GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED POWER-DISTRIBUTION SYSTEMS WITH ADJUSTABLE-SPEED DRIVES 1. Modified_103007

Similar documents
Motor Protection. May 31, Tom Ernst GE Grid Solutions

SE-502 MANUAL GROUND-FAULT GROUND-CONTINUITY DETECTOR

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

Multimeter 500CVD21 RTU500 series

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

Detecting and Managing Geomagnetically Induced Currents With Relays

Electromagnetic Harmonic Filters Technical Guide

Transformer Protection

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Fluke Clamp Meters Solutions for every need

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

Transformer Protection

How adjustable speed drives affect power distribution

g GE POWER MANAGEMENT

PR Rectifier Module

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

Generator Advanced Concepts

ECET Modern Power

Filter Considerations for the IBC

~=E.i!=h. Pre-certification Transformers

MPS PROFIBUS-DP INTERFACE

Supplemental Motor Protection Devices Specifications

SE-330/SE-330AU/SE-330HV PROFIBUS-DP INTERFACE

Safety through proper system Grounding and Ground Fault Protection

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Overcurrent and Overload Protection of AC Machines and Power Transformers

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

Summary of the Impacts of Grounding on System Protection

Deploying Current Transformers in Applications Greater Than 200 A

Power Metering Fundamentals Jim Spangler Cirrus Logic 1 March 2011

Short Circuit Current Calculations

7/15/2002 PP.AFD.08 1 of 28

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Preface...x Chapter 1 Electrical Fundamentals

Power. Power is the rate of using energy in joules per second 1 joule per second Is 1 Watt

ADJUSTABLE SPEED DRIVES FS1

Generator Protection GENERATOR CONTROL AND PROTECTION

Table of Contents. Proximity Sensors. IEC Limit Switches. Encoders. Current Sensors. Section 17

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority

Earth Fault Protection

Transformer Waveforms

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

AF91 Adjustable Frequency Drives Series B

Digital Line Protection System

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

OVEN INDUSTRIES, INC. Model 5C7-362

Practical Tricks with Transformers. Larry Weinstein K0NA

ECET Industrial Motor Control. Variable Frequency Drives. Electronic Motor Drives

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

Supplemental Motor Protection Devices Specifications

Industrial Electrician Level 3

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

High Frequency SineWave Guardian TM Filter

Substation applications

Lecture 22 - Three-phase square-wave inverters

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Phoenix DX Clean Power (18 Pulse) AC Drive

MV network design & devices selection EXERCISE BOOK

Power Factor & Harmonics

Protective Relays Digitrip 3000

Problems connected with Commissioning of Power Transformers

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Improve asset protection and utilization

Fundamentals of Power Quality

AC Sources for IEC 1000 Harmonics and Flicker Testing

Alternating Current Page 1 30

Low Pass Harmonic Filters

Effective Harmonic Mitigation with Active Filters

BUS2000 Busbar Differential Protection System

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security

E3 Adjustable Speed Drive Engineering Specification

RCMS460 and RCMS490 Series

CHAPTER 6 ANALYSIS OF THREE PHASE HYBRID SCHEME WITH VIENNA RECTIFIER USING PV ARRAY AND WIND DRIVEN INDUCTION GENERATORS

MINUTES OF PRE BID MEETING

GPM. Field and Stator Ground Fault Protection Modules. Instruction Manual AF1. GE Grid Solutions

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Trees, vegetation, buildings etc.

Single-phase Variable Frequency Switch Gear

Open-Delta Systems Affect Variable Frequency Drives

DEPARTMENT OF DEFENSE HANDBOOK

COPYRIGHTED MATERIAL. Index

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

1 INTRODUCTION ORDER CODE / INFORMATION

Conventional Paper-II-2011 Part-1A

Electromagnetic Harmonic Filters Technical Guide

3Ø Short-Circuit Calculations

Catastrophic Relay Misoperations and Successful Relay Operation

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Transcription:

GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED POWER-DISTRIBUTION SYSTEMS WITH ADJUSTABLE-SPEED DRIVES 1

TWO BASIC PROBLEMS 1. Prevent nuisance or false trips because of noise on loads or feeders without an ASD. 2. Reliably detect a ground fault on an ASD-driven motor load. 2

