Comparison of recloser and breaker standards

Similar documents
The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

Distribution/Substation Transformer

How to maximize reliability using an alternative distribution system for critical loads

Two- and three-phase MagneX interrupter

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Medium voltage circuit breaker technical guide

Three-Phase VFI Padmount Transformers. Double Duty in a Single Package. www. ElectricalPartManuals. com

CONTENTS. 1. Introduction Generating Stations 9 40

TABLE OF CONTENT

NOVA-TS Triple-Single Recloser and Form 5/TS Control Frequently Asked Questions

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Figure 1. Two- and Three-phase MagneX Interrupter.

Eaton s Cooper Power Series DEADFRONT ARRESTERS

Power systems Protection course

Single Line Diagram of Substations

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester

BED INTERCONNECTION TECHNICAL REQUIREMENTS

35 kv Class M.O.V.E. DirectConnect elbow arrester

HIGH VOLTAGE CIRCUIT BREAKERS

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

ISSN: Page 298

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

Medium Voltage Switchgear

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

1% Switchgear and Substations

3Ø Short-Circuit Calculations

Power-Sure 700. Technical Data TD158001EN. Contents

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

Electrical Protection System Design and Operation

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

E N G I N E E R I N G M A N U A L

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

Unit 2. Single Line Diagram of Substations

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

One line and Three line diagrams Schematics Wiring Diagrams Logic ladders Ancillary prints Pictorial instructions

Transformer Protection

INTERNATIONAL STANDARD

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

Notes 1: Introduction to Distribution Systems

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Impact Assessment Generator Form

Back to the Basics Current Transformer (CT) Testing

SINGLE-PHASE VSV SWITCH

Preface...x Chapter 1 Electrical Fundamentals

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

SECTION AUTOMATIC TRANSFER SWITCH

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

THREE-PHASE SHORT-CIRCUIT TESTING OF HIGH-VOLTAGE CIRCUIT-BREAKERS USING SYNTHETIC CIRCUITS

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

Adaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers

Enclosed circuit breaker (ECB) with Arcflash Reduction Maintenance System

Effective February 2017 Supersedes January 2012 (CP1122)

Overcurrent and Overload Protection of AC Machines and Power Transformers

7. INSPECTION AND TEST PROCEDURES

Industrial Electrician Level 3

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Generator Protection GENERATOR CONTROL AND PROTECTION

Appendix D Fault Levels

Transmission Facilities Rating Methodology for Florida

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software

Short Circuit Current Calculations

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

Protective Relaying for DER

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

Note: The let-through of the protective device must be equal to or less than the short-circuit current rating of the component being protected.

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

Capacitor protection relay

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

ETAP PowerStation 4.0

PROTECTION of electricity distribution networks

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Effective November 2017 Supersedes May 2017

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

Substation Design Volume VII

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Burdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

EI HIGH VOLTAGE INSULATION TESTING POLICY

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

GE Power Management. Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C

VACUUM INTERRUPTER APPLICATION NOTES Filename: VIAN X-Rays and Vacuum Interrupters Revision: 0 PAGE 1

Generation Interconnection Requirements at Voltages 34.5 kv and Below

ECP HV INSULATION TESTING

COPYRIGHTED MATERIAL. Index

Transcription:

s Technical Data TD280024EN Supersedes February 1994 (R280-90-5) COOPER POWER SERIES Comparison of recloser and breaker standards

