Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis

Similar documents
Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits

Power Quality Improvement using Hysteresis Voltage Control of DVR

Medium Voltage Three Phase Static Transfer Switch Operation: Simulation and Modeling RECEIVED ON ACCEPTED ON

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Protection from Voltage Sags and Swells by Using FACTS Controller

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Power Quality enhancement of a distribution line with DSTATCOM

ISSN Vol.07,Issue.21, December-2015, Pages:

Voltage Sag Index Calculation Using an Electromagnetic Transients Program

Power Quality Basics. Presented by. Scott Peele PE

International Journal of Scientific & Engineering Research, Volume 6, Issue 8, August ISSN

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

FRIENDS Devices and their Coordination

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

Synchronous Reference Frame Theory (SRF) along with PI Controller Based Dynamic Voltage Restorer

The Effect of Transformer s Vector Group on Retained Voltage Magnitude and Sag Frequency at Industrial Sites Due to Faults

Design of Interline Dynamic Voltage Restorer for Voltage Sag Compensation

ISSN Vol.03,Issue.11, December-2015, Pages:

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

II. RESEARCH METHODOLOGY

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Design Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System

Mitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM)

Simulation and Implementation of DVR for Voltage Sag Compensation

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

POWER QUALITY ENHANCEMENT BY DC LINK SUPPLIED INDUSTRIAL SYSTEM

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Mitigating Voltage Sag Using Dynamic Voltage Restorer

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Power Quality Improvement in Distribution System Using D-STATCOM

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Design Requirements for a Dynamic Series Compensator for Voltage Sags Mitigation in Low Voltage Distribution System

Assessment of Saturable Reactor Replacement Options

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

COMPARITIVE STUDY ON VOLTAGE SAG COMPENSATION UTILIZING PWM SWITCHED AUTOTRANSFORMER BY HVC

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3

Power Control Scheme of D-Statcom

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT

Voltage Sag and Mitigation Using Dynamic Voltage Restorer (DVR) System

Mitigation of Faults in the Distribution System by Distributed Static Compensator (DSTATCOM)

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

VOLTAGE SAG MITIGATION USING A NEW DIRECT CONTROL IN D-STATCOM FOR DISTRIBUTION SYSTEMS

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

Mitigation of Voltage Sag and Swell using D-STATCOM to improve Power Quality

Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

Dynamic Voltage Restorer for Mitigation of Voltage Sag and Swell

Design and Development of DVR model Using Fuzzy Logic Controller for Voltage Sag Mitigation

Power Quality and the Need for Compensation

Development and Simulation of Dynamic Voltage Restorer for Voltage SAG Mitigation using Matrix Converter

Compensation of Different Types of Voltage Sags in Low Voltage Distribution System Using Dynamic Voltage Restorer

Voltage Correction Methods in Distribution System Using DVR

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK

Performance of DVR & Distribution STATCOM in Power Systems

A New ISPWM Switching Technique for THD Reduction in Custom Power Devices

Mitigation of Voltage Sag and Swell Using Distributed Power Flow Controller

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

FLYWHEEL BASED ENERGY STORAGE SYSTEM FOR VOLTAGE SAG CORRECTION AND DETECTION

APPLICATION OF INVERTER BASED SHUNT DEVICE FOR VOLTAGE SAG MITIGATION DUE TO STARTING OF AN INDUCTION MOTOR LOAD

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

A NOVEL APPROACH ON INSTANTANEOUS POWER CONTROL OF D-STATCOM WITH CONSIDERATION OF POWER FACTOR CORRECTION

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM

DYNAMIC VOLTAGE RESTORER USING THREE PHASE AC-AC CONVERTER

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

Power Quality Analysis: A Study on Off-Line UPS Based System

Compensation of Unbalanced Sags/Swells by Single Phase Dynamic Voltage Restorer

VOLTAGE SAG COMPENSATION USING UNIFIED POWER FLOWER CONTROLLER IN MV POWER SYSTEM USING FUZZY CONTROLLER

p. 1 p. 6 p. 22 p. 46 p. 58

Dynamic Performance Evaluation of an HVDC Link following Inverter Side Disturbances

