Distributed Series Reactor An overview of the conductor impacts of the DSR

Similar documents
Smart Wires. Distributed Series Reactance for Grid Power Flow Control. IEEE PES Chapter Meeting - Jackson, MS August 8, 2012

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

PHYSICAL PHENOMENA EXISTING IN THE TURBOGENERATOR DURING FAULTY SYNCHRONIZATION WITH INVERSE PHASE SEQUENCE*

Induction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions

Harmonic control devices. ECE 528 Understanding Power Quality

Standards Developments for Fault Current Limiters

TECHNICAL SPECIFICATION

PHG 70 TD PD / PHG 80 TD PD

Chapter 13 Tuned-Mass Dampers. CIE Structural Control 1

StarSine Power Quality Products

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

VIBREC500 Recorders. Advanced Recorders to Measure Conductor Motions. the power connection THE PFISTERER GROUP

Active Smart Wires: An Inverter-less Static Series Compensator. Prof. Deepak Divan Fellow

CP CU1. Coupling unit for line and ground testing

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Past CIGRE and Emerging IEEE Guide Documents on FCLs

Power Analyser AM-10-PA2

LONGITUDINAL INDUCTION VOLTAGE MEASUREMENT ON COMMUNICATION CABLES RUNNING PARALLEL TO OVERHEAD LINES

p. 1 p. 6 p. 22 p. 46 p. 58

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

Harmonic control devices

SEL Phase Comparison Faulted Circuit Indicator (PC FCI) Communicates to line crews using the. Features and Benefits

Mitigating Murphy s Law While Test. Frédéric Dollinger

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

MVCT. Megger VT & CT Analyzer. MVCT Megger VT & CT Analyzer

VFRA-25 transformer frequency response analyzer

Design and Implementation of Power Line Sensornet for Overhead Transmission Lines*

FRAX Series Sweep Frequency Response Analyzers

Network Analyzer for Low-, Medium- and High-Voltage Networks

7P Series - Surge Protection Device (SPD) Features 7P P P

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER

INTRODUCTION. General Design Criteria o (include charts from Section 2 of TSS) Functional Criteria o (from TSS section 3) Accessibility and Layout

PCR Polarization Cell Replacement. The Polarization Cell Replacement (PCR) Technical Literature COMMON APPLICATIONS

1. Introduction to Power Quality

Understanding Input Harmonics and Techniques to Mitigate Them

DEVELOPING TESTING PROCEDURES FOR HIGH VOLTAGE INNOVATION TECHNOLOGIES

P331-2 set ESD generator (IEC )

the pilot valve effect of

High Voltage Surge Resistor

Effects of Harmonic Distortion I

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Wide-band Models from DC to 100 MHz

TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

Diagnostic testing of cast resin transformers

DEVELOPMENT OF A TEST PROTOCOL FOR A 15 KV CLASS SOLID-STATE CURRENT LIMITER

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

Line Impedance Estimation Using SCADA Data

ODEN AT Primary Current Injection Test System

MULTIBLOC 00.ST8 Size A, 690VAC Bottom Fitting, 1-,2-,4-pole

Our experience. Our products

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Electrical Engineering. Power Systems. Comprehensive Theory with Solved Examples and Practice Questions. Publications

CONTENTS. 1. Introduction Generating Stations 9 40

FRANEO 800. The next generation for a reliable core and winding diagnosis of power transformers

Wide-band Models from DC to 100 MHz

DB230 Capacitor Tester

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

WIND FARM Flexible AC Transmission Systems

Differential Current Sensor acc. to the standard UL2231 Ed.2.0. Customer: Standard type Page 1 of 7. Electrical data Ratings min. typ. max.

POWER QUALITY AND SAFETY

Error vs. Uncertainty Historical Perspective

HP 34401A Specifications 8

Cable testing and diagnostics

Modeling insulation in high-voltage substations

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Substation Design Volume VII

Digital Grid Products. SICAM Fault Sensor Indicator (FSI) The Guardian for your Overhead Line Networks

GFL-1000 User Manual Ground Fault Locator

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

PARALLEL GROOVE CLAMPS

Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

Magnetization System of Magnetically Controlled Shunt Reactors

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Powered by technology...driven by service CURRENT TRANSFORMERS. Multifunction Meters. Transducers & Isolators. Temperature Controllers

