Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL

Similar documents
Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL

Design Guide of the Medium Voltage Transformers for KACO Central Inverter

Technical Information Installation Requirements for TRANSFORMER COMPACT STATION 500SC-JP/630SC-JP/800SC-JP

Installation at high altitudes

Technical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US

SINVERT. Technical requirements for medium-voltage transformers for use with SINVERT central inverters. Application manual 04/2012

3-Phase Transformers. Author: Sergey Dubatov. belfuse.com/signal

Installation requirements

Technical information SUNNY BOY 3.0-US / 3.8-US / 5.0-US / 6.0-US / 7.0-US / 7.7-US

POWER TRANSFORMERS CATALOGUE

Technical information SUNNY TRIPOWER CORE1-US

TECHNICAL INFORMATION

Technical Information Short-Circuit Currents Information on short-circuit currents of SMA PV inverters

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

12 Transformers and other Equipment for Switchgear Installations

5 Summary LOW VOLTAGE RIDE THROUGH WITH HIGH CURRENT INJECTION. Motivation. Future Requirements. Test results for symmetrical failures

BAT-Series Grid Inverter. Battery Charger.

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Technical Information PV Inverters

, ,54 A

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

Component Requirement Specification for SGI 500XT Isolation Transformer

GREEN TRAFO PRODUCTS SHR - THREE-PHASE SHUNT REACTOR

ESB National Grid Transmission Planning Criteria

SPECIFICATION Item no.: T60404-N4646-X764

Status Date Prepared Reviewed Endorsed Approved

Application Note. Applicable Product: AC Drives

Transformer Protection Principles

RAP Ripple Control Coupling for parallel injection of RC signals in Medium and High Voltage Networks

High Performance Current Transducer ITL 900-T = A

Regional Technical Seminar SHORT CIRCUIT FORCES

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

Switching power supplies CP range, Linear power supplies CP-L range. Content

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit.

ISSN: [IDSTM-18] Impact Factor: 5.164

ISOLATING TRANSFORMERS FOR TLC PLANTS

16B2011B1 EASY HARMONICS USER MANUAL

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

On-load tap-changer VACUTAP VRC and VRE

The relative simplicity of transformers belies their. Transformer Fundamentals

English 8 P EN.01/01.

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

On-load tap-changer VACUTAP VRD, VRF, VRG

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

Power Transformer Ratings' Calculation and Analysis - IEEE C

SPECIFICATION Item No.: T60404-P4640-X100

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

POWER TRANSDUCERS ACTIVE AND REACTIVE SERIES: T-W WATT T-V VAR

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

Basic principles and operation of a transformer

VI 3 - i TABLE OF CONTENTS

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

CONTENTS. 1. Introduction Generating Stations 9 40

5 Summary test results and additional findings

Electrical Description

SPECIFICATION Item no.: T60404-N4646-X762

Tripping of circuit breakers in PV installations due to zero sequence field impedance

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

SECTION TRANSFORMERS

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

R Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Overcurrent and Overload Protection of AC Machines and Power Transformers

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

ON-SITE TESTING OF SPECIAL TRANSFORMERS

SPECIFICATION Item no.: T60404-N4646-X975

SPECIFICATION Item no.: T60404-N4646-X663

CP CU1. Coupling unit for line and ground testing

V P N. Voltage transducer DVM 2000-B = 2000 V

Technical manual. Microstep driver SMC11. NANOTEC ELECTRONIC GmbH & Co. KG Gewerbestraße 11 D Landsham near Munich, Germany

HVDC High Voltage Direct Current

SPECIFICATION Item no.: T60404-N4646-X662

24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

ULTRA-K Series 600K - he

AUTOMOTIVE CURRENT TRANSDUCER OPEN LOOP TECHNOLOGY HAH3DR 800-S0C

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Regional Technical Seminar TAP CHANGERS

Introduction. Centrado leading-edge transformer. Introduction

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

SKS B2 120 GDD 69/11 - A11 MA PB

K Factor Power Transformers

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Embedded Generation Connection Application Form

Controlling the Power Flow!

