Modeling and Evaluation of Geomagnetic Storms in the Electric Power System

Similar documents
GIC Analysis using PSS E. K.V. PATIL Siemens Power Technologies International Schenectady, New York, USA

GIC Calculations Using PSS E. Live Demonstration February 16, 2017

The Engineering Problem. Calculating GIC Flow through the EHV System

Power System Impacts of Geomagnetic Disturbances

Integration of Geomagnetic Disturbance Modeling into the Power Flow: A Methodology for Large-Scale System Studies

2013 Grid of the Future Symposium. Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765 kv Power Transformer Design

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

Case Study Effects of Geomagnetically Induced Current (GIC) Neutral Blocking Device

GMD Voltage Collapse Study

Geomagnetic Disturbances. IEEE PES Chicago Chapter Technical Presentation March 12, Alan Engelmann Transmission Planning ComEd.

Power Grid Sensitivity Analysis of Geomagnetically Induced Currents

High-Level Harmonic Distortion During Geomagnetic Disturbances - a Hidden Threat to Grid Security

A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Transformer Thermal Impact Assessment White Paper Project (Geomagnetic Disturbance Mitigation)

TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Impact of Solar Storms on the Swiss Transmission Network

A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC

POWER TRANSFORMERS: Saturation Compensation Modeling, Simulation, and Experiments

Model, Monitor & Mitigate Geomagnetically Induced Currents

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Transformer Thermal Impact Assessment White Paper (Draft) Project (Geomagnetic Disturbance Mitigation)

Effects of GIC on Power Transformers and Power Systems

2012 Grid of the Future Symposium. Geomagnetic Disturbance Impacts and AEP GIC/Harmonics Monitoring System

Comparison of methods for modelling geomagnetically induced currents

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection

Geo-Magnetic Disturbance Analysis of HV and EHV Grids

Investigation of Geomagnetic Induced Current Effects on Power Transformer

TPL is a new Reliability Standard to specifically address the Stage 2 directives in Order No. 779.

Consolidated Edison s Experience with On-line Monitoring and Mitigation of Geomagnetic Disturbances

Determination of Smart Inverter Power Factor Control Settings for Distributed Energy Resources

Novel Simulation Method to Quantify Induced Voltage & Current between Parallel or Partially Parallel Proximity AC Transmission Circuits

Unofficial Comment Form Project Geomagnetic Disturbance Mitigation

Space Weather Impact on the Scandinavian Interconnected Power Transmission System

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

Facilitating Bulk Wind Power Integration Using LCC HVDC

Interfacing Power System Simulators with Geomagnetically Induced Currents (GIC) Simulation Programs. Luis Marti Hydro One, Canada

GIC Distribution. Carlos David Fernández Barroso. Division of Industrial Electrical Engineering and Automation Faculty of Engineering, Lund University

North Europe power transmission system vulnerability during extreme space weather

Grounding Resistance

Vulnerability Assessment and Planning

Impact of transformer saturation from GIC on power system voltage regulation

Evaluating Transformer Heating due to Geomagnetic Disturbances

ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT

Hydro One GMD Preparedness Plan for Cycle 24

DISTURBANCES IN THE SOUTHERN AFRICAN POWER NETWORK DUE TO GEOMAGNETICALLY INDUCED CURRENTS

DIRECT CURRENT COMPENSATION FIELD EXPERIENCE UNDER SERVICE CONDITIONS

Transformer Technology Seminar GIC Capability of Power Transformers

Online Wide-Area Voltage Stability Monitoring and Control: RT-VSMAC Tool

See Benchmark Geomagnetic Disturbance Event Description white paper, May 12, Filed by NERC in Docket No. RM15 11 on June 28, 2016.

Operational Experiences of an HV Transformer Neutral Blocking Device

Keywords: Transformer modeling, saturation, hysteresis, MATLAB. Introduction

Making VSC-HVDC Control Robust to Geomagnetically Induced Current

IEEE PES/IAS Joint Chapter July Technical Presentation Meeting Basics of solar phenomena & How transformers react and handle events

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

EH2741 Communication and Control in Electric Power Systems Lecture 2

GIC Neutral Blocking System Prototype to Production

Study of Power Transformer Abnormalities and IT Applications in Power Systems

Geomagnetic Disturbances: Impact on Power System Components

AEP s 765kV Transmission Line Model Validation for Short Circuit and System Studies. T. YANG, Q. QIU, Z. CAMPBELL American Electric Power USA

Application Guide. Computing Geomagnetically-Induced Current in the Bulk-Power System. December 2013

PredictiveGrid. GMD/GIC detection explorations via PMU s

Grid Impact of Neutral Blocking for GIC Protection:

