TS-9100 Electronic Sensors and Transducers. Features and Benefits. G Wide range of enclosures and signal outputs

Similar documents
Series HT-9000 Electronic Humidity Transmitter. Features and Benefits. HT-9000 Electronic Humidity Transmitter

FA-3300 Heavy Duty Electric Actuator. Features and Benefits. FA-3300 Actuator with VG8000 valve. Constant running time. Fixed close-off force.

TS Temperature Sensor and Transducers. Product Bulletin. Wide range of mounting types and signal outputs

Series A36 3- and 4 Stage Thermostats for Refrigeration, Cooling, Heating, Ventilation and Air-conditioning. Feature and Benefits.

FX10 Standard Programmable Electronic controller for HVAC and refrigeration applications. Features and Benefits

Electronic Controls For general purpose and multi stages controls. Features and Benefits

DP2500 DP0100 DP0250 Differential Pressure Transmitter

DP2500 DP0100 DP0250 Differential Pressure Transmitter

CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter

QPM Series Indoor Air Quality Duct Sensors

Type Overview. Technical Data. Outdoor Humidity, Temperature Sensor

HLC-1000 High-limit Humidity Control

WRZ-RMT10K-0 Wireless Remote Temperature Transmitter

Indoor, outdoor and duct resistance thermometers

Relative Humidity & Temperature Transmitters

Type EXT with cable, probe sold

Output Signal Active Note. Output Signal Temperature 22UTH-51 DC V, DC V

HD48V01T HD48V17T HD48V77T. [ GB ] Temperature, Relative humidity and Dew Point transmitters

Screw-in resistance thermometers with plug connector

Output Signal Active Temperature. Electrical data Power Supply DC V, ±10%, 0.5 W

Humidity Temperature Sensor TFG80 Duct version with Polyga measuring element

SensyTemp TSBA (BA R) Resistance thermometer for building automation, machine construction and environmental engineering

Signal converter for electromagnetic flowmeters

ph or ORP Transmitter

USER'S GUIDE. Vaisala HUMICAP Humidity and Temperature Transmitters HMD70U/Y U303EN11

Type PLC Fitting. Valve for Continuous control. Diaphragm valve. Output

Signal converter for electromagnetic flowmeters

TEMPERATURE MEASUREMENT...

QFM21... Duct sensors. Symaro. for relative humidity and temperature

Pressure Transmitter SIL

SEM104 SERIES. SEM104P Pt100 Temperature Transmitter. SEM104TC Thermocouple Temperature Transmitter INDEX SECTION CONTENTS PAGE NO.

CombiTemp TCR6 Standard RTD temperature sensor

FINAL. Hygro-ThermoTransmitter-compact xxx xxx MEETINSTRUMENTATIE. Instruction for use /06/ x4.0xx/1xx/4xx/8xx...

Electromagnetic flowmeters and switches DWM 1000/2000

Online data sheet MAX48N-31V10K12500 MAX48 LINEAR ENCODERS

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

HD 48V01T... HD 4977T...

WATERFLUX 3000 Quick Start

WATERFLUX 3000 Quick Start

Outside Temperature Sensors

FM series position switches

TE-6300P Series Temperature Sensors

DM-45 Digital Multimeter

Original operating instructions Fail-safe inductive sensor GG507S / / 2013

Temperature Sensor for Build-In System G3/8" FLEXadapt

Electromotoric actuators for stroke valves

Temperature Sensor for Build-In System G3/8" FLEXadapt

Product Information Measuring resistor with the Pt100-sensor referring to DIN EN Pt100, Pt500, Pt1000

Temperature Sensor with G1/2" hygienic

Differential pressure sensors

Digital inductive conductivity transmitter

Hygro-ThermoTransmitter-compact xxx

SITRANS F flowmeters SITRANS F US SONOCAL /184 Siemens FI

Digital flow ELEMENT transmitter for continuous flow measurement

Temperature Sensor with Thread G1/4" FLEXadapt

DATASHEET AIR / FLUE GAS TEMPERATURE SENSOR. TSD2-Series

The transducer component converts the measured signal and displays the actual value.