SOME BACKGROUND 3

SENSING GROUND FAULTS on a grounded electrical system THE BEST WAY TO DETECT A GROUND FAULT: CURRENT SENSING - usually with a zero-sequence core-balance current transformer (CT or ZSCT) - permits selective coordination and ease of finding a fault 4

Q: What is a Core-Balance Zero-Sequence CT? Answer: Any window-type current transformer is a core-balance zero-sequence CT when all current-carrying conductors are passed through the CT window. Specialized CT s for low-level fault detection are available (EFCT-x, SE-CS30-x). 5

LIMITING PHYSICAL FACTORS LOW-LEVEL GROUND-FAULT DETECTION: PHYSICAL LIMITING FACTORS 1.) System Capacitance 2.) Unbalanced 1-Phase Loads 3.) Current-Sensor Limitations 4.) Harmonic Components 1, 2, & 4 result in current flowing to earth in an unfaulted system. 3 can result in incorrect indication of a ground fault. 6

SYSTEM CAPACITANCE Capacitor Noun: A device used to store an electric charge, consisting of one or more pairs of conductors separated by an insulator. All electrical systems have phase-to-ground capacitance distributed throughout the system modeled here as lumped values in a simple singleload system 7

CHARGING CURRENT 2 1 Definition of charging current: The current that flows when one phase of an ungrounded system is shorted to ground Note: A core-balance CT at 1 will measure charging current A core-balance CT at 2 will measure zero 8

CHARGING CURRENT & SYMPATHETIC OPERATION A4 A4 READS I Z A core-balance CT on an unfaulted feeder will detect its feeder s charging current when a ground fault occurs on another feeder. To avoid sympathetic tripping (alarming), protection must be set above the charging current level Protection level can be set below charging current if sympathetic tripping (alarming) is acceptable Charging current does not flow to the system neutral 9

CAPACITANCE UNBALANCE 51G Balanced Phase-to-Ground Capacitance: Xa=Xb=Xc Phase capacitive currents are equal Core-balance CT reads zero. Unbalanced Phase-to-Ground Capacitance: Xa Xb Xc Phase capacitive currents are not equal Core-balance CT reads a finite value 10

VOLTAGE UNBALANCE Voltage Unbalance, Van Vbn Vcn: May be the result of unbalanced singlephase utility loads Voltage unbalance combined with capacitance unbalance forces capacitive current unbalance resulting in steady-state zero-sequence current. These affects are usually small, but may affect low-level earth-fault current detection 11

UNBALANCED LOAD CURRENTS Do unbalanced load currents cause ground-fault trips? 51G No. If there is no leakage to ground, unbalanced load currents add to zero, therefore no core-balance CT output. Ia + Ib + Ic = 0 Balanced or Unbalanced 12

CURRENT TRANSFORMERS Practical Current-Transformer Considerations: Excitation Current minimum primary current that will give an output. can require specialized ZSCT. Saturation output current not proportional to large primary current (high-level fault) Local Saturation output with no zero-sequence current surge currents and poor conductor placement correct with proper conductor location and flux conditioner 13

HARMONIC FREQUENCIES Often result from use of Adjustable-Speed Drives and Solid-State Starters ASD s build waveforms in a series of steps. Each step includes harmonic frequencies. Phase Conductor Earth X C XC = 1 2πfC Where C=capacitance f=frequency Capacitive impedance (X C ) decreases at higher frequencies Current per volt increases at higher frequencies The affect of capacitive and voltage unbalance are greater at higher frequencies current flowing to ground, with no fault present 14

Building a Sine Wave DC Voltage is switched on and off Resulting AC current is a noisy sine wave. A real example 15

TRIPLEN HARMONICS: A Special Case In 3-phase systems third-order harmonics are in-phase their values add; they do not cancel + + = Example: Fundamental & 3rd harmonic Can cause nuisance ground-fault tripping 16