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Distribution System Development & Preliminary Studies

Transcription:

Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL ENGLISH SC_Trafo-TI-en-65 Version 6.5

Table of Contents SMA Solar Technology AG Table of Contents 1 Information on this Document... 3 1.1 Validity... 3 1.2 Limited statutory warranty... 3 1.3 Nomenclature... 3 2 Technical requirements for the MV transformer... 4 2.1 General Requirements... 4 2.2 Requirements for two-winding transformers used to connect one inverter... 5 2.3 Requirements for three-winding transformers used to connect two inverters... 5 2.4 Requirements for four-winding transformers used to connect two inverters... 8 2.5 Requirements for multi-winding transformers used to connect three inverters... 10 2.6 Requirements for multi-winding transformers used to connect four inverters... 11 3 Technical requirements for the transformer for internal power supply... 12 3.1 General Requirements... 12 3.2 Requirements for the connection to the park-side utility grid... 12 3.3 Requirements for the connection to the AC output of the inverter... 13 4 Appendix... 14 4.1 Technical data of the inverter... 14 4.2 Technical data of the transformers... 15 2 SC_Trafo-TI-en-65 Technical Information

SMA Solar Technology AG 1 Information on this Document 1 Information on this Document 1.1 Validity This document applied to all device types of the Sunny Central inverter. It describes the requirements for MV transformers and transformers for internal power supply that are connected to Sunny Central inverters and provided by the customer. Please note that not all Sunny Central inverters can be combined with all MV transformers. For more details, please refer to the following pages. 1.2 Limited statutory warranty SMA Solar Technology AG only provides statutory warranty for products purchased from SMA Solar Technology AG. SMA Solar Technology AG America LLC only provides statutory warranty for products purchased from SMA Solar Technology AG America LLC. The statutory warranty for the inverters and other products purchased from SMA does not apply if the requirements described in this document are not met. 1.3 Nomenclature Complete designation SMA Solar Technology America LLC SMA Solar Technology AG Sunny Central Sunny Central Storage Medium-voltage transformer Designation in this document SMA SMA MV transformer Technical Information SC_Trafo-TI-en-65 3

2 Technical requirements for the MV transformer SMA Solar Technology AG 2 Technical requirements for the MV transformer 2.1 General Requirements The MV transformer can be of the liquid-immersed transformer type (for example, with mineral oil or organic oil) or of the dry-type transformer. The MV transformer must be designed at its low-voltage windings for voltages that arise during pulsed mode of the inverter. The power connection used must have suitable insulation resistance since voltages to ground of ±2400 V at the most occur when the inverter is in pulsed mode (see Section 4.1 "Technical data of the inverter", page 14). Figure 1: AC voltage level for SC 2500-EV The low voltage windings of the MV transformer must be designed for voltages that are capable of a rate of rise in voltage dv/dt of up to 500 V/µs to ground. The line-to-line voltages are sinusoidal. A shield winding grounded on the tank must be provided between the low voltage windings and the high voltage windings. This serves as an additional dv/dt filter. Each inverter requires a separate, galvanically insulated low-voltage winding. Therefore, the parallel operation of several inverters on one low-voltage winding is not permissible. The voltages at the low-voltage windings of the MV transformer must match the AC output voltage of the inverter (see Section 4.1 "Technical data of the inverter", page 14). The voltage level on the high-voltage side of the MV transformer must be selected according to the gridconnection point. The MV transformer must be connected to the medium-voltage grid or the high-voltage grid. Connection to the low-voltage grid is not permissible. When connecting to the medium-voltage grid, the use of a MV transformer with tap changer on the high voltage side is recommended. MV transformer with tap changer on the high-voltage side enables an adaptation to the voltage level of the medium-voltage grid. The MV transformer must be rated according to the temperature-dependent power behavior of the inverter. For thermal design, the load curve of the MV transformer and the ambient conditions at the respective mounting location must be taken into account. When operating with an additional reactive power supply, the increased loads in the design of the MV transformer are to be observed (for information about the reactive power supply of the inverter, see the inverter documentation). When designing the MV transformer for use with the Sunny Central Storage, it is important to remember that due to battery operation the MV transformer hardly cools down at all at night. 4 SC_Trafo-TI-en-65 Technical Information