How OSHA s New Transient Overvoltage Requirements Affect Work Practices. B.A. YEUNG, H. BRANCO Leidos Engineering, LLC USA

TPL Project Geomagnetic Disturbance Mitigation. Technical Conference May 20, 2014

Geomagnetic Disturbance Planning Guide

concerning the risks to the electric power grid from geomagnetic storms,

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/

Comprehensive Study on Magnetization Current Harmonics of Power Transformers due to GICs

Solar Storm Probabilities Grid Contingencies Harmonic Relay Settings

ESB National Grid Transmission Planning Criteria

GMD Impacts on Generators

See Benchmark Geomagnetic Disturbance Event Description white paper, May 12, Filed by NERC in RM15-11 on June 28,

ROSE - Real Time Analysis Tool for Enhanced Situational Awareness

Magnetohydrodynamic Electromagnetic Pulse Assessment of the Continental U.S. Electric Grid

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1

Low-Frequency Protection Concepts for the Electric Power Grid: Geomagnetically Induced Current (GIC) and E3 HEMP Mitigation

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

PowerWorld Simulator GIC

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1

The Use of Intensity Modulated Optical Sensing Technology to Identify and Measure Impacts of GIC on the Power System

Placement of Multiple Svc on Nigerian Grid System for Steady State Operational Enhancement

University of Cape Town

Inversion of Geomagnetic Fields to derive ionospheric currents that drive Geomagnetically Induced Currents.

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

Increased Reliability of EHV Systems through Station Switchable Spare Transformer and Shunt Reactor Design and Operation

Comparative Study of Various Filtering Techniques to Reduce Harmonics in HVDC Converter Transfomer Due to GIC

Effect of Topology Control on System Reliability: TVA Test Case

1.1 Summary of previous studies in Finland

Comparison Analysis of the Effects of Small Resistor and Capacitor on Mitigation GIC in Power Grid

Industry Webinar. Reactive Power Planning. NERC System Analysis and Modeling Subcommittee (SAMS) March 2017

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1

Study on New Type Magnetic Saturation Transformer Based on PDF Theory

Endorsed Assignments from ERS Framework

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

100-year GIC event scenarios. Antti Pulkkinen and Chigomezyo Ngwira The Catholic University of America & NASA Goddard Space Flight Center

System Operating Limit Definition and Exceedance Clarification

Long lasting transients in power filter circuits

Transcription:

21, rue d Artois, F-75008 PARIS C4-306 CIGRE 2014 http : //www.cigre.org Modeling and Evaluation of Geomagnetic Storms in the Electric Power System K. PATIL Siemens Power Technologies International, Siemens Industry, Inc. Schenectady, New York, USA SUMMARY A solar magnetic disturbance in the direction of earth can produce severe fluctuations in the earth s magnetic field. Such geomagnetic storms or geomagnetic disturbances (GMD) induce potential gradients on the surface of the earth causing the earth surface potential (ESP) to rise. ESP rise in the range of 1 to 10 V/km can occur during severe geomagnetic disturbances in certain regions where the earth conductivity is low [1]. These induced voltages can cause induced currents (called geomagnetically induced currents or GICs) to flow on the surface of the earth. GICs induced on the earth s surface can flow into the electric power system if there is a closed path for the current to flow between the electric network and the earth. This path is typically provided by grounding connections of substation transformers and shunts. GICs are often described as being quasi-direct current (DC), although the frequency variation of GICs is governed by the time variation of the induced electric field [2]. The GIC is a low frequency current. Any GIC flow through transformers can cause half-cycle saturation. This can result in highly distorted excitation currents rich in harmonics and consequent increases in reactive power consumption [3-6]. The increased reactive power consumption could cause unacceptable system wide voltage depressions leading to possible voltage collapse and/or erroneous operation of protective relays and consequent system stability issues. The GMD events thus have the ability to disrupt normal operation of the power grid and hence there is a need to model and study the effects of GMD and the consequent GIC on the reliability and secure delivery of electric power. This paper describes the modeling methodologies for studying the effects of GIC on the electric power network for various system planning studies such as power flow, contingency, and voltage stability (QV) analysis. KEYWORDS Geomagnetic Disturbance Geomagnetically Induced Currents Transformer Half Cycle Saturation Power System Modeling Power System Analysis krishnat.patil@siemens.com