Harmonic Currents Harmonic currents can flow to earth through system capacitance and cause nuisance earthfault tripping Triplen harmonics are detected by core-balance current transformers because they don t cancel Solution: set ground-fault pickup level above harmonic current background level, or filter the harmonics with a protective device that responds only to the fundamental frequency 17

Required Filter Characteristics Filtering Requirements: Respond to the fundamental frequency to detect true zero-sequence ground-fault current Do not respond to dc-offset caused by starting motors Do not respond to harmonic-frequency components The Discrete Fourier Transform has these characteristics Ip = 2 m m 1 n= 0 2πn I(n) sin m 18

Example of 50-Hz Fundamental with 150-Hz Component 2-component Signal 2 1.5 1 Amperes 0.5 0 50 Hz 0 4 8 12 16 20-0.5 150 Hz -1-1.5 Sample -2 Time (ms) 50 Hz Component 150 HzComponent EF Current Waveform Samples Sampler is set to take a known number of samples per 50 Hz cycle (here 20 samples/cycle) 19

DFT Measures the Desired Frequency Sample Number (n) 50 Hz Comp. I f (n) 150 Hz Comp. Sampled Value I(n) I f (n)sin(2*pi*n/20) I(n)sin(2*pi*n/20) 0 0.000 0.000 0.000 0.000 0.000 1 0.437 0.381 0.818 0.135 0.253 2 0.831 0.448 1.280 0.489 0.752 3 1.144 0.146 1.290 0.926 1.043 4 1.345-0.277 1.068 1.279 1.016 5 1.414-0.471 0.943 1.414 0.943 6 1.345-0.277 1.068 1.279 1.016 7 1.144 0.146 1.290 0.926 1.043 8 0.831 0.448 1.280 0.489 0.752 9 0.437 0.381 0.818 0.135 0.253 10 0.000 0.000 0.000 0.000 0.000 11-0.437-0.381-0.818 0.135 0.253 12-0.831-0.448-1.280 0.489 0.752 13-1.144-0.146-1.290 0.926 1.043 14-1.345 0.277-1.068 1.279 1.016 15-1.414 0.471-0.943 1.414 0.943 DFT of 50 Hz 16-1.345 0.277-1.068 1.279 1.016 17-1.144 component -0.146-1.290 = 14.142 0.926 1.043 18-0.831-0.448-1.280 0.489 0.752 19-0.437-0.381-0.818 0.135 0.253 14.142 14.142 DFT of signal = 14.142 The result for the multiple-frequency signal is the same as the result for the 50 Hz component Only one cycle is required to calculate earth-fault current, and is updated every sample 20

A SOLUTION FOR AVOIDING FALSE TRIPS IN HARMONIC-RICH SYSTEMS Use a ground-fault protection device incorporating sampling technology and DFT processing for: DC-offset filtering Harmonic filtering Speed - one cycle maximum detection time Examples are: SE-701, SE-704, SE-330, MPU-32, MPS, FPU-32, FPS 21

What about detecting a ground fault in a VFD circuit when the VFD is operating outside of 50-60 Hz? Another filtering algorithm is necessary; Peak Detection. 22

THE TROUBLE WITH VFD BUILT-IN GROUND-FAULT PROTECTION MANY LOW-VOLTAGE DRIVES HAVE A FIXED (Non-Adjustable) GROUND-FAULT PROTECTION LEVEL. Often presumes a solidly grounded system Often a large percentage (eg: 50%) of rated current Often not compatible with a high-resistance grounded system THESE DRIVES REQUIRE SUPPLEMENTAL GROUND-FAULT PROTECTION 23

Why is Inability to Detect a GF in an ASD System a Problem? 24

Why is Inability to Detect a GF in an ASD System a Problem? 25

What Happened Here? The System: Low-voltage Variable-speed drive 5-A neutral-grounding resistor (NGR) Some type of fault occurred with The Result: Melted copper and steel Luckily, no fire Ground was obviously involved But the ground fault was not detected! 26

What Happened Here? The System: Low-voltage Variable-speed drive 5-A neutral-grounding resistor (NGR) Could the damage be the direct result of the ground fault? No. P = I 2 R and I GF 5 A. Furthermore, for 5 A to flow, the fault impedance R must = 0 Ω (so P=0). As fault impedance rises, current decreases and power dissipation at the fault is small. Fault Power Dissipation 600-Vll, 5-A NGR Watts 600 400 200 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 27 Fault Impedance (Ohms)