SMA Solar Technology AG 2 Technical requirements for the MV transformer The MV transformer must be designed for the AC output currents of the inverter (see Section 4.1 "Technical data of the inverter", page 14). If grounding of the MV transformer on the medium voltage side is required, the type of grounding regarding the entire system including the MV transformer must be taken into consideration. The consequences of any error, such as a short circuit, ground fault or voltage failure, must be taken into account when considering the overall system. The country-specific power frequency must be taken into account. The applicable country-specific standards and directives must be taken into account. SMA reserves the right to measure the currents of the sine-wave filter capacitors during commissioning and, if necessary, to optimize the entire system. 2.2 Requirements for two-winding transformers used to connect one inverter The following vector groups are recommended for handling the corresponding neutral points. Insulated neutral point on medium-voltage side Dy11, Dy5, Dy1, Dd0, Dd6 Yd11, Yd5, Yd1 Resonant grounding on mediumvoltage side YNy0 YNd11, YNd5, YNd1 Low-resistance grounded neutral point YNy0 If there is a neutral-point terminal on the low-voltage side, this neutral-point terminal must not be grounded or connected. Figure 2: Circuit diagram of two-winding transformers (example) The relative impedance voltage V k of the MV transformer between grid-connection point and AC output of the inverter must be between the minimum value V k min and the maximum value V k max. The nominal power of the MV transformer (see Section 4.2 "Technical data of the transformers", page 15) is the basis of the relative impedance voltage. 2.3 Requirements for three-winding transformers used to connect two inverters A three-winding transformer (low-high-low) consists of one high-voltage winding and two low-voltage windings. Technical Information SC_Trafo-TI-en-65 5

2 Technical requirements for the MV transformer SMA Solar Technology AG Only three-winding transformers with LHL windings are permitted. In such MV transformers, the high-voltage winding is located between two low-voltage windings. Figure 3: Design of a three-winding transformer Position A Designation Core B Low-voltage winding 1 C High-voltage winding D Low-voltage winding 2 E Shield winding Three-winding transformers may only be used with the following inverters starting from the specified production version. The production version can be found on the type label of the inverter. Sunny Central CP-US Sunny Central CP XT Starting from production version B9 A4 Three-winding transformers with varying vector groups can be used. The following vector groups are recommended for handling the corresponding neutral points. Insulated neutral point on medium-voltage side Dy11y11, Dy5y5, Dy1y1, Dd0d0, Dd6d6 Yd11d11, Yd5d5, Yd1d1 Resonant grounding on mediumvoltage side YNy0y0 YNd11d11, YNd5d5, YNd1d1 Low-resistance grounded neutral point YNy0y0 6 SC_Trafo-TI-en-65 Technical Information

SMA Solar Technology AG 2 Technical requirements for the MV transformer If there is a neutral-point terminal on the low-voltage side, this neutral-point terminal must not be grounded or connected. Figure 4: Circuit diagram of three-winding transformers (example) Three-winding transformers must be designed for an asymmetrical load flow in the low-voltage systems. This means that to ensure permanent operation, the transformer must be designed for feed-in with one inverter. Three-winding transformers must be designed for the use of inverters of the Sunny Central Storage series so that full power can be fed in at one of the low-voltage windings and that full power can be used at the other lowvoltage winding. The transformer must be designed for continuous operation in this operating state. The relative impedance voltage V k of the MV transformer between grid-connection point and AC output of the inverter must be between the minimum value V k min and the maximum value V k max. The relative impedance voltage is based on half the nominal power of the MV transformer (see Section 4.2 "Technical data of the transformers", page 15). The difference of the relative impedance voltages between the grid-connection point of the AC outputs of the two inverters must not exceed 0.5% (see Section 4.2 "Technical data of the transformers", page 15). Example: Permissible Difference of Impedance Voltages V k dif max The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 1 is 6.0%. The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 2 is 5.6%. The deviation of the relative impedance voltages is permissible since the difference amounts to 0.4% and is thus smaller than 0.5%. Example: Non-Permissible Difference of Impedance Voltages V k dif max The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 1 is 6.0%. The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 2 is 5.4%. The deviation of the relative impedance voltages is not permissible since the difference amounts to 0.6% and is thus greater than 0.5%. Technical Information SC_Trafo-TI-en-65 7