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Mitigation of Power Quality Problems Using DVR in Distribution Network for Welding Load

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

CHAPTER 6 MITIGATION OF VOLTAGE SAG, SWELL AND SINGLE PHASE OUTAGE USING MULTI WINDING TRANSFORMER

Implementing Re-Active Power Compensation Technique in Long Transmission System (750 Km) By Using Shunt Facts Control Device with Mat Lab Simlink Tool

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

Power Quality Improvement by DVR

A Voltage Controlled Dstatcom for Power Quality Improvement

MITIGATION OF VOLTAGE SAG AND SWELL FOR POWER QUALITY IMPROVEMENT USING DISTRIBUTED POWER FLOW CONTROLLER

Compensation of Balanced and Unbalanced voltage disturbance using SRF controlled DVR

Transcription:

Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis M. N. Moschakis* N. D. Hatziargyriou National Technical University of Athens Department of Electrical and Computer Engineering 9, Iroon Polytexneiou, 15773 Zografou, Athens, GREECE Tel.: +302107723696, E-Mail: mosxakis@power.ece.ntua.gr ABSTRACT: Industrial customers often suffer from supply voltage interruptions and sags due to the increase in the utilization of sensitive equipment in the process automation and control. An effective way to improve power quality and reliability of sensitive customers is to use a Static Transfer Switch (STS). This device is used to connect an alternate source of ac power to the sensitive load when the main source fails. Thus, power quality problems become transparent to the critical or sensitive equipment. In this paper, the main parts of a STS, performance characteristics and power system as well as fault parameters that influence them, are discussed. A STS model is presented and its behaviour on various cases is shown. Keywords: power quality, custom power, power conditioning, sensitive loads, static transfer switch, voltage detection, voltage sags. I. INTRODUCTION The increasing sensitivity of consumer equipment, has given rise to growing interest concerning the quality" of the electric power. Voltage sags of even low magnitude and short duration can cause financial losses to industrial customers due to process down-time, lost production, idle work forces and other factors [1]. There is a growing need, therefore, for power conditioning devices that will act very fast resulting in mild voltage sags of minimum duration experienced by the load. Many devices based on Power Electronics Technology have been proposed and applied in many cases where mitigation of voltage sags is needed. The Static Transfer Switch (STS), the Dynamic Voltage Restorer (DVR), the Distribution STAtic COMpensator (DSTATCOM), the Static Var Compensator (SVC) and the Solid State Tap Changer (SSTC) are the most used devices. One of the most effective solutions among the above is the Static Transfer Switch (STS). If an alternate feeder exists or can be provided to the critical load at reasonable cost, STS can transfer quickly enough the voltage supply to an alternate source and sensitive load experiences only a shallow sag of short duration. Obviously, STS is not effective in the event of a utility complete outage and cannot provide power conditioning, if both feeders sag in voltage simultaneously, as might be the case for a fault near the point where the two feeders join [2]. II. STS STRUCTURE A. Power circuit of the STS The three-phase model of a STS is shown in Figure 1. It consists of two thyristor blocks at the P(referred) and A(lternate) source, which connect the load to the two alternate sources. Each thyristor block is composed of three thyristor modules corresponding to the three phases of the system. In each thyristor module, two sets of thyristor switches are connected in opposite directions, e.g. PP1/PN1 and AP1/AN1, to allow the load current to flow in both positive and negative directions. Mechanical bypass switches Pb and Ab are used in parallel with the thyristor blocks A and P, respectively to supply the load, even if the thyristor switches are out of operation. Isolator switches M1p / M1a and M2p / M2a are also used to isolate the thyristor blocks from the rest of the system for maintenance of thyristor modules and test purposes[4]. B. Control circuit of the STS Fig. 1. Static transfer switch The control circuit (Figure 2a) takes as input the voltage magnitudes of the two feeders and performs a load-transfer when needed. When a deviation from the pre-set limits on the preferred source is detected, a transfer signal is generated. Index 1shows that transfer to the alternate source is affected, while index 0 shows transfer to the preferred source. When the conditions for a safe commutation at each phase separately are