Technical Data TD280024EN Comparison of recloser and breaker standards Introduction Automatic circuit reclosers and high-voltage circuit breakers provide alternate means for distribution circuit protection. To aid in the evaluation and application of these devices, the ratings and standards of reclosers and breakers are compared here. For clarity and conciseness, only those parts of the standards and ratings are selected that are of most significance in the application and comparison of reclosers and breakers, or those items that have been a source of confusion in the past. The recloser standards used is ANSI/IEEE C37.60-1981 and C37.61-1973. Circuit breaker standards used for this comparison are C37.04-1979, C37.06-1987 and C37.09-1979. General comparison Perhaps the most significant difference between a recloser and a breaker is that the recloser was designed as a selfcontrolled device. Standards have been established and capabilities determined within the characteristics of the integral control scheme of the recloser. Because a breaker was designed for use with a separate relay/control scheme, a breaker must be defined and rated for a wide variety of relay/control sequences. Thus, the breaker standard recognizes, and the breaker must be built to permit, a range of permissible values for: Maximum tripping delay Reclosing interval Short-time current As pertains to a recloser, these capabilities are defined by the recloser s predetermined time-current characteristics and reclosing settings. Definitions Following are the definitions taken from ANSI/IEEE C37.100-1981. IEEE Standard Definition for Power Switchgear. Automatic Circuit. A self-controlled device for automatically interrupting and reclosing an alternating-current circuit, with a predetermined sequence of opening and reclosing followed by resetting, hold closed, or lockout. Circuit. A mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions and also, making, carrying for a specified time and breaking currents under specified abnormal circuit conditions such as those of short circuit. Ratings Difference in design and application show up readily when comparing the ratings. Rated interrupting current A recloser is rated on the basis of the maximum symmetric fault current it is designed to interrupt. This current remains a constant for the complete operating-voltage range, except for some recloser ratings where the interrupting current is increased at some lower voltage as shown in Example 1 below. Example 1. Type WE recloser Operating voltage (kv) 2.4 to 4.8 12,000 above 4.8 to 15.5 10,000 Rated interrupting current (amp) Historically, circuit breakers have been rated on a constant MVA basis, with a K factor used to determine the minimum voltage for the constant MVA rating. See Example 2. Example 2. rated 500 MVA A breaker rated 500 MVA nominal, with a rated short-circuit current of 18kA at 15.5 kv, K Voltage Range Factor of 1.29. The K factor established the minimum voltage for constant MVA as: 15.5 kv = 12 kv 1.29 The Symmetrical Current Interrupting Capability at 12kV would be: 18KA x 15.5kV = 23.25 ka 12.0KV For voltages lower than 12kV, the interrupting current capability is constant at 23.25 ka. The revised breakers standards have abandoned the constant MVA rating approach. The K factor is now 1.0, meaning that the interrupting current is constant for any operating voltage. This is equivalent to the rating method used for reclosers, per C37.60-1981. Table 1. Typical breaker ratings taken from Table 2 C37.06-1987. Rated max. voltage kv, RMS Rated voltage range factor K Rated cont. current at 60H 3 Amp, RMS 15.5 1.0 600, 1200 12.5 15.5 1.0 1200, 2000 20.0 25.8 1.0 1200, 2000 12.5 25.8 1.0 1200, 2000 25.0 Maximum symmetric interrupting Capability ka, RMS Duty cycle The term duty cycle has been used to mean different things for reclosers and breakers. Duty cycle is a standardized test sequence to which a recloser is subjected to establish its minimum life and rated interrupting current. A recloser duty cycle (Standard Operating Duty) establishes the capability of a recloser to interrupt a relatively large number of faults, tested at three separate current values. In Example 3, the Type VSA12 recloser duty cycle is a total of 232 operations consisting of 88-112-32 interruptions at the specified currents. 2