2 Technical requirements for the MV transformer SMA Solar Technology AG The value of the relative impedance voltage V k 1-2 between the two low-voltage winding must be at least 9%. The impedance voltage is based on half the nominal power of the MV transformer. This value can be determined by shorting a low-voltage winding and increasing the voltage on the other low-voltage winding until the nominal current of a low-voltage system flows. During this time, the high-voltage windings are in no-load operation. Figure 5: Circuit diagram for determining the impedance voltage V k 1-2 in three-winding transformers (example) 2.4 Requirements for four-winding transformers used to connect two inverters A four-winding transformer (double story transformer) consists of two high-voltage windings and two low-voltage windings. For four-winding transformers, a separate shield winding, grounded on the tank, is to be provided between each low-voltage winding and high-voltage winding. A B C D G E F Figure 6: Four-winding transformers with separate shield windings Position A Designation Core B Low-voltage winding 1 C High-voltage winding 1 8 SC_Trafo-TI-en-65 Technical Information

SMA Solar Technology AG 2 Technical requirements for the MV transformer Position Designation D Shield winding 1 E Low-voltage winding 2 F High-voltage winding 2 G Shield winding 2 Four-winding transformers may only be used with the following inverters starting from the specified production version. The production version can be found on the type label of the inverter. Sunny Central 1000 kva Sunny Central > 1000 kva Starting from production version A4 A7 Four-winding transformers with varying vector groups can be used. The following vector groups are recommended for handling the corresponding neutral points. Insulated neutral point on medium-voltage side Dy11y11, Dy5y5, Dy1y1, Dd0d0, Dd6d6 Yd11d11, Yd5d5, Yd1d1 Resonant grounding on mediumvoltage side YNy0y0 YNd11d11, YNd5d5, YNd1d1 Low-resistance grounded neutral point YNy0y0 If there is a neutral-point terminal on the low-voltage side, this neutral-point terminal must not be grounded or connected. Figure 7: Circuit diagram of four-winding transformers (example) Technical Information SC_Trafo-TI-en-65 9

2 Technical requirements for the MV transformer SMA Solar Technology AG Four-winding transformers must be designed for an asymmetrical load flow in the low-voltage systems. This means that for long-term operation, the transformer must be designed for the feed-in of one inverter only. Four-winding transformers must be designed for the use of inverters of the Sunny Central Storage series so that full power can be fed in at one of the low-voltage windings and that full power can be used at the other low-voltage winding. The transformer must be designed for continuous operation in this operating state. The relative impedance voltage V k of the MV transformer between grid-connection point and AC output of the inverter must be between the minimum value V k min and the maximum value V k max. The relative impedance voltage is based on half the nominal power of the MV transformer (see Section 4.2 "Technical data of the transformers", page 15). The difference of the relative impedance voltages between the grid-connection point of the AC outputs of the two inverters must not exceed 0.5% (see Section 4.2 "Technical data of the transformers", page 15). Example: Permissible Difference of Impedance Voltages V k dif max The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 1 is 6.0%. The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 2 is 5.6%. The deviation of the relative impedance voltages is permissible since the difference amounts to 0.4% and is thus smaller than 0.5%. Example: Non-Permissible Difference of Impedance Voltages V k dif max The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 1 is 6.0%. The value of the relative impedance voltage from the high-voltage winding to low-voltage winding 2 is 5.4%. The deviation of the relative impedance voltages is not permissible since the difference amounts to 0.6% and is thus greater than 0.5%. The value of the relative impedance voltage V k 1-2 between the two low-voltage winding must be at least 9%. The impedance voltage is based on half the nominal power of the MV transformer. This value can be determined by shorting a low-voltage winding and increasing the voltage on the other low-voltage winding until the nominal current of a low-voltage system flows. During this time, the high-voltage windings are in no-load operation. Figure 8: Circuit diagram for determining the impedance voltage U k 1-2 in four-winding transformers (example) 2.5 Requirements for multi-winding transformers used to connect three inverters The requirements for MV transformers to which three inverters are to be connected are the same as for two-winding transformers. Three two-winding active parts are mounted in a tank. All three active parts must be set up with separated cores. 10 SC_Trafo-TI-en-65 Technical Information