fulfilled, load is completely transferred to the alternate source, until the voltage on the preferred source is restored. For the transfer to the preferred source, current zero-crossing is only detected. The outputs of the control circuit are the pulses for the preferred and alternate source thyristor switches [4]. Fig. 2a. Control circuit configuration of the STS B1. Voltage detection strategy The voltage detection circuit is presented in Figure 3. In this paper only voltage sags will be studied. By modifying the voltage detection circuit, the STS can provide transfer when any other voltage disturbances occur on the preferred feeder (e.g. voltage swells). In order a voltage sag to be detected, the instant phase voltages are digitally sampled (sampling frequency=10 khz) and the rms value is calculated by squaring and integrating the produced signal [11]. A second order transfer function [11] is used to enable a fast response of the calculated rms voltage to any voltage fluctuations, as shown in Figure 3. By taking the minimum of the three rms phase voltages, the response becomes even faster. Next, the deviation from the preset reference voltage (e.g. 1.0 pu) is compared to a tolerance limit. The most frequently used values for the tolerance limit are 10% or 15% depending on the sensitive load s supply voltage. If this voltage fluctuates often around 90% of the nominal, the tolerance limit should be set at 15%. If not, a 10% tolerance limit is preferable to allow faster voltage detection. When the voltage on the preferred source is within tolerance, control logic turns on the corresponding thyristors. Power then can flow from the preferred source to the load. If voltage deviates from the tolerance limit, the control logic checks the voltage of the alternate source. If the alternate source voltage is within tolerance limits, the load is transferred to the alternate source, otherwise, it does not issue any changes in the feeding source of the load. When the voltage on the preferred source returns to acceptable values, load is transferred back to the preferred source after a time delay (a few cycles are enough) to ensure that preferred source phase voltages are perfectly restored. The detection time is calculated for all types of fault and different fault instances (0-180 0 with a 18 0 step) and depicted in Figures 3a to 3d for two different tolerance limits(10% and 15%). It is obvious that the detection system s response to symmetrical and non-symmetrical voltage sags of different magnitude is not constant. It depends on the sag magnitude (all types of fault) and on the fault instant (except for the symmetrical faults) that the disturbance occurs. Thus, minimum maximum and average values of the detection time in relation to the sag magnitude are presented to depict the performance of the detection logic. fig. 3a. Minimum, maximum and versus sag magnitude (remaining voltage) in case of a single phase-toground fault. fig. 3b. Minimum, maximum and versus sag magnitude in case of a phase-to-phase-to-ground fault fig. 3c. Minimum, maximum and versus sag magnitude in case of a phase-to-phase fault fig. 3d. Minimum, maximum and versus sag magnitude in case of a symmetrical fault Fig. 3. Voltage detection circuit configuration Figures 3a to 3d indicate that the detection time is shorter for more severe faults (deeper voltage sag). The response of the