Comparison of recloser and breaker standards Technical Data TD280024EN Example 3. Type WE (oil interrupters) and Type VSA12 (vacuum inter- rupters) duty cycle. Current in % of interr. current Type WE Minimum X/R No. of unit operations Type VSA12 Minimum X/R No. of unit operations 15-20 3 28 4 44 (88)* 45-55 7 20 8 56 (112)* 90-100 14 10 15 16 (32)* Total Operations 58 116 (232) * Number in parentheses is actual duty cycle as established by test. The smaller number - 116- is half-life. standards allow the manufacturer to test only to half-life because of the expense and time required for a test of the duty cycle of a vacuum recloser. The entire operating duty is performed with the recloser adjusted to give the maximum permissible number of unit operations before lock- out, with the minimum reclosing intervals for which the recloser is designed. Eaton Cooper Power series reclosers are tested for a sequence of O+INSTANTANEOUS+CO+2s+CO+2s+CO. The Rated Standard Operating Duty (Standard Duty Cycle) of a circuit breaker shall be two unit operations with a 15 second interval between operations (CO+15s+CO). (C37.04-5.6). In addition, the breaker must be capable of a number of operations in which the sum of the currents interrupted does not exceed 400 percent of the required asymmetrical interrupting capability of the breaker at its operating voltage, for fault currents between its rated continuous current and 85 percent of its required asymmetrical interrupting capability at its operating voltage. (C37.04-5.10.3.3.1). NNote: The 400 percent value relates to oil circuit breakers. ANSI/IEEE 37.04g-1986 specifies a duty of 800 percent for hermetically sealed interrupting units. This would include vacuun interruption and sealed SF6 interrupter units. Additional interrupting duty at the rated continuous cur- rent is specified in Standard C37.06, Table 8. For exam- ple, a 600- or 1200-amp breaker is required to close and interrupt the rated continuous current for 100 operations. The life of a breaker before maintenance (the equivalent of a recloser duty cycle) is specified in ANSI Standard C37.04 which includes a method for determining breaker life for currents between rated continuous current and 85% of the required asymmetrical capability. Comparison of duty cycle ratingse: recloser vs breaker To see how these ratings compare in establishing the recloser or breaker life before maintenance, below is a comparison of the Type VSA20A recloser duty cycle and life and a breaker rated 20kA, 15kV, calculating total oper- ations available at currents 50% and 100% of the maxi- mum symmetric current rating: Example 4. VSA20 & VSA20A, rated 20,000 amps symmetric at 14.4kV operating voltage with a duty cycle ofe: The total number of unit operations for 50% and 100% faultcurrent levels are calculated in accordance with Appendix C of ANSI C37.61-1973 (Guide for the Application, Operation, and Maintenance of Automatic Circuit s): (4,000 amps) 1.5 = 25.3 x 10 4 ; x 88 operations = 22.26 x 10 6 (10,000 amps) 1.5 = 100 x 10 4 ; x 112 operations = 112.00 x 10 6 (20,000 amps) 1.5 = 282.4 x 10 4 ; x 32 operations = 90.37 x 10 6 Total duty factor = 224.63 x 10 6 No. of unit operations at 10,000 amps (50%) = 224.63 x 10 6 = 224 operations 100 x 10 4 No. of unit operations at 20,000 amps (100%) = 224.63 x 10 6 = 79 operations 4 282.4 x 10 Example 5. For a 20 ka, 15kV breaker, calculated in accordance with C37.04, the number of unit operations for 50% and 100% ise: At 14.4kV, the symmetrical current interrupting capability is 20,000 amps. Assuming a maximum S factor of 1.4 (S factor for asymmet- ric capability multiplier based on a circuit X/R ratio of 15, equivalent to the maximum X/R ratio of recloser test requirements), the asymmetrical interrupting capability is: 20,000 x 1.4 = 28,000 Amps And, according to C37.04 (oil) and C37.04g-1986 (vacuum and SF 6 28,000 x 400% = 112,000 Amps (oil) 28,000 x 800% = 224,000 Amps (vacuum/ SF 6 ) At 10,000 amps (50% of 20,000), the number of unit operations is: 112,000 = 11.2 (oil) 10,000 224,000 10,000 = 22.4 (vacuum/ SF ) 6 At 20,000 amps, the number of unit operations is: 112,000 = 5.6 (oil) 20,000 224,000 20,000 =11.2 (vacuum/sf ) 6 Comparison of device life before maintenance at 50% and 100% of rated interrupting current: 50% Maximum Interruptinge: : 224 operations : 11.2 (22.4) operations 100% Maximum Interruptinge: : 79 operations : 5.6 (11.2) operations NNote: Exercise discretion in using this comparison because it compares device life as defined by standards. Actual device life may be greater than the numbers calculated which would, of course, affect any real world comparison. Current in % of interrupting current X/R No. of unit operations 15-20 4 88 45-55 8 112 90-100 16 32 232 3