1 POWER SYSTEM MODELING FOR GIC ANALYSIS GICs are low frequency currents that flow into the electric power system if there is a closed path for the current to flow between the electric network and the earth. This path is typically provided by grounding connections of substation transformers and shunts. For the purpose of GIC analysis the ac power system is reduced to a dc resistive network with the following network assumptions [1]: Transmission lines are modeled with their dc resistance in series with induced dc voltage [7]. Transmission line reactors and charging are ignored. Series compensated transmission lines block GIC flow and hence are ignored. The windings of two and three winding transformers that have ground paths are modeled with their dc resistance to ground. The series winding and common winding (if grounded) of auto transformers are modeled. Bus shunts (if grounded) are modeled with their dc resistance to ground. Equivalent station grounding resistance is considered. A dc network representation of a typical ac power system used in GIC calculations is shown in Figure 1. It is assumed that transmission line Rline4 is terminated into substations Sub2 and Sub4 transformers whose winding 2 is grounded. There are grounded bus shunts in substations Sub2, Sub3 and Sub4. Notations: GIC induced voltages on a transmission lines: V1, V2, V3 and V4 Transmission Line dc resistances: Rline1, Rline2, Rline3, Rline4 Transformer Winding dc resistances: Rtrn1-w2, Rtrn2-w2 Shunt dc resistances: Rsh1, Rsh2, Rsh3 Substation ground dc resistances: Rgrd1, Rgrd2, Rgrd3, Rgrd4 Substations: Sub1, Sub2, Sub3, Sub4 Figure 1: DC representation of AC Power System used in GIC Calculations The induced dc voltages (V1, V2, V3 and V4) in transmission lines are calculated [3] as in equation (1). + (1) where E N and L N are the Northward electric field and Northward distance, while, E E and L E are the Eastward electric field and Eastward distance. Typical power flow programs require ac network data. However, for GIC calculations, dc resistance data of transmission lines, transformer windings, bus shunts, and effective substation ground are required. Additionally, the configuration (vector group) of transformer windings and bus shunts is required to determine their ground connection. In order to calculate the induced dc voltage in transmission lines using equation (1), the geographical location (latitude and longitude) of transmission lines is also required. A power system dc network as shown in Figure 1 is converted into its Norton equivalent and solved to determine the GICs flowing in the network. 1

1.1 Effective GIC in a Transformer The effective GIC (I eff ) flow in a transformer due to GICs flowing in one or more of its winding is dependent upon transformer type. Figure 2 illustrates the GIC flows in transformer windings for various transformer configurations. Figure 2: Effective GIC Calculation for Various Transformers (a) Two Winding (b) Two Winding Auto (c) Three Winding (d) Three Winding Auto Assuming I eff is represented on the winding 1 side of a transformer, this can be derived for various transformer types as below. + + ( + ) + + (2) ( 1) + (2) (a) Two Winding Transformers + + + + (2) (c) Three Winding Transformers (b) Two Winding Auto Transformers + ( + ) + ( 1) + + + + (2) (d) Three Winding Auto Transformers In the above, the ampere per phase GIC flow in various windings is identified as: I 1 Winding 1, I 2 Winding 2, I 3 Winding 3, I C Auto Transformer Common Winding, and I S Auto Transformer Series Winding. 2

1.2 Transformer Reactive Power Losses due to GIC Flow One of the effects of the GICs flowing in transformer windings is that the transformer is subjected to half-cycle saturation resulting in increased reactive power (Mvar) losses in these equipments [1]. Using the effective GICs flowing in transformers, the reactive power losses are calculated as [6]:!"# (3) where K factor is Mvar/ampere scaling factor. This scaling factor could be a generic value based on the transformer type, or could be a specific value obtained for the specific transformer. The GIC analysis results presented in the next section use a generic K factor provided in [6]. A different approach for calculating transformer reactive power consumption due to GICs flow is described in [8]. 2 POWER SYSTEM GIC ANALYSIS To study the effects of GMD on power system performance and operation, the transformer reactive power losses due to GIC flow are added to the base power system network as constant reactive current loads. A sample network comprising 42 buses, 23 transformers, 56 branches, and 20 substations is considered for the analysis presented here. For this sample network, the power flow analysis, contingency analysis and QV analysis are discussed, accounting for the effects of GMD. For the purpose of this analysis, the dc resistance values are calculated from ac resistance values and the geographical locations of the substations are assumed. 2.1 Power Flow Analysis For the sample system, the power flow is solved without GMD effects. Figure 3 shows power flow solution minimum voltage of buses terminated in that substation for the base case network. The transmission line colors indicate voltage levels. The bus voltage colors indicate bus voltage range; with green indicating 0.95<pu<1.05. Substations are indicated by numbers, and are located on the map by longitude and latitude. The size of the circle at the substation indicates the deviation of bus voltage from 1 pu. As seen in the network map, all bus voltages are within normal operating limits. Figure 3: Network Bus Voltages without GMD 3