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information

NEUROLOGIC RESEARCH CORPORATION

Precision humidity control/sensing

Digital conductivity transmitter

Fluoro plastic housing for highest chemical and detergent resistance

OPTITEMP TT 20 Technical Datasheet

Overview of types. Technical data

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

Installation Instructions

Room Sensors. for relative humidity and temperature

Digital flow transmitter for continuous flow measurement

Room Sensors. In ventilating and air conditioning plants to acquire relative humidity and temperature in rooms. Humidity measuring range

MODEL AT-10 ANALOG TRANSMITTER

Instruction Manual T5140 T5141 T5145 T5240 T5241 T5245. Programmable transmitter of CO2 concentration with 4-20 ma output. with 0-10 V output

P5201 Universal Programmable Transmitters with Galvanic Isolation

Electronic Thermostat TE-1 Version according to EN

Mineral-insulated resistance thermometers to EN

Original operating instructions Fail-safe inductive sensor GM504S / / 2010

COMMERCIAL. GA Series - Actuator Operating Instructions. GA Non-Spring Return Actuator - (GA24-562) 04/08 /15

Room Temperature Controllers. for heating and cooling systems

MODEL: M2SES SEN TRONIC AG [3] OUTPUT

Analogue temperature controllers

SENSORS. Seamlessly Integrated SENSORS

ActiLume G2 Indus Sensor H513

CDG. Carbon Dioxide - User Manual Gas Detector. 1 Intended Use. 2 Functional Description. 3 Installation. 4 Electrical Connection.

Digital flow ELEMENT transmitter for continuous flow measurement

NOVOHALL Rotary Sensor non-contacting. Series RSC2800 analog

User Manual. PolyGard AT-2000 V3. Infrared Refrigerant Gas Transmitter Serial No. AT March, 2009

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems

Pharma Temperature Sensor G3/8"

Original operating instructions Fail-safe inductive sensor GG507S

DT1100 xx xx xx PS. Isolators, Isolator / Power Supplies. Operating Instructions

RF-RR-T 24V Powered Routers/Temp Sensors

RTD Temperature Sensor omnigrad T -TSM 480, TR 480. Hygienic RTD sensor with Pt 100, class A TSM 480 with electronics programmable via PC

SITRANS F flowmeters SITRANS F M. Flow sensor MAG /48 Siemens FI Overview

Thermocouple - Transducer

SITRANS F flowmeters SITRANS F US. SONOFLO SONO 3000 transmitter. 4/152 Siemens FI Overview

Temperature Sensor Tri-Clamp

omnigrad T - TSM 480, TR 480. Technical Information. RTD Temperature Sensor Hygienic design TSM 480 with electronics programmable via PC

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

Control module 2 circuits AD290. Installation and Service Manual

Transcription:

European Electronic Controls Catalogue Catalogue Section A Product Bulletin TS-9100 Issue Date 09 2000 TS-9100 Electronic Sensors and Transducers I ntroduction The TS-9100 series of electronic temperature sensors and transducers provides a passive or active signal that corresponds with the air or water temperature in heating, ventilating and air conditioning applications. They provide either a 0 10V signal directly proportional to the sensed temperature, or a passive resistive signal NTC or Pt 100. They are primarily designed to be used as an input to a digital controller of the system 9100 family (except for Pt 100), but can be used with other electronic devices. Rod TS-910x-82xx with and without well (immersion or duct applications) Rod fast response TS-910x-83xx Immersion well for cable sensor TS-910x- 850x Ceiling model TS-910x-870x Rod fast response model TS-910x-835x with duct flange TS-9100-8950 Features and Benefits G Wide range of enclosures and signal outputs G PG 13.5 cable inlet for all models with makrolon housing G For immersion applications, well can be mounted before rod sensor is mounted G Rubber gasket and reduced tube diameter for "rod" and "fast rod response" sensors G Different length of tubes and wells for duct and immersion applications Flexible applications Protection against humidity and firm fixation of cable Easy installation and servicing Allows more flexibility in sensor selection Tight fixation to duct and easy installation Senses the temperature at the desired location 2000 Johnson Controls, Inc. A2.1 Order Nr. DS 24.125 E