What Happened Here? A Theory A phase-to-winding connection became disconnected in the terminal box, but electrical continuity was maintained by (hi-impedance) contact with the grounded terminal-box cover. 51G > 5 A Motor I θ = I motor + 5 A, max VFD I GF = 5 A max This fault wouldn t cause an overcurrent trip And the ground fault was not detected 28

THE CHALLENGE IN VFD GROUND-FAULT PROTECTION CHALLENGE: RELIABLY DETECT A LOW- LEVEL GROUND FAULT ACROSS VFD OPERATING-FREQUENCY RANGE WITHOUT NUISANCE TRIPS. BIG QUESTION WHERE TO PUT THE CT? LINE SIDE? LOAD SIDE? WE DID SOME TESTING; and invented a new product 29

Littelfuse Startco R&D Lab VFD Ground-Fault Test Setup We set up a system with an NGR-grounded three-phase supply to a VFD feeding a motor, with a controlled ground fault, protection relays, and instrumentation 30

Littelfuse Startco R&D Lab VFD Ground-Fault Test Setup 31

Littelfuse Startco R&D Lab VFD Ground-Fault Test Setup Analog outputs from three SE-701 s were recorded. EFCT-1 Current Transformers were input devices. 32

Littelfuse Startco R&D Lab VFD Ground-Fault Test Setup An adjustable decade box was used to simulate a ground fault at various system locations. Digital RMS meters and a power analyzer were used to confirm SE-701 Ground Fault Monitor readings. 33

Sample 1: No Ground Fault VFD Phase-Voltage Spectrum: 30 Hz No Filter Phase X C Earth VL-G XC = 1 2πfC 34

Sample 1: No Ground Fault VFD Phase-Voltage Spectrum: 30 Hz 500-Hz Low-Pass Filter VL-G 35

Sample 2: System with a Ground Fault VFD Ground-Fault Spectrum: 60 Hz, 0.3 A No Filter VL-G IL-G VN-G IN-G 36

Sample 2: System with a Ground Fault VFD 60 Ground-Fault Hz Sample with Spectrum: 60 Hz, 0.3 A 500-Hz 500-Hz Low-Pass Low-Pass Filter Filter VL-G IL-G VN-G IN-G 37

Sample 3: System with a Ground Fault VFD Ground-Fault Spectrum: 10 Hz, 1 A No Filter VL-G IL-G VN-G IN-G 38

Sample 3: System with a Ground Fault VFD 10 Ground-Fault Hz Sample with Spectrum: 10 Hz, 1 A 500-Hz 500-Hz Low-Pass Low-Pass Filter Filter VL-G IL-G VN-G IN-G 39

SE-70x Monitors Have a Filter-Selector Switch SE-701 top view 40

SE-70x Filter Characteristics 1.2 1.1 1 0.9 SE-70X Frequency Response Variable Frequency Peak Detection 1.2 1.1 1 0.9 SE-70X Frequency Response Fixed Frequency 50/60 Hz DFT Filter Output 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 10 20 30 40 50 6070 100 200 300 400500 700 1000 Frequency (Hz) Filter Output 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 10 20 30 40 50 60 7080 100 200 300 400 500 Frequency (Hz) Peak-Detection Filter (labeled as Variable Frequency) DFT Filter (labeled as Fixed Frequency) 41

What about CT Location? A Littelfuse Startco Ground-Fault Monitor can be installed upstream of the drive. REALLY?? 42

Yes. Really. A VFD DOES NOT ISOLATE THE LOAD FROM THE SUPPLY Drive Frequency (Hz) Fault Current (ma) (No Filter) NGR Current (ma) SE-701 Filter Selection Upstream SE-701 Downstream SE-701 NGR SE-701 60 316 326 DFT 251 251 243 50 364 375 DFT 260 260 260 40 513 537 DFT 270 270 270 30 735 760 DFT 330 330 300 25 910 945 DFT 340 340 318 43