voltage detection logic is mainly determined by the midreject-filter damping ratio DR. The lower the DR, the faster the detection circuit and the shorter the detection time. However, decreasing DR makes the detection logic more sensitive to voltage transients, e.g. capacitor switching. Therefore, a trade-off needs to be made between the speed of the detection logic and its sensitivity to voltage transients. B2. Commutation and gating strategy A fast and safe commutation of the preferred source thyristor switches for every phase, depends directly on the relative position and magnitude of three variables when a voltage sag is detected: 1. Preferred source instant phase voltage (e.g. Va_p(t) ) 2. Alternate source instant phase voltage (e.g. Va_a(t) ) 3. Preferred source instant line current (e.g. Ia_p(t) ) Subsequently, transfer time, which is the difference between the time at which a disturbance is detected and the time at which the last faulty phase is transferred, is directly related to the following parameters: The phase angle difference between the pre-fault phase voltages of the two alternate sources. This may be between 0 and 40 0 depending on the line impedance and the active and reactive power transferred to the load. The pre-fault voltage magnitude of the alternate source. The load power factor, which determines the position of the current with respect to the voltage on the preferred source [7]. The severity of the fault, which determines the value of the instant voltage on the preferred source when a transfer signal is initiated [7]. The phase angle jump the fault introduces. The post-fault phase voltages, thus the type of the fault [7]. The instant at which the fault occurs [7]. Hence, the commutation from one source to another requires some critical conditions to be fulfilled (Figure 2a), in order to enable fast transferring to alternate source and to avoid false switching off of thyristor switches. This would lead to a cross current flowing through an outgoing (incoming) thyristor of one phase of the alternate source and through an incoming (outgoing) thyristor of a corresponding phase of the preferred source, which will feed the fault current [6]. Therefore, a transfer strategy which will take into account the relative position and magnitude of corresponding instant phase voltages of the two alternate sources and corresponding instant line current on the preferred source, is needed. Transferring does not always occur simultaneously for every phase. Each phase has to wait for one of the following conditions to become true in order to initiate transferring: I. A) The three aforementioned variables are of the same sign and B) The instantaneous difference in absolute voltage magnitude (e.g. Va_p(t) - Va_a(t) ) is larger than a certain limit V1 min, in order to give thyristor switch, which conducts at that moment, enough time to turn off. An example where condition A initiates transferring on phase - a is depicted in Figure 4a. Fault occurs at t=0.028 s, transfer signal is generated(voltage sag is detected) at t=0.032 s and transferring(only for phase - a) is initiated at t=0.0325 s. Thyristor PP1 is forced to turn off by turning on thyristor AP1(figure 1). It can be seen that Deblock Signal (dblk_altsrc_a), which enables firing pulses of alternate phase a thyristor switches, is delayed for a short time in order to assure that voltage difference is within the preset limit. Furthermore, as expected, the two instant phase voltages become equal when alternate source phase a thyristor AP1 is fired, until thyristor PP1 is completely turned-off. In this particular case, a smaller difference in instantaneous voltages ( Va_p(t) - Va_a(t) ) might have been able to lead to a safe commutation of thyristor switch. However, in a different case (Figure 4b), this smaller difference would lead to a high cross current because thyristor switch PP1 would not have enough time to turn off. Fault occurs at t=0.028 s and transfer signal as well as transferring are initiated at t= 0.0295 s. Thyristor PP1 is forced to turn off by turning on thyristor AP1(figure 1), but given time is not enough. Eventually, PP1 does not turn off and when AN1 is turned on, a large current(about 3 times larger than in normal operation) flows from the alternate source through AN1 and PP1 feeding the fault located upwards the load on the preferred source. Hence, a certain value in voltage difference needs to be applied in every case to assure safe transferring. II. A) If condition I-A is true but I-B is not, transfer logic delays until line current(e.g. Ia_p(t) ) crosses zero, and B) If ( Va_p(t) - Va_a(t) ) > 0 applies, initiates transferring (Figure 5). Fault occurs at t=0.022 s, transfer signal is generated at t=0.0277 s and transferring is initiated at t=0.0296 s. III. A) If II_B does not apply when line current (e.g. Ia_p(t) ) crosses zero but the three variables are of the same sign transferring is issued when: B) ( Va_p(t) - Va_a(t) ) > 0 for the first time(figure 6). Fault occurs at t=0.032 s, transfer signal is generated at t=0.0337 s and transferring is initiated at t=0.0372 s. IV. A) Another important case is the one shown in Figure 7. Va_a(t) and Ia_p(t) are of the same sign and Va_p(t) of opposite sign, when a transfer signal is issued. In this case transferring can be initiated to reduce transfer time, when: B) Va_p(t) - Va_a(t) is larger than a preset value V2 min, to assure successful commutation of thyristor PP1. Fault occurs at t=0.027 s detected at t=0.0293 s. At that time, Va_p(t) takes values of opposite sign with respect to Va_a(t) and Ia_p(t) values. Furthermore, Va_p(t) - Va_a(t) is larger than the preset value V2 min, so transferring can be initiated. Obviously, if transferring was not issued at the