2 TS-9100 Application overview The TS-9100 series of electronic room temperature sensors and transducers provides, depending on the selected models: a 0 10 V signal directly proportional to the sensed temperature. an NTC K2 resistance signal (see table on page 4). an NTC K10 resistance signal (see table on page 4). a Pt 100 resistance signal (IEC751 platinum sensing element). The different TS-9100 versions with different output signals can be connected to the controllers of the system 9100 series (see Ordering data below), but can also be used with other electronic devices. The 0...10VDC temperature transducers receive a +15 VDC supply voltage, available from the system 9100 controllers. For NTC K10 sensor the temperature range 20 120 C is only used as input to the SC-9100 controller, while the temperature range 0 50 C is used by the TC-8800 controllers. Ordering data Features Applications TS-9101-8101 0...10V Remote element - -40...50 C yes - - - TS-9101-8103 0...10V Remote element - 0 40 C yes - - - TS-9101-8104 0...10V Remote element - 0...100 C yes - - - TS-9101-8212 0...10V Rod *2) 160mm -20...40 C yes - - - TS-9101-8213 0...10V Rod *2) 160mm 0...40 C yes - - - TS-9101-8214 0...10V Rod *2) 160mm 0...100 C yes - - - TS-9101-8222 0...10V Rod *2) 200 mm -20...40 C yes - - - TS-9101-8223 0...10V Rod *2) 200 mm 0...40 C yes - - - TS-9101-8224 0...10V Rod *2) 200 mm 0...100 C yes - - - TS-9101-8225 0...10V Rod *2) 200 mm 0...150 C yes - - - TS-9101-8226 0...10V Rod *2) 200 mm 20 120 yes - - - TS-9101-8227 0...10V Rod *2) 200 mm 50 150 yes - - - TS-9101-8232 0...10V Rod *2) 300 mm -20...40 C yes - - - TS-9101-8233 0...10V Rod *2) 300 mm 0...40 C yes - - - TS-9101-8234 0...10V Rod *2) 300 mm 0...100 C yes - - - TS-9101-8235 0...10V Rod *2) 300 mm 0...150 C yes - - - TS-9101-8252 0...10V Rod *2) 500 mm -20...40 C yes - - - TS-9101-8253 0...10V Rod *2) 500 mm 0...40 C yes - - - TS-9101-8254 0...10V Rod *2) 500 mm 0...100 C yes - - - TS-9101-8322 0...10V Rod fast resp. 200 mm -20...40 C yes - - - TS-9101-8323 0...10V Rod fast resp. 200 mm 0...40 C yes - - - TS-9101-8324 0...10V Rod fast resp. 200 mm 0...100 C yes - - - *1) Or other electronic devices with 0...10 V inputs. *2) Rod sensors can either be for: - Duct applications (alone) - Immersion applications (with well); See dimension drawings on page 7 and 8. 2000 Johnson Controls, Inc. A2.1