Yes. Really. Drive Frequency (Hz) A VFD DOES NOT ISOLATE THE LOAD FROM THE SUPPLY Fault Current (ma) (No Filter) NGR Current (ma) SE-701 Filter Selection Upstream SE-701 Downstream SE-701 NGR SE-701 60 280 295 Peak 264 268 263 50 299 317 Peak 268 265 253 40 353 371 Peak 268 268 258 30 432 453 Peak 260 260 270 20 670 700 Peak 325 312 312 10 1000 1030 Peak 400 400 380 44

A VFD Does Not Isolate the Load from the Supply ~ M 45

Ground-Fault Pickup Setting Guide 1 SE-701 Frequency Response SVX9000 Drive 0.9 Normalized Response 0.8 0.7 0.6 0.5 0.4 0.3 0.2 10 15 20 25 30 35 40 45 50 55 60 Drive Output Frequency From the chart, multiply the desired pickup at a frequency by the Normalized Response Value. 46

What About a DC-Bus Fault? Can an AC-sensing relay detect a DC fault? 47

How a VFD Makes DC from AC: Start with Full-Wave Rectification Show four waveforms. 1-phase 60-hz sine, 3-phase 60-hz sine, rectified 1 and 3-phase sine Single-Phase Sine Wave On Average, the value is 0 Full-Wave Rectified Singe-Phase Sine Wave On Average, the value is +ve 48

How a VFD Makes DC from AC: Start with Full-Wave Rectification, 3θ Three-Phase Sine Waves On Average, the value is 0 Full-Wave Rectified Three-Phase Sine Waves On Average, the value is +ve 49

DC from AC AC Ripple DC 50

VFD Negative DC-Bus Fault, 500 ma VL-G IL-G VN-G IN-G All of the measurements show the 180-Hz ripple. 51

DC Fault Spectrum Analysis 52

DC Fault Spectrum Analysis 180 Hz and Harmonics 53

ONE SOLUTION FOR TWO PROBLEMS FEEDER 1 LOAD 1 SE-701 51G VFD LOAD 2 SE-701 51G FEEDER 2 54

SOLUTIONS FOR GROUND-FAULT DETECTION in an HRG SYSTEM with ASD s RUNNING NEAR LINE FREQUENCY For non-asd circuits, use a detection device with a narrow band-pass filter 1.2 SE-70X Frequency Response Fixed Frequency 50/60 Hz DFT 1.1 1 0.9 Filter Output 0.8 0.7 0.6 0.5 0.4 Frequency (Hz) For ASD circuits, use a detection device with a low-pass filter 0.3 0.2 0.1 0 10 20 30 40 50 60 7080 100 200 300 400 500 1.2 1.1 1 0.9 SE-70X Frequency Response Variable Frequency Peak Detection Filter Output 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 10 20 30 40 50 6070 100 200 300 400500 700 1000 Frequency (Hz) 55

SOME ASD S ARE USED AT VERY LOW SPEEDS <20 Hz 1.2 SE-70X Frequency Response Fixed Frequency 50/60 Hz DFT 1.1 1 0.9 Filter Output 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 10 20 30 40 50 60 7080 100 200 300 400 500 Frequency (Hz) 1.2 SE-70X Frequency Response Variable Frequency Peak Detection 1.1 1 0.9 Filter Output 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 10 20 30 40 50 6070 100 200 300 400500 700 1000 Frequency (Hz) 56

SOMETIMES A CONVENTIONAL GROUND- FAULT RELAY WON T DO SOMETIMES ACCURATE DC-to-60 Hz MEASUREMENT IS NECESSARY SOMETIMES ACCURATE HIGH-FREQUENCY MEASUREMENT IS NECESSARY 57

SE-70x Filter Characteristics 1.2 1.1 1 0.9 SE-70X Frequency Response Variable Frequency Peak Detection 1.2 1.1 1 0.9 SE-70X Frequency Response Fixed Frequency 50/60 Hz DFT Filter Output 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 10 20 30 40 50 6070 100 200 300 400500 700 1000 Frequency (Hz) Filter Output 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 10 20 30 40 50 60 7080 100 200 300 400 500 Frequency (Hz) 400 Hz Peak-Detection Filter (labeled as Variable Frequency) 1000 Hz 90 Hz DFT Filter (labeled as Fixed Frequency) 58