Technical Data TD280024EN Comparison of recloser and breaker standards Derating of rated interrupting current for reclosing duty A recloser is capable of its full interrupting rating for a complete four-operation sequence, based on the sequence used to determine the Standard Operating Duty. s, therefore, do not require derating. A breaker is subject to derating (reduction) of its rated interrupting current for an operating sequence having either more operations or a shorter time interval between operations than the standard CO+15s+CO duty cycle. (C37.04-5.10.2.6). Example 6. Derating (per C37.04-5.10.2.6) Select a breaker rated 15.5kV, 20,000 ampere interrupting rating. The 20,000 ampere rating applies for a sequence of CO+15s+CO. Derate for a typical breaker sequence of: O + 0s + CO + 15s + CO + 45s + CO The derating factor D = 9.9% (*) Therefore, the rated interrupting current is: 20,000 x.901 = 18,020 Amps. Derate for a recloser sequence of: O +0s + CO + 2s + CO + 2s +CO The derating factor D = 15.6% (*) Therefore, the rated interrupting current is: 20,000 x.844 = 16,880 Amps. * Calculations of derating factors is included in Appendix A. A recloser with a rated interrupting current of 20,000 Amps will maintain the rated interrupting current of 20,000 Amps for either of these sequences with no derating involved. Required asymmetrical interrupting capability When applied within the maximum symmetric fault current rating and the maximum X/R ratio, a recloser is capable of interrupting any degree of asymmetrical current that can occur. Example 7. Assume a Type VSA20 recloser rated 20,000 Amps sym- metric, maximum X/R of 16, is applied on a circuit with this fault available. The maximum asymmetric current that the circuit can deliver is 20,000 x 1.53 (ratio of asymmetric to symmetric current for circuit X/R of 16) = 30,600 Amps (first major loop of current). The breaker requiring asymmetrical interrupting capability is determined by multiplying the symmetric interrupting capability by a factor S; the value of S shall be 1.4, 1.3, 1.2, 1.1, or 1.0. For breakers having primary arcing contact parting times of 1, 1.5, 2, 3, 4, or more cycles, respectively. (C37.04-5.10.2.2). Required closing-latching-carrying-interrupting capabilities (C37.04-4-4.5.2.4) A breaker is required to close and latch any current which does not exceed 1.6Kx rated short-circuit current. A breaker is required to carry a short circuit current for any time up to permissible tripping delay. standards define a Rated Symmetrical Making Current : The rated symmetrical making current shall be the same value as the rated symmetrical interrupting current, with maximum symmetry corresponding to the X/R ratio. This rating establishes the capability to close in on any symmetric or asymmetric current within the interrupting rating of the recloser. Required short-time current carrying capability This rating establishes the breaker capability to close in on and carry the maximum fault current for a duration of three seconds. standards do not include any short-time requirements. A short-time current capability is established during testing of the Standard Operating Duty (duty cycle), where the recloser must withstand the maximum time delay curve with the maximum available minimum trip value as part of the recloser operating sequence. While not required by standards some reclosers are tested to establish a short-time current rating. Continuous current standard list 600- and 1200-amp continuous current ratings (plus higher ratings such as 2000 and 3000 Amps, beyond recloser ratings). current rating originated with the series-coil type of recloser, utilizing coil ratings of 25, 35, 50, 70, 100, 140, 200, 280, 400 and 560 Amps. Each succeeding rating is approximately 1.4 (or 2) times larger than the previous value. Higher ratings of 800 and 1120 Amps are exten- sions of this number series. Essentially, the 560 and 1120 Amp ratings are equivalent to 600 and 1200 Amp breaker ratings. Several of the larger rated reclosers have continuous current ratings of 800 or 1200 Amps. Load current switching capability Both reclosers and breakers are required to have capability of interrupting load currents. Rated capacitor current switching Capacitance Switching Current ratings are specified in C37.06, Table 2A. No ratings are specified in standards. However, some reclosers have been tested and are rated for Capacitance Current Switching in accordance with C37.06. Rated line charging current switching s have an Overhead Line Current rating. s have a Cable Charging Interrupting Current rating. Ratings for both reclosers and breakers are 2 Amps at 15.5kV; and 5 Amps at 25.8kV (breakers), 27.0kV (reclosers), and 38.0 kv. Rated excitation current switching Under study in the IEEE Switchgear Committee. (C37.04-5.17) s have a Transformer Magnetizing Current Interruption 1 rating. The interrupting rating is equal to 3 % of the continuous current rating of the recloser. 2 4