Multilevel Inverter Based Statcom For Power System Load Balancing System

1.0 mh, 3150 A LINE TRAP

Voltage and Current Waveforms Enhancement using Harmonic Filters

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

Harmonic resonances due to transmission-system cables

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS

UNDERSTANDING SUB-HARMONICS

Installation Instructions for OPGW Bolted Dead End

CPCO Series (160mm) DC-AC Current Probe, Clamp On ±4000A, ±8000A, ±12000A,


THE power grid infrastructure in the U.S. is in urgent need

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

Transcription:

1 Distributed Series Reactor An overview of the conductor impacts of the DSR Joseph Goldenburg, P.E. Mechanical Section Lead and Hardware Manager at NEETRAC

2 DSR Technology Overview History Table of Contents NEETRAC Testing Review of NEETRAC Testing Results

3 DSR Technology Overview A multi dimensional solution to control power flow through existing transmission lines developed by Smart Wire Grid Increases line impedance by injecting a pre tuned value of magnetizing inductance of the Single Turn Transformer Two modes of operation: 1. Autonomously, based on locally programmable set points 2. Two way communication, enabling more sophisticated operation and line monitoring

4 DSR Technology History DSR Prototype Formation of the Smart Wire Grid, Inc. (SWG) NEETRAC Gen 1 Testing NEETRAC Gen 2 Testing 2001 2008 2009 2010 2011 2012 2013 2014 Initial Patent Filing Formation of the Smart Wire Focus Initiative (SWFI) 99 units installed at TVA 33 units installed at Southern Company

5 Testing NEETRAC worked with SWFI to develop tests for the DSR, including: Clamp slip Vibration Impulse Fault Current Corona With the exception of the vibration testing, tests shown are for Gen 2 units.

6 Testing NEETRAC worked with SWFI to develop tests for the DSR, including: Clamp slip Vibration Impulse Fault Current Corona

7 Method Clamp Slip Testing

8 Clamp Slip Testing Results

9 Results Clamp Slip Testing DSR Type Sample ID Sample Test Run Initial Slip Load (lb) 1 445 32013 002 10 1 2 495 3 518 1 525 1000 32313 002 10 2 2 520 3 540 1 455 3213 003 10 3 2 530 3 500 1 620 3213 002 15 4 2 555 3 700 1 627 1500 32013 002 15 5 2 648 3 678 1 570 32313 001 15 6 2 680 3 525

10 Takeaways Clamp Slip Testing Post test inspection of the clamps showed no deformation of the conductor or rods.

11 Testing NEETRAC worked with SWFI to develop tests for the DSR, including: Clamp slip Vibration Impulse Fault Current Corona

12 Methods Vibration Testing Tested in advance of each DSR installation using installation specific line specifications So far only tested on Gen 1 DSRs Tests were based on: IEEE Std 664 1993: IEEE Guide for Laboratory Measurement of the Power Dissipation Characteristics of Aeolian Vibration Dampers for Single Conductors, IEEE Std 1368 2006: IEEE Guide for Aeolian Vibration Field Measurements of Conductors, and IEEE Std 563 1978: IEEE Guide on Conductor Self Damping Measurements.

13 Vibration Testing The purpose of these tests was to understand what happens to the line dynamics when one places an approximately 100 kg mass on the line. If line dynamics are unacceptable, develop appropriate mitigation strategy.

14 Results Vibration Testing 4200 lb tension, Unit Placed 6 ft 10 in From Termination Relative Displacement (in) 0.026 0.024 0.022 0.020 0.018 0.016 0.014 0.012 0.010 0.008 0.006 0.004 0.002 0.000 4 6 8 10 12 No Damper (Config. 13) 14 16 18 20 22 24 26 28 Frequency (Hz) 30 32 34 36 38 Meter 1 2 3 40 42 Relative Displacement (in) 0.026 0.024 0.022 0.020 0.018 0.016 0.014 0.012 0.010 0.008 0.006 0.004 0.002 0.000 4 6 8 10 Damper at 8 ft 6 in (Config. 14) 12 14 16 18 20 22 24 26 28 Frequency (Hz) 30 32 34 36 38 Meter 1 2 3 40 42 Relative Displacement (in) 0.026 0.024 0.022 0.020 0.018 0.016 0.014 0.012 0.010 0.008 0.006 0.004 0.002 0.000 4 6 8 10 Damper at 9 ft (Config. 15) 12 14 16 18 20 22 24 26 28 Frequency (Hz) 30 32 34 36 38 Meter 1 2 3 40 42 Relative Displacement (in) 0.026 0.024 0.022 0.020 0.018 0.016 0.014 0.012 0.010 0.008 0.006 0.004 0.002 0.000 4 6 8 10 Damper at 9 ft 6 in (Config. 16) 12 14 16 18 20 22 24 26 28 Frequency (Hz) 30 32 34 36 38 Meter 1 2 3 40 42

15 Results Vibration Testing

16 Takeaways Vibration Testing For TVA line, NEETRAC recommended that: DSR unit should be installed 6 ft. 4 in. ±6 in. from the suspension clamp. An AFL 1706 damper should be placed 9 ft. ±6 in. from the DSR face. Results are relatively consistent across a range of DSR and damper placements so slight deviation from the recommended installation location of the DSR and/or the damper should not affect the damper s performance.