time shown in Figure 7, it could be done to satisfy condition III approximately 3 ms later, as shown by the intersection of the voltage waveforms at t=0.032 s. Fig. 6. Instant phase voltages and line currents of phase -a for a voltage sag where condition III initiates transferring. Fig. 4a. Instant phase voltages and line currents of phase a (for both alternate sources), where condition I initiates transferring. Fig. 7. Instant phase voltages and line currents of phase a for a voltage sag where condition IV initiates transferring. Fig. 4b. Instant phase voltages and line currents of phase -a where commutation fails. When voltage on the preferred source returns to its acceptable limits, another transfer is needed. To ensure that all three phase voltages are completely restored, a short delay of 100 ms was introduced. When the transfer signal finally becomes zero, all thyristors of alternate source side of the STS are switched off immediately and thyristors of preferred source side are switched on at the first zero current. III. STS PERFORMANCE The performance of the STS is tested on a sensitive load (a papermill). A simplified single-phase diagram of the equivalent network is shown in Figure 8. The installation of this consumer contains protection systems that trip immediately after even shallow sags with only a short duration. Fig. 5. Instant phase voltages and line currents of phase -a for a voltage sag where condition II initiates transferring. Fig. 8. Single-phase diagram of the simplified network.

Three cases are presented to indicate the performance of STS (in all cases, fault is applied for 40 ms) : Case 1 A symmetrical fault that would lead to a sag magnitude of 16.14%(remaining voltage) without STS occurs at t fault = 0.012 s. Voltage on the alternate feeder was set to lag voltage on the preferred feeder by 40 0 just ore the event occurred, and their magnitudes were: V p = 1.0 pu and V a = 1.0 pu. Fault was detected at t det = 0.0127 s and transfer was completed at t trnsfr =0.01334 s. The sag magnitude experienced by the load when a STS was used was 79.4% and its duration was 6.2 ms. The results are presented in Figures 9a to 9c. Case 2 A single phase-to-ground fault that would lead to a sag magnitude of 81% without STS occurs at t fault = 0.01 s. Voltage on the alternate feeder was set to lead voltage on the preferred feeder by 20 0 just ore the event occurred, and their magnitudes were: V = 1.0 pu and V = 1.0 pu. p Fault was detected at t det = 0.01338 s (detection time=3.38 ms) and transfer was completed at t trnsfr = 0.01984 ms (transfer time=9.84 ms). The sag magnitude experienced by the load when a STS was used was 82.65% and its duration was 6.6 ms. The results are presented in Figures 10a to 10c. a Fig. 9a. Rms voltages with and without STS. The most sagged phases are shown. Fig. 10a. Rms voltages with and without STS. Fig. 10b. Instant phase voltages and line currents in all phases of the two alternate sources during the commutation. Fig. 9b. Instant phase voltages and line currents in all phases of the two alternate sources during the commutation. Fig. 9c. Signals indicating fault initiation and transfer signal generation. Fig. 10c. Signals indicating fault initiation and transfer signal generation.