TS-9100 3 Features Applications TS-9101-8333 0...10V Rod fast resp. 300 mm 0...40 C yes - - - TS-9101-8353 0...10V Rod fast resp. 500 mm 0...40 C yes - - - TS-9101-8401 0...10V Outdoor - -40...50 C yes - - - TS-9101-8402 0...10V Outdoor - -20...40 C yes - - - TS-9101-8604 0...10V Strap-on - 0 100 yes - - - TS-9101-8703 0...10V Ceiling - 0...40 C yes - - - TE-9100-8501 NTC K2 Cable sensor - - yes - - TE-9100-8502 NTC K10 Cable sensor - - - yes - TS-9103-8220 NTC K2 Rod *2) 200 mm - - yes - - TS-9103-8250 NTC K2 Rod *2) 500 mm - - yes - - TS-9103-8320 NTC K2 Rod fast response 200 mm - - yes - - TS-9103-8400 NTC K2 Outdoor - - - yes - - TS-9103-8600 NTC K2 Strap-on - - - yes - - TS-9103-8700 NTC K2 Ceiling - - - yes - - TS-9104-8220 NTC K10 Rod *2) 200 mm - - - yes - TS-9104-8230 NTC K10 Rod *2) 300 mm - - - yes - TS-9104-8600 NTC K10 Strap-on - - - - yes - TS-9105-8220 Pt 100 Rod *2) 200 mm - - - - yes TS-9105-8230 Pt 100 Rod *2) 300 mm - - - - yes TS-9105-8250 Pt 100 Rod *2) 500 mm - - - - yes TS-9105-8400 Pt 100 Outdoor - - - - - yes TS-9105-8600 Pt 100 Strap-on - - - - - yes TS-9105-8700 Pt 100 Ceiling - - - - - yes *1) Or other electronic devices with 0...10 V inputs. *2) Rod sensors can either be for: - Duct applications (alone) - Immersion applications (with well); See dimension drawings on page 7 and8 Accessories (order separately) Order code Description Material Length External Diam.(mm) TS-9100-8950 Duct flange Stainless steel + brass -- -- TS-9100-8903 Imm.well Copper 260 mm. 12 TS-9100-8902 Imm.well Copper 200 mm. 12 TS-9100-8907 Imm.well Copper 150 mm. 12 TS-9100-8901 Imm.well Copper 120 mm. 12 TS-9100-8905 Imm.well Copper 50 mm. 9 TS-9100-8913 Imm.well Stainless steel 260 mm. 12 TS-9100-8912 Imm.well Stainless steel 200 mm. 12 TS-9100-8917 Imm.well Stainless steel 150 mm. 12 TS-9100-8911 Imm.well Stainless steel 120 mm. 12 TS-9100-8915 Imm.well Stainless steel 50 mm. 9 2000 Johnson Controls, Inc. A2.1

4 TS-9100 A pplication Immersion well length Rod Sensor length Immersion well length Rod Sensor length Immersion well length Rod Sensor length No space for pipe insulation 120 mm TS-9100-89x1 160 mm TS-910x-821x 150 mm TS-9100-89x7 200 mm TS-910x-822x 260 mm TS-9100-89x3 300 TS-910x-823x Space for pipe insulation 120 mm TS-9100-89x1 200 mm TS-910x-822x 200 mm TS-9100-89x2 300 mm TS-910x-823x -- -- Rod sensor with immersion wells, with or without pipe insulation. Termal Insulation of the pipe Pipe Pipe 2000 Johnson Controls, Inc. A2.1

TS-9100 5 Mounting and wiring instructions The TS 9100 can be mounted in virtually any position. For mounting follow the instructions below: Locate the sensors, where they will be exposed to representative conditions. Avoid non-representative air draughts, direct sunlight, etc. For strap-on models use a thermal conductive paste between well or pipe and sensor to improve reaction times. The sensor should not be exposed to direct radiation (lamps, radiators, etc.) or to the sun, since it would lead to incorrect measurement. Wiring instructions For wiring follow the instructions below: All wiring must be in accordance with local regulations and national rules. Do not attempt field repairs. If the transmitter is not operating properly, even though it is wired correctly, it should be replaced NTC "K2" or "K10" Wiring diagrams NTC "K2" and "K10" models Pt 100 1 2 1 2 3 4 Wiring diagrams Pt-100 models I+ U+ U- I- WARNING When wiring or servicing make sure that: the electric voltage to the sensor is switched off to avoid possible damage to the equipment, personal injury or shock. you do not touch or attempt to connect or disconnect wires when electric power is on. T E 1 3 4 + 15 V supply temperature 0...10 V Com Wiring diagrams active 0...10 V models A2.1