17 Testing NEETRAC worked with SWFI to develop tests for the DSR, including: Clamp slip Vibration Impulse Fault Current Corona

18 Method Impulse Testing Tested in accordance with IEEE Standard Techniques for High Voltage Testing 1995 1050 kv BIL selected Units tested to ensure functionality after impulse testing

19 Results Impulse Testing Takeaways Units were functional after impulse testing at 1050 kv Additional tests scheduled for 1550 kv BIL

20 Testing NEETRAC worked with SWFI to develop tests for the DSR, including: Clamp slip Vibration Salt Fog Impulse Fault Current Corona

21 Method Fault Current Testing Tested in accordance with IEEE C37.100.1 2007, IEEE Standard of Common Requirements for High Voltage Power Switchgear Rated Above 1000 V 63 ka RMS 30 cycle rating selected per Table 3 of IEEE C37.32 2002, High Voltage Switches, Bus Supports, and Accessories Schedules of Preferred Ratings, Construction Guidelines, and Specifications

22 Test Sequence Fault Current Testing

23 Fault Current Testing Results Date DSR Type DSR SN ka (rms) Results 11/20/2013 1000 32013-001-10-02A-0 68.9 Passed 11/20/2013 1000 32013-003-10-02A-0 69 Passed 11/21/2013 1000 32013-002-10-02A-0 68.4 Passed 11/21/2013 1500 32013-001-15-02A-0 68.8 Passed 11/21/2013 1500 32013-003-15-02A-0 68.6 Passed 11/21/2013 1500 32013-002-15-02A-0 68.8 Passed

24 Fault Current Testing 2-1 = 566.6483 m 91.1 V 02:14.3790372 External Trigger 02:14.9541482 02:14.3874998 1 2 Sample_Volt 1 27.74 V 2-34.17 V Voltage across DSR -102.0 V 215.0 kamps Sample_Curr_Z 1-157.7 kamp 2-13.58 kamp Fault Current -186.7 kamps 02:12.9 2.000s/div 02:24.1

25 Fault Current Testing 02:14.3790372 External Trigger 83.39 V 02:14.3874998 1 Sample_Volt 1 27.74 V 2-34.17 V Voltage across DSR -102.0 V 215.0 kamps Fault Current Sample_Curr_ 1-157.7 kamp 2-13.58 kamp -172.2 kamps 02:14.3650 10.00 ms/div 02:14.4190

26 Takeaways Fault Current Testing Conductor was inspected following completion of testing. There was no visible evidence of test conductor damage.

27 Testing NEETRAC worked with SWFI to develop tests for the DSR, including: Clamp slip Vibration Impulse Fault Current Corona

28 Method Corona/RIV Testing Tested in accordance with IEEE C37.34 1994, IEEE Standard Test Code for High Voltage Air Switches Tested with and without protector rod.

29 Corona/RIV Testing w/ Protector Rod 180 kv Line to Gnd ~ 310 kv Line to Line

30 Corona Testing w/ Protector Rod The RIV requirement for units installed on 230 kv lines with a 1050 kv BIL rating are less than 500 µv RIV at 156 kv.

31 Corona/RIV Testing w/o Protector Rod Inception at 296 kv and extinction at 290 kv which are ~ 500 kv Line to Line

32 Takeaways Corona Testing Model 1000 DSRs w/ protector rod passed RIV requirements for 230 kv line, case inception >296 kv line ground with 11 ft. ground plane. Model 1000 DSRs w/o protector rod passed RIV requirements for 345 kv line with 11 ft. ground plane (standard allows more distance to ground plane at 345 kv). Re design of protector rod may enable coronafree operation above 230 kv when using protector rod.

33 Clamp Slip Impulse Fault Current Corona Conclusion The following tests indicate that DSR type device should have no impact on the conductor or support structures: The following tests indicate that DSR type device, without mitigation, would have a significant impact on: Vibration (Note: At TVA and Southern Company, successful mitigation strategies were developed.)