Comparison of recloser and breaker standards Technical Data TD280024EN Reclosing interval time The reclosing interval is The open-circuit time between an automatic opening and the succeeding automatic reclo- sure. (C37.100) This is the actual dead time (no current flow) of the cir- cuit since the recloser control determines the interval between opening and reclosure. See Appendix B, Figure 1. The reclosing time is The interval between the time when the actuating quantity of the release (trip) circuit reaches the operating value (the breaker being in the closed posi- tion) and the re-establishment of the circuit on the primary arcing contacts on the reclosing stroke. (C37.100). On a reclosing sequence, the actual dead time will depend on the reclosing time sequence as set up on the reclosing relay. For an Instantaneous reclosing, the cir- cuit dead time will be the breaker reclosing time, less the breaker interrupting time. Subsequent dead times are essentially determined by the reclosing relay settings, less the overcurrent relay time delay. See Appendix B, Figure 2. Various breaker specification considerations Beyond the basic comparison of standards and ratings, customer specifications frequently call for features that have become somewhat standard for breakers. Because of differences in design and construction, it is impossible and often not worth the customer s expense - to completely satisfy some of these requirements in reclosers: 1. Ten stage auxiliary switch This is frequently specified in customer specifications. s can be equipped with a three-stage auxil- iary switch as an accessory and, where required, a total of five stages can be provided. This has gener- ally been satisfactory. Typically, breaker requirements include the use of four stages for control wiring, leaving six stages available for customer use. When an auxiliary switch is provided on reclosers, all stages are available for customer use. 2. Bushings. specifications sometimes specify condenser- type or transformer-breaker-interchangeable bushings or bushings per ANSI C76.1. a. Condenser type. bushings are condenser type when the size, use and dielectric requirements dictate. Most recloser bushings are not condenser type. bushings are designed to be completely adequate with regard to dielectric ratings and performance, size and operation of reclosers. b. Transformer-breaker interchangeable. bushings are not transformer-breaker interchangeable. This requirement would dictate a considerably larger bushing for most recloser types and the resulting larger overall recloser size would significantly reduce the savings offered by reclosers. The added cost would be much greater than any possible savings due to interchangeable bushings. c. ANSI C76.1. This is a standard for outdoor apparatus bushings which defines the electrical characteristics, dimensions, mounting flange size, hole spacing, etc. It helps the bushing manufacturer to make bushings that can be used in different types of apparatus, and allows equipment manufacturers and utilities to buy bushings from different bushing suppliers. bushings are designed and tested for use with - and to meet all requirements of - reclosers. This allows the optimum recloser size and design at the lowest cost to the customer. 3. Bushing current transformers. specifications appear to routinely require two sets of BCT s - one set for overcurrent protection and the other set for customer metering and /or additional relaying. Since electronically controlled reclosers are equipped with sensing CT s (1000:1 or 2000:1 ratio) for overcur- rent protection (and for metering with the Form 4C microprocessor control), separate CT s are usually not necessary. When the recloser is used with the Form 3A control, one set of additional CT s is usually required for metering. When the Form 4C control is used, the Form 4C control provides both overcurrent protection and demand metering with the standard recloser sensing CT s. Thus, no additional CT s are required. 4. Red-green lights. Red-green lights are essentially standard equipment for breakers and can be simply and inexpensively provided for breakers because the control panel is usually mounted as part of the breaker in - or adjacent to-the operating cabinet that contains the auxiliary switches. For remote relay mounting, the interconnecting cable or cables involve many conductors so the additional wiring for the red-green lights are available at minimum expense. For a recloser controlled by the Form 4C control, the control provides RECLOSER OPEN and RECLOSER CLOSED indication via the LCD indicators on the front panel. For a recloser controlled by the Form 3A control, the control can be provided with red-green lights as an accessory, operated from the recloser auxiliary switch (and connecting cable) or from a control Status accessory. 5. Cincinnati analyzer. This device provides a plot of the opening and closing operations of a breaker. It is of most use with the larger, more complicated mechanisms where many different linkages, levers and bearings are involved. mechanisms, by nature of their smaller size, simpler design, and higher speed, are not adaptable to this type of analyzer. A recloser mechanical failure will generally be in the nature of complete failure to open or close. Prior to this failure, there is generally little - or no - advance indication that would be detected by this type of equipment. 5

Technical Data TD280024EN Comparison of recloser and breaker standards Appendix a: Calculation of derating factors for breakers for reclosing duty Rated Interrupting Current = 20,000 Amps. For 20,000-Amp interrupting capability, d 1 = 3.3 (C37.06, Figure 2). Derate for reclosing duty of O + 0s + CO + 15s + CO + 45s + CO Derating factor D = 3.3 (2) + 3.3 (15-0) (15-15) + 3.3 = 9.9 15 15 Reclosing capability factor R = 100-9.9 = 90.1% Derate for reclosing duty of O + 0s + CO + 2s + CO + 2s + CO Derating factor D = 3.3 (2)+ 3.3 (15-0) (15-2) (15-2) + 3.3 + 3.3 15 15 15 = 15.6 Reclosing capability factor R = 100-15.6 = 84.4% Appendix b Initiation of short circuit Actuation of trip circuit Primary arcing contacts part Final arc extinction Primary arcing contacts make Time Interrupting time Reclosing interval Release delay Opening time Arcing time Contact parting time Clearing time Figure 1. Reclosing interval - recloser 6

Comparison of recloser and breaker standards Technical Data TD280024EN Initiation of short circuit Energization of trip circuit Extinction of arc on primary contacts Resistor circuit completed on reclosure Parting of primary arcing contacts Parting of secondary arcing contacts Extinction of arc shunting resistor current Primary arcing contacts make me Interrupting time Arc shunting resistor current arcing time Reclosing time Tripping delay Opening time Contact parting time Arcing time Figure 2. Reclosing time - breaker 7

Technical Data TD280024EN Guide to emergency overload capability Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No. TD280024EN July 2017 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series product information call 1-877-277-4636 or visit:.