6 TS-9100 Resistance tables NTC "K10" models NTC "K2" models Temperature in C Resistance in Ω 0 32.650 5 25.390 10 19900 15 15710 20 12490 25 10000 30 8057 35 6530 40 5327 45 4370 50 3603 55 2986 60 2488 65 2083 70 1752 75 1479 80 1255 85 1070 90 915.3 95 786.7 100 678.3 105 587.3 110 510.3 115 445.0 120 389.3 Temperature in C Resistance in Ω 0 7352.8 5 5717.8 10 4481.5 15 3537.9 20 2812.8 25 2252.0 30 1814.4 35 1470.6 40 1199.6 Pt 100 models The Pt 100 models are equipped with a resistive Pt 100 element according to IEC 751 and DIN 43760. At 0 C the resistance value is 100 Ω. The accuracy is according to IEC 751 Class A Temperature in C Resistance in Ω -50 80.31-45 82.29-40 84.27-35 86.25-30 88.22-25 90.19-20 92.16-15.12-10 96.09-5 98.04 0 100.00 5 101.95 10 103.90 15 105.85 20 107.79 25 109.73 Temperature in C Resistance in Ω 30 111.67 35 113.61 40 115.54 45 117.47 50 119.40 55 121.32 60 123.24 65 125.16 70 127.07 75 128.98 80 130.89 85 132.80 90 134.70 95 136.60 100 138.50 A2.1

TS-9100 7 Dimensions (in mm.) 52 52 38 47 5 Cablelength 2 m. 60 Ø6 Remote sensor TS-9101-810x 52 5 38 47 38 47 5 Outdoor sensor TS-910x-840x 52 5 38 47 Strap-on sensor TS-910x-860x 36 Cablelength 1,5 m. 60 Ø6 Cable sensor TE-910x-850x Ceiling sensor TS-910x-870x with brass well TS-9100-8905 with stainless steel well TS-9100-8915 Cable sensor TE-910x-850 2000 Johnson Controls, Inc. A2.1

TS-9100 8 Dimensions (in mm.) continued Gasket for direct duct mounting Gasket for direct duct mounting 200/300/500 160/200/300/500 Rod fast response sensor with flange Rod immersion with or without well Accessories Ø76 Ø64 22 Ø6 Ø6 120 30 50 G½" 120/150/200/260 G½" 50 R½" ISO 7/1 120/150/200/260 R½" ISO 7/1 Duct flange TS-9100-8950 Ø12 Stainless steel wells TS-9100-891x Ø12 Copper wells TS-9100-890x Duct flange and immersion wells 2000 Johnson Controls, Inc. A2.1

TS-9100 9 Notes: 2000 Johnson Controls, Inc. A2.1

TS-9100 10 S pecifications Sensing Element: 0...10V NTC K2 NTC K10 Pt 100 Supply Voltage: 15 VDC ± 10 % - Power Consumption: Output signal: 0.1 VA (5mA) no load Active 0...10V linear Resistive NTC K2 2 252 Ω = 25 C Resistive NTC K10 10 000 Ω = 25 C - Resistive Pt 100 100 Ω = 0 C Output load: max. 2mA - - - Temp. Ranges: see table on 0...40 C TC-8800: 0...50 C - page 2 and 3 SC-9100: 20...120 C Accuracy: ±1 % full scale Ambient Operating Conditions: Max. medium temperature: ± 0.2 K range 0 40 C ± 0.2 K range 0 120 C Maximum for electric connection box: 50 C for transducer (active) 70 C for sensors (resistive) 0 10V: max 130 C for range 20 120 C max 110 C for range 0 100 C max 160 C for range 0 150 C max 70 C for all other temperature ranges max 70 C NTC K2: NTC K10: max 120 C Pt100: max 150 C Storage Conditions: -40 to 70 C, 10 to 90 % RH non condensing Terminations: Screw terminals for 1 x 1,5 mm² / 14 AWG (maximum) cable Housing: Protection: IP54 Dimensions: Depending on model see dimension drawings on page 5 and 6 Materials: Rod/outdoor/strap-on/ceiling models: Housing: Polycarbonate Makrolon tube: copper Wells: copper or stainless steel AISI 304 Compliance: EMC (89/336 EEC) according to the standard EN 50081-1 and EN 50082-1 According to IEC 751, class A. The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Johnson Controls International, Inc. Headquarters: Milwaukee, WI, USA European Headquarters: Westendhof 8, 45143 Essen, Germany European Factories: Lomagna (Italy), Leeuwarden (The Netherlands), Essen (Germany) Branch Offices: principal European Cities This document is subject to change without notice Printed in Europe 2000 Johnson Controls, Inc. A2.1