SMA Solar Technology AG 2 Technical requirements for the MV transformer 2.6 Requirements for multi-winding transformers used to connect four inverters The requirements for MV transformers to which four inverters are to be connected are the same as for four-winding transformers. Two four-winding active parts of double story design are mounted in a tank. Both active parts must be set up with separated cores. Technical Information SC_Trafo-TI-en-65 11

3 Technical requirements for the transformer for internal power supply SMA Solar Technology AG 3 Technical requirements for the transformer for internal power supply 3.1 General Requirements The inverters up to 1000 kva require an external AC voltage supply. The voltage for the inverters can be supplied by a transformer for internal power supply. The inverters from 2200 kva have an integrated transformer for internal power supply with a power of 8.4 kva and are not dealt with here. The transformer for internal power supply must be of three-phase design. The secondary side of the transformer for internal power supply must supply a voltage of 230 V/400 V (3/N/PE) to connect to the inverter. The transformer for internal power supply must provide a power of at least 2.8 kva per inverter. Several inverters can be supplied by one transformer for internal power supply if this transformer can provide a power of at least 2.8 kv per inverter. The transformer for internal power supply must be designed for an asymmetric load of 80%. A transformer for internal power supply with the Dyn5 or Dyn11 vector group is recommended. A shield winding that has to be grounded at the enclosure must be provided between the windings of the transformer for internal power supply. The transformer for internal power supply must be equipped with an external protection against overload. The transformer for internal power supply must have external short-circuit protection ensuring that any potential short-circuit currents are limited to 6 ka at the inverter. To protect the inverter, overvoltage protection must be provided between the inverter and the transformer for internal power supply. The ambient conditions of the transformer for internal power supply must be taken into account. The country-specific power frequencies must be taken into account. The applicable country-specific standards and directives must be taken into account. 3.2 Requirements for the connection to the park-side utility grid Figure 9: Connection of the transformer for internal power supply to the park-side utility grid 12 SC_Trafo-TI-en-65 Technical Information

SMA Solar Technology AG 3 Technical requirements for the transformer for internal power supply For the connection to the park-side utility grid, the primary voltage of the transformer for internal power supply must be equal to the grid voltage. 3.3 Requirements for the connection to the AC output of the inverter Figure 10: Connection of the transformer for internal power supply to the inverter's AC output The primary voltages of the transformer for internal power supply must correspond to the AC output voltages of the inverter (see Section 4.1 "Technical data of the inverter", page 14). On the primary side, the transformer for internal power supply must be suitable for the pulsed mode of an inverter. On the primary side, the transformer for internal power supply must be suitable for voltages that arise from pulsed mode of the inverter. The power connection used must have suitable insulation resistance since voltages to ground of ±2,400 V at the most occur when the inverter is in pulsed mode (see Section 4.1 "Technical data of the inverter", page 14). On the primary side, the transformer for internal power supply must be designed for voltages reaching a rate of rise in voltage dv/dt of up to 500 V/µs to ground. The line-to-line voltages are sinusoidal. The windings of the transformer for internal power supply must be galvanically insulated. Do not use autotransformers. Technical Information SC_Trafo-TI-en-65 13