Introducing the EL731 EL731 AC/DC SENSITIVE EARTH-LEAKAGE RELAY 59

THERE IS A NEW APPROACH TO WIDE-BAND CURRENT MEAUSUREMENT THE EL731 accurately measures ground-fault current in the frequency range of 0 to 6 khz using conventional CT s AC/DC EARTH-LEAKAGE RELAY 60

Benefit #1 Provides low frequency to high frequency protection capability with one relay 0 to 6 khz 1.1 1 0.9 EL731 Frequency Response SE-731 Frequency Response Normalized Response 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 CT1 CT2 0 10 20 30 50 70 100 200 300 500 1000 2000 5000 10000 20000 Frequency (Hz) 61

AC/DC EARTH-LEAKAGE RELAY CURRENT TRANSFORMER #1 CT1 MEASURES 0 TO 100 Hz 0 Hz = DC CT1 IS A STANDARD SENSITIVE EARTH-FAULT CT AND A DCCT USED ALONE OR WITH CT2 30 T0 5,000 ma SETTING RANGE EFCT-SERIES 62

AC/DC EARTH-LEAKAGE RELAY CURRENT TRANSFORMER #2 CT2 MEASURES 20 TO 6,000 Hz A STANDARD SENSITIVE EARTH-FAULT CT USED ALONE OR WITH CT1 30 T0 5,000 ma SETTING RANGE EFCT-SERIES 63

CT1 AND CT2 USE ONE OR BOTH COMBINED 0 TO 6,000 HZ FREQUENCY RESPONSE 64

Benefit #2 EFCT series CT used on previous applications can be re-used. Upgrade SE-701 applications. 65

Benefit #3 Separate Alarm and Trip relay outputs 3 programmable Form-C relays Early detection of alarm conditions allows prevention of extended downtime. 66

DC Applications 67

DC Application Must be grounded DC supply. 68

Benefit # 4 Feature: Ability to detect DC faults with a CT Benefit provides ability to locate the fault on a grounded-dc system. Improves upon previous DC ground-fault detection methods that would only tell you the system had a fault and possibly which bus was faulted. (SE-601) 69

But Wait There s more A fan cooled motor operated at low speed draws less air over the windings. Less cooling equates to higher winding temperature. 70

Feature and Benefit #5 The only ground-fault relay on the market with temperature protection. RTD or PTC Thermistor input for temperature measurement and protection. Allows measurement of motor, load or drive temperature. Many drives operate motors at lower speed (less cooling) but most do not offer temperature protection. 71

Features and Benefits #6 and #7 Communications module available to send info to data network. Flash upgradeable via optional communication adapter. Allows field modification of firmware if ever required. 72

Feature and Benefit #8 Password Protection 1 st of our ground-fault relays with this feature. 73

Features and Benefits #9 and #10 Metering on the door. 2-Line OLED display Panel-mount adapter not required for door mounting. No PMA-55 or PMA-60 required. Optionally available surface-mount adapter 74

Accessories 75

EL731 Benefits Reviewed 1. Full Frequency Coverage 2. Re-use existing EFCT series CT 3. Detection and fault location on DC systems 4. Separate Trip and Alarm Setpoints 5. Overtemperature Protection 6. Communications Capable GF relay 7. Firmware Upgradeable 8. Password Protected 9. Panel Mount Ready; optional surface mounting 10. Metering 76

Ground-Fault Protection for VFD s on High-Resistance-Grounded Systems SE-701 Ground-Fault Monitor Pickup: 50 ma to?? A SE-704 Earth-Leakage Monitor Pickup: 10 ma to 5 A EL731 AC/DC Sensitive Earth-Leakage Relay Pickup: 30 ma to 5 A Frequency Response: 32 to 86 Hz, 20 to 420 Hz Frequency Response: 0 to 90 Hz, 20 to 90 Hz, 20 to 3,000 Hz, 190 to 6,000 Hz, 0 to 6,000 Hz 77