers

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

EE 340 Power Transformers

IVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1

Oscillators. An oscillator may be described as a source of alternating voltage. It is different than amplifier.

Real Analog - Circuits 1 Chapter 11: Lab Projects

Alternating current circuits- Series RLC circuits

Generation of Sub-nanosecond Pulses

APPLICATION NOTE - 018

RC circuit. Recall the series RC circuit.

Practical Tricks with Transformers. Larry Weinstein K0NA

1. Explain in detail the constructional details and working of DC motor.

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Bakiss Hiyana binti Abu Bakar JKE, POLISAS BHAB

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

AP Physics C. Alternating Current. Chapter Problems. Sources of Alternating EMF

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

University of North Carolina-Charlotte Department of Electrical and Computer Engineering ECGR 4143/5195 Electrical Machinery Fall 2009

Transcription:

Open Circuit (OC) and Short Circuit (SC) Tests on Single Phase Transformer 1 Aim To obtain the equivalent circuit parameters from OC and SC tests, and to estimate efficiency & regulation at various loads. 2 Theory Equivalent circuit of transformer and simplified form of the circuit are shown in Fig. 1 and Fig. 2 respectively. Various performance parameters of transformers can be calculated if we know values of parameters in equivalent circuit. These parameters can be easily determined by performing tests that involve little power consumption. Two tests - no-load test (or open circuit test) and short circuit test will provide information for determining the parameters of the equivalent circuit. Figure 1: Equivalent circuit of a transformer Figure 2: Simplified equivalent circuit of a transformer 2.1 Open circuit (OC) test The shunt branch parameters are determined by performing this test. Since, the core loss and the magnetizing current depend on applied voltage only and are practically unaltered by the load current (why?). Hence to get these parameters, rated voltage is applied to one of the windings keeping the other winding open (generally HV winding is kept open and rated voltage is applied to LV winding - (why?). The circuit diagram to conduct this test is shown in Fig. 3. The secondary terminals are open 1

Figure 3: Connection diagram for OC test of a transformer (a) Equivalent circuit for no load (b) Phasor diagram on no-load Figure 4: Equivalent circuit and phasor diagram for OC test ( no load is connected across the secondary), hence the current drawn from the source is called as no load current. On no-load, the approximate equivalent circuit shown in Fig. 2 can be further reduced and is shown in Fig. 4. Under no-load condition, load resistance is not present in Fig. 1. Hence power input to the transformer is equal to the sum of losses in the primary winding resistance R 1 and core loss. But, no load current is very small (< 10%) as compared to full load current the loss in winding resistance is neglected. Thus, on no load the power drawn from the source is dissipated as heat in the core. If I o and P i are the current and input power drawn by the transformer at rated voltage V 1 respectively, then cos ζ o = P i (1) V 1.I 0 From Fig. 4, I c = I 0 cos ζ o, I m = I 0 sin ζ o, (2) R 0 = V 1 /I c, X m = V 1 /I m (3) 2.2 Short circuit (SC) test Consider the circuit shown in Fig. 2. Suppose the input voltage is reduced to a small fraction of rated value and secondary terminals are short-circuited. A current will circulate in the secondary winding. Since a small fraction of rated voltage is applied to the primary winding, the flux in the core and hence the core loss is very small. Hence, the power input on short circuit is dissipated as heat in the winding. The circuit diagram to conduct this test is shown in Fig. 6. In this test, the LV terminals of the transformer are short circuited. The primary voltage is gradually applied till the rated current flows in 2

the winding. Since, the applied voltage is very small (may be of the order of 5 8%), the magnetizing branch can now be eliminated from the equivalent circuit. The modified equivalent circuit is shown in Fig. 5. If V sc is the applied voltage to circulate the rated current (I 2) on short circuit, and P c is the power input to the transformer then, Figure 5: Equivalent circuit on SC test 3 Pre-lab Questions Z sc = V sc cos θ = (4) I 2 V sc.i 2 (R 1 + R 2) = Z sc cos θ, (X 1 + X 2) = Z sc sin θ (5) 1. A 100 kva, 240 V: 8 kv, 50 Hz single phase transformer has following parameters R 1 = 7 Ω R 2 = 3.6 Ω R 0 = 245.3 Ω P c X 1 = 45 Ω X 2 = 40 Ω X m = 120 Ω Assume that the transformer is supplying its rated kva at its low voltage terminals. Calculate the load current. Also calculate the magnetizing current as a fraction of load current. 2. Why HV winding, and not LV winding, is kept open during OC test? 4 Procedure Note down the name plate readings and determine the rated currents for both the windings. 4.1 No-Load Test: 1. Connect the circuit as shown in Fig. 3 2. Apply voltage to the LV side in steps upto the rated voltage and for each case record primary current and power drawn from the source. Also, observe the current waveform on the power analyzer. 3. Also, observe the waveform on DSO (Digital Storage Oscilloscope). Save ( record ) signals of the voltage and the current in form of a data file. 4. Increase the applied voltage by 10% and repeat the above step. 5. Reduce the output voltage of the variac to zero and switch-off the supply. 3

4.2 Short-Circuit Test: Figure 6: Connection diagram for short circuit test 1. Connect the circuit as shown in Fig. 6. Set the autotransformer output to zero. It is extremely important to note that a low voltage is to be applied to the primary winding. 2. Adjust the output of the autotransformer such that rated current flows through the windings. Record the applied voltage, current and input power. 3. Reduce the output voltage of the autotransformer to zero and put off the supply. 5 Report 1. Determine the equivalent circuit parameters from the test results. 2. Using equivalent circuit parameters compute the following: regulation at 25%, 75% and full load for powerfactor = 1, 0.6 lag and 0.6 lead. efficiency at 25%, 50%, 75% and full load for powerfactor = 1, 0.8 lag, and 0.6 lead. 3. Plot the variation of Efficiency with load VA for each power factor Regulation with powerfactor. 4. Plot the recorded data of voltage and current using appropriate tool e.g. gnuplot, MATLAB. Using this data, calculate the power dissipated and power factor. Note that in theory, vidt = P. However, in practice, we get discrete time samples as voltage and current signals. Hence, to calculate power we need to do numerical integration (i.e. summation) to get power disssipated. 6 Post-lab Questions 1. Which winding ( LV or HV) should be kept open while conducting OC test? Justify your answer. 2. Assume that the given transformer has the following name plate ratings: 40 kva, 440 V/11 kv, 50 Hz. What do these numbers imply? 4

3. Comment on the nature of the current waveform drawn from the source during OC test for (i) 50%, (ii) 100% and (iii) 110% of the rated voltage. 4. Can the regulation be negative? What does it signify? 5. Assume that you have been given a transformer manufactured in the US ( The supply voltage and frequency are 110 V and 60 Hz respectively). What voltage will you apply if this transformer is to be used in this country? Justify your answer. 6. What is the reason for high no load current at lower-than-rated voltage for the no load test on high frequency transformer which was demonstrated to you by the TAs? 7. Assume that you have been given two transformers of identical VA, and voltage ratings. But one of them is a 10 khz transformer and another is a 100 Hz transformer. Just by inspection, how would you identify which one is the high frequency transformer? Justify your answer. 8. What is an impedance matching transformer? Name one instrument of everyday use, in which this transformer being used. This experiment/chapter is prepared by Makarand M Kane (Research Scholar, 2015 batch) 5