4 Appendix SMA Solar Technology AG 4 Appendix 4.1 Technical data of the inverter Sunny Central type DC voltage AC voltage AC peak voltage to ground AC current at 25 C at 40 C at 50 C SC 500CP XT 1000 V 270 V ±1450 V 1176 A 1113 A 1070 A SC 630CP XT 1000 V 315 V ±1450 V 1283 A 1202 A 1155 A SC 720CP XT 1000 V 324 V ±1450 V 1411 A 1335 A 1283 A SC 760CP XT 1000 V 342 V ±1450 V 1411 A 1335 A 1283 A SC 800CP XT 1000 V 360 V ±1450 V 1411 A 1335 A 1283 A SC 850CP XT 1000 V 386 V ±1600 V 1411 A 1335 A 1283 A SC 900CP XT 1000 V 405 V ±1600 V 1411 A 1335 A 1283 A SC 1000CP XT 1000 V 405 V ±1600 V 1586 A 1426 A 1283 A SC 2200 1100 V 385 V ±1800 V 3300 A 3120 A 3000 A SC 2500-EV 1500 V 550 V ±2400 V 2624 A 2467 A 2362 A SC 2750-EV 1500 V 600 V ±2400 V 2646 A 2502 A 2406 A Sunny Central US type DC voltage AC voltage AC peak voltage to ground AC current at 25 C at 40 C at 50 C SC 500CP-US 600 V 200 V ±800 V 1588 A 1502 A 1444 A SC 500CP-US 1000 V 270 V ±1450 V 1176 A 1113 A 1070 A SC 630CP-US 1000 V 315 V ±1450 V 1283 A 1202 A 1155 A SC 720CP-US 1000 V 324 V ±1450 V 1411 A 1335 A 1283 A SC 750CP-US 1000 V 342 V ±1450 V 1411 A 1335 A 1283 A SC 800CP-US 1000 V 360 V ±1450 V 1411 A 1335 A 1283 A SC 850CP-US 1000 V 386 V ±1600 V 1411 A 1335 A 1283 A SC 900CP-US 1000 V 405 V ±1600 V 1411 A 1335 A 1283 A SC 1850-US 1000 V 385 V ±1700 V 2774 A 2774 A 2774 A SC 2200-US 1000 V 385 V ±1700 V 3300 A 3120 A 3000 A SC 2500-EV-US 1500 V 550 V ±2400 V 2624 A 2467 A 2362 A SC 2750-EV-US 1500 V 600 V ±2400 V 2646 A 2502 A 2406 A 14 SC_Trafo-TI-en-65 Technical Information

SMA Solar Technology AG 4 Appendix Sunny Central CP JP type DC voltage AC voltage AC peak voltage to ground AC current at 25 C at 40 C at 50 C SC 500CP-JP 600 V 205 V ±800 V 1411 A 1335 A 1283 A SC 630CP-JP 1000 V 315 V ±1450 V 1283 A 1202 A 1155 A SC 800CP-JP 1000 V 360 V ±1450 V 1411 A 1335 A 1283 A SC 1000CP-JP 1000 V 405 V ±1600 V 1586 A 1426 A 1283 A Sunny Central Storage type DC voltage AC voltage AC peak voltage to ground AC current at 25 C at 40 C at 50 C SCS 500 850 V 270 V ±1450 V 1411 A 1113 A 1070 A SCS 630 850 V 315 V ±1450 V 1411 A 1202 A 1155 A SCS 720 850 V 324 V ±1450 V 1411 A 1335 A 1283 A SCS 760 850 V 342 V ±1450 V 1411 A 1335 A 1283 A SCS 800 950 V 360 V ±1450 V 1411 A 1335 A 1283 A SCS 850 950 V 386 V ±1600 V 1411 A 1335 A 1283 A SCS 900 950 V 405 V ±1600 V 1411 A 1335 A 1283 A SCS 1000 900 V 405 V ±1600 V 1568 A 1426 A 1283 A SCS 2200 1100 V 385 V ±1800 V 3300 A 3120 A 3000 A SCS 2200-US 1100 V 385 V ±1800 V 3300 A 3120 A 3000 A SCS 2475 1100 V 434 V ±1800 V 3292 A 3113 A 2993 A SCS 2475-US 1100 V 434 V ±1800 V 3292 A 3113 A 2993 A SCS 2500-EV 1500 V 550 V ±2400 V 2624 A 2467 A 2362 A SCS 2500-EV-US 1500 V 550 V ±2400 V 2624 A 2467 A 2362 A SCS 2750-EV 1500 V 600 V ±2400 V 2646 A 2502 A 2406 A SCS 2750-EV-US 1500 V 600 V ±2400 V 2646 A 2502 A 2406 A 4.2 Technical data of the transformers s above 1000 kva are not approved for three-winding transformers. Technical Information SC_Trafo-TI-en-65 15