Case 3 A phase-to-phase-to-ground fault that would lead to a sag magnitude of 46.4% without STS occurs at t fault = 0.019 s. Voltage on the alternate feeder was set to lag voltage on the preferred feeder by 30 0 just ore the event occurred, and their magnitudes were: V = 1.0 pu and V = 0.95 pu. p Fault was detected at t det = 0.02 s and transfer was completed at t trnsfr = 0.02588 ms. The sag magnitude experienced by the load when a STS was used was 83.16% and its duration was 2.2 ms. The results are presented in Figures 11a to 11c. a IV. CONCLUSION In this paper, a model of a Static Transfer Switch is presented. The importance of detection and transfer-gating scheme is mentioned. A fast voltage detection strategy and a novel transfer-gating scheme are proposed. Power system parameters as well as fault characteristics that influence STS performance are discussed. Finally, the STS performance on three different cases is presented, where it is clearly shown that the resulting sag magnitude and sag duration when this STS model is used are not enough to create any problems to a sensitive load. V. REFERENCES Fig. 11a. Rms voltages with and without STS. [1] G. Reed, M. Takeda, I. Iyoda, S. Murakami, T. Aritsuka, K. Tokuhara, Improved Power Quality Solutions Using Advanced Solid-State Switching and Static Compensation Technologies, in Proc. 1999 IEEE Power Engineering Society Winter Meeting,, vol. 2, pp. 1132-1137. [2] J. Burke, D. Griffith, D. Ward, Power Quality-Two Different Perspectives, IEEE Trans. Power Delivery, vol. 5, No.3, July 1990. [3] J. Jippling, W. Carter, Application and Experience with a 15 kv Static Transfer Switch,, IEEE Trans. Power Delivery, vol. 14, pp. 1477-1481, October 1999. [4] H. Mokhtari, S. Dewan, M. Iravani., Performance Evaluation of Thyristor Based Static Transfer Switch, IEEE Trans. Power Delivery, vol. 15, pp. 960-966, July 2000. [5] H. Mokhtari, S. Dewan, M. Iravani., Effect of Regenerative Load on a Static Transfer Switch Performance, IEEE Trans. Power Delivery, vol. 16, pp. 619-624, October 2001. [6] H. Mokhtari, S. Dewan, M. Iravani., Benchmark Systems for Digital Computer Simulation of a Static Transfer Switch, IEEE Trans. Power Delivery, vol. 16, pp. 724-731, October 2001. [7] H. Mokhtari, S. Dewan, M. Iravani., Analysis of a Static Transfer Switch with respect to Transfer Time, IEEE Trans. Power Delivery, vol. 17, pp. 190-199, January 2002. [8] B. Bose, Power Electronics and Ac Drives, Prentice Hall, 1986, p. 6. [9] M. Bollen, Understanding Power Quality Problems: Voltage Sags and Interruptions, IEEE Press Series on Power Engineering, P.M. Anderson Series Editor, 2000, p. 255. [10] Voltage characteristics of electricity supplied by public electricity distribution networks, European Standard EN 50160, November 1994. [11] PSCAD/EMTDC Power Systems Simulation Software Manual, Manitoba HVDC Research Center, MB, Canada, 1997. Fig. 11b. Instant phase voltages and line currents in all phases of the two alternate sources during the commutation VI. ACKNOWLEDGMENT This paper presents results from the project Power Quality Analysis and Improvement of the Greek Electricity Distribution Networks. The authors gratefully acknowledge the financial support of the Public Power Corporation of Greece and the contributions of Professors N. Vovos and G. Giannakopoulos of University of Patras. Fig. 11c. Signals indicating fault initiation and transfer signal generation. VII. BIOGRAPHIES M. N. Moschakis was born in 1974. He received the Diploma in Electrical Engineering from the National Technical University of Athens (NTUA), Greece, in 1998. Currently he is a Ph.D student in NTUA. His scientific interests mainly concern Custom Power Device Modeling and Evaluation, and Voltage Sag Stochastic Assessment. N. D. Hatziargyriou is Professor at Power Division of the Electrical Engineering Department of NTUA. His research interests include Power System Transient Analysis and Modeling. He is member of CIGRE SC38 and currently Chairman of the IEEE Greek Power Chapter.