Considering a GMD of uniform field strength of 1 V/km, transformer reactive power losses are calculated using varying disturbance directions of 0 through 360 degrees. Figure 4 shows those reactive power losses. The disturbance direction of 96 degrees results in the maximum reactive power loss of 204.83 Mvar. Figure 4: Transformer Reactive Power Losses for GMD of 1 V/km and direction 0-360 degrees Next, with GMD direction set to 96 degrees, power flows are solved with varying uniform field strength. The goal at this point is to find the maximum possible disturbance strength for which a converged power flow solution can be found. For the sample network, the maximum disturbance strength with a converged power flow solution is 7 V/km. Figure 5 shows the network bus voltages for a GMD of 7 V/km at 96 degrees. As expected, and as can be seen in Figure 5, the bus voltages are much lower as compared to voltages in Figure 3. The size of the circles easily illustrates the locations of the network with significant voltage dip problems. This analysis demonstrates that the network would need additional capacitive reactive power support for normal operation. Figure 5: Network Bus Voltages with GMD of 7 V/km at 96 degrees 4

Figure 6 and Figure 7 show GICs flowing in substation ground and transmission lines for a GMD of 7 V/km at 96 degrees. Figure 6 shows substations that have considerable GIC flow and where GIC mitigation measures may be needed. Figure 6: GICs Flowing in Substation Ground with GMD of 7 V/km at 96 degrees Figure 7: GICs Flowing in Transmission Lines with GMD of 7 V/km at 96 degrees 2.2 Contingency Analysis The contingency events comprising single or parallel transmission line outages are simulated. The GIC flows and transformer reactive power are calculated by varying both disturbance direction and disturbance strength for each contingency. As shown in Figure 8, first, disturbance directions are varied to determine the disturbance directions that result in the largest transformer reactive power losses for each contingency. Using those disturbance directions and as shown in Figure 9, the maximum possible disturbance strength for which a converged power flow solution is found for each contingency is determined. As can be seen from Figure 4, Figure 8, and Figure 9, disturbance strength and direction affect the network differently. Figure 8: Contingency Analysis for Varying GMD Directions (Electric Field1 V/km) 5

2.3 QV Analysis Figure 9: Contingency Analysis for Varying GMD Electric Fields Figure 10 shows QV analysis at one of the network buses in substation 1 where the voltage dip is largest. As expected the additional reactive power support needed increases as GMD strength increases. Figure 10: QV Analysis 6

3 CONCLUSION This paper outlines the power system modeling requirements for evaluating the effects of GIC on electric power systems. The paper illustrates the techniques for conducting power system planning studies such as power flow, contingency, and QV analysis considering various GMD scenarios. By varying the GMD directions that give maximum transformer reactive power losses, and ascertaining the GMD strength tolerated before voltage collapse, the GMD limits for any network can be determined. BIBLIOGRAPHY [1] IEEE Transmission and Distribution Committee Working Group on Geomagnetic Disturbances and Power System Effects Report, Geomagnetic Disturbances Effects on Power Systems, IEEE Transactions on Power Delivery, Vol. 8, No. 3, July 1993, pages 1206-1216. [2] R. Pirjola, Properties of matrices included in the calculation of GICs in power systems and introduction of a test model for GIC computation algorithms, Earth, Planets and Space, Vol. 61, 2009, pages 263-272. [3] R. Horton, D. Boteler, T.J. Overbye, R. Pirjola, and R.C. Dugan, A Test Case for the Calculation of Geomagnetically Induced Currents, IEEE Transactions on Power Delivery, Vol. 27, No. 4, October 2012, pages 2368-2373. [4] North American Electric Reliability Corporation (NERC), 2012 Special Reliability Assessment Interim Report, Effects of Geomagnetic Disturbances on the Bulk Power System. [5] V. D. Albertson, J. G. Kappenman, N. Mohan, G. A. Skarbakka, "Load-flow Studies in the Presence of Geomagnetically-induced Currents", IEEE Transactions on Power Apparatus and Systems, Vol. PAS-100, No. 2, February 1981, pages 594-607. [6] X. Dong, Y. Liu, J. G. Kappenman, Comparative Analysis of Exciting Current Harmonics and Reactive Power Consumption from GIC Saturated Transformers, Proceedings IEEE, 2001, pages 318-322. [7] D. H. Boteler and R. J. Pirjola, "Modeling Geomagnetically Induced Currents produced by Realistic and Uniform Electric Fields", IEEE Transactions on Power Delivery, Vol. 13, No. 4, October 1998, pages 1303-1308. [8] R.A. Walling and A.H. Khan, Characteristics of Transformer Exciting-Current during Geomagnetic Disturbances, IEEE Transactions on Power Delivery, Vol. 6, No. 4, October 1991, pages 1707-1714. 7