4 Appendix SMA Solar Technology AG Sunny Central Type of the Two-winding transformers Three-winding and four-winding transformers V k min V k nom V k max V k min V k nom V k max V k dif max V k 1-2 min SC 500CP XT 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SC 630CP XT 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SC 720CP XT 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SC 760CP XT 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SC 800CP XT 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SC 850CP XT 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SC 900CP XT 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SC 1000CP XT 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % Type of the Two-winding transformers Four-winding transformers V k min V k nom V k max V k min V k nom V k max V k dif max V k 1-2 min SC 2200 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % SC 2500-EV 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % SC 2750-EV 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % Sunny Central US Type of the Two-winding transformers Three-winding and four-winding transformers V k min V k nom V k max V k min V k nom V k max V k dif max V k 1-2 min SC 500CP-US* 5.4 % 6.0 % 6.6 % 5.4 % 6.0 % 6.6 % 0.5 % 9.0 % SC 500CP-US** 5.4 % 6.0 % 6.6 % 5.4 % 6.0 % 6.6 % 0.5 % 9.0 % SC 630CP-US 5.4 % 6.0 % 6.6 % 5.4 % 6.0 % 6.6 % 0.5 % 9.0 % SC 720CP-US 5.4 % 6.0 % 6.6 % 5.4 % 6.0 % 6.6 % 0.5 % 9.0 % SC 750CP-US 5.4 % 6.0 % 6.6 % 5.4 % 6.0 % 6.6 % 0.5 % 9.0 % SC 800CP-US 5.4 % 6.0 % 6.6 % 5.4 % 6.0 % 6.6 % 0.5 % 9.0 % SC 850CP-US 5.4 % 6.0 % 6.6 % 5.4 % 6.0 % 6.6 % 0.5 % 9.0 % SC 900CP-US 5.4 % 6.0 % 6.6 % 5.4 % 6.0 % 6.6 % 0.5 % 9.0 % * DC voltage = 600 V ** DC voltage = 1000 V Type of the Two-winding transformers Four-winding transformers V k min V k nom V k max V k min V k nom V k max V k dif max V k 1-2 min SC 1850-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % SC 2200-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % 16 SC_Trafo-TI-en-65 Technical Information

SMA Solar Technology AG 4 Appendix Type of the Two-winding transformers Four-winding transformers V k min V k nom V k max V k min V k nom V k max V k dif max V k 1-2 min SC 2500-EV-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % SC 2750-EV-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % Sunny Central CP JP Type of the Two-winding transformers Three-winding and four-winding transformers V k min V k nom V k max V k min V k nom V k max V k dif max V k 1-2 min SC 500CP-JP 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SC 630CP-JP 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SC 800CP-JP 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SC 1000CP-JP 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % Sunny Central Storage Type of the Two-winding transformers Three-winding and four-winding transformers V k min V k nom V k max V k min V k nom V k max V k dif max V k 1-2 min SCS 500 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SCS 630 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SCS 720 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SCS 760 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SCS 800 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SCS 850 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SCS 900 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % SCS 1000 5.0 % 6.0 % 7.0 % 5.0 % 6.0 % 7.0 % 0.5 % 9.0 % Type of the Two-winding transformers Four-winding transformers V k min V k nom V k max V k min V k nom V k max V k dif max V k 1-2 min SCS 2200 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % SCS 2200-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % SCS 2475 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % SCS 2475-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % SCS 2500-EV 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % SCS 2500-EV-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % SCS 2750-EV 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % SCS 2750-EV-US 5.0 % 6.0 % 8.5 % 5.0 % 6.0 % 8.5 % 0.5 % 9.0 % Technical Information SC_Trafo-TI-en-65 17

www.sma-solar.com