Harmonic Distortion Evaluations

Similar documents
BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP

Effects of Harmonic Distortion I

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

POWER QUALITY AND SAFETY

Power Factor & Harmonics

Alternative Designs to Support Electronic Loads in Extensive UPS Distribution Systems

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Prepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA

1C.4.1 Harmonic Distortion

22.0 Harmonics in Industrial Power Systems

Southern Company Power Quality Policy

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

Harmonic control devices. ECE 528 Understanding Power Quality

PowerMonitor 5000 Family Advanced Metering Functionality

Unit 29 Three-Phase Transformers

NJWA - Harmonics and Drives Proper System Design

ECE 528 Understanding Power Quality

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

shunt (parallel series

Power Quality and Digital Protection Relays

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

Transformer Protection

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

E N G I N E E R I N G M A N U A L

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ZENER ELECTRIC PTY LTD

Alternators Reactance for Nonlinear Loads

Roadmap For Power Quality Standards Development

ECE 528 Understanding Power Quality

Power Quality Requirements for Connection to the Transmission System

Principles for Controlling Harmonics

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

1. Introduction to Power Quality

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Harmonic Filtering in Variable Speed Drives

Alternator winding pitch and power system design

Wind Power Facility Technical Requirements CHANGE HISTORY

Harmonic Mitigating Transformer - Technical Guide

New Methods to Mitigate Distribution System Harmonics

Emicon Engineering Consultants L.L.C.

Project acronym: Multi-island

Harmonic control devices

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Overcurrent Elements

POWER QUALITY PRODUCTS FOR NON-LINEAR LOADS

Dry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

Final Exam Fall 2018

FAQ for SIMOREG 6RA70 and Control Module

Understanding Input Harmonics and Techniques to Mitigate Them

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08

Mitigation of Harmonics Produced by Nonlinear Loads in Industrial Power System

Grid Impact of Neutral Blocking for GIC Protection:

Harmonic Filters for Single Phase Equipment

Harmonic Requirements

PTTS series. Power Transformer Test System. Scope of Work:

TO LIMIT degradation in power quality caused by nonlinear

Drives 101 Lesson 5. Power Input Terminology for a VFD

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

Table of Contents. Introduction... 1

EN50160 Individual Report Summary

Power Analysis Summary

Evaluation of Harmonic Suppression Devices

STUDY OF THE EFFECTS OF HARMONICS IN THE DESIGN OF TRANSMISSION NETWORK SHUNT COMPENSATORS: NETWORK SIMULATION AND ANALYSIS METHODS

Emission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System

The increase in the application

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

New power tools provide quality and efficiency By

Analysis of Harmonic Distortion in Non-linear Loads

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM

Power Quality Notes 2-1 (MT)

CHAPTER 4 HARMONICS AND POWER FACTOR

Harmonics White Paper

Harmonic Planning Levels for Australian Distribution Systems

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

Power Quality in High Density Residential Distribution Grids

IMPACT OF VARIABLE FREQUENCY DRIVES ON ELECTRICAL SYSTEM

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO

Fluke 40/41 Power Harmonics Analysers

ELECTRICITY ASSOCIATION SERVICES LIMITED 2001

Harmonics Elimination Using Shunt Active Filter

An Introduction to Power Quality

Harmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems

Simulation of H bridge Inverter used for Induction Melting Furnace

Distance Relay Response to Transformer Energization: Problems and Solutions

Power quality measurements in a singlehouse

Transcription:

Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion observed in many places in the system. Therefore, to limit both voltage and current harmonic distortion, IEEE Standard 519-1992 proposes to limit harmonic current injection from end users so that harmonic voltage levels on the overall power system will be acceptable if the power system does not inordinately (extremely) accentuate the harmonic currents. This approach requires participation from both end users and utilities. End users For individual end users, IEEE Standard 519-1992 limits the level of harmonic current injection at the point of common coupling (PCC). This is the quantity end users have control over. Recommended limits are provided for both individual harmonic components and the total demand distortion. The concept of PCC is illustrated in Fig. 6.1. These limits are expressed in terms of a percentage of the end user s maximum demand current level, rather than as a percentage of the fundamental. This is intended to provide a common basis for evaluation over time. The utility

Since the harmonic voltage distortion on the utility system arises from the interaction between distorted load currents and the utility system impedance, the utility is mainly responsible for limiting the voltage distortion at the PCC. The limits are given for the maximum individual harmonic components and for the total harmonic distortion (THD). These values are expressed as the percentage of the fundamental voltage. For systems below 69 kv, the THD should be less than 5 percent. Sometimes the utility system impedance at harmonic frequencies is determined by the resonance of power factor correction capacitor banks. This results in a very high impedance and high harmonic voltages. Therefore, compliance with IEEE Standard 519-1992 often means that the utility must ensure that system resonances do not coincide with harmonic frequencies present in the load currents. Thus, in principle, end users and utilities share responsibility for limiting harmonic current injections and voltage distortion at the PCC. Since there are two parties involved in limiting harmonic distortions, the evaluation of harmonic distortion is divided into two parts measurements of the currents being injected by the load and calculations of the frequency response of the system impedance. Measurements should be taken continuously over a sufficient period of time so that time variations and statistical characteristics of the harmonic distortion can be accurately represented. Sporadic measurements should be avoided since they do not represent harmonic characteristics accurately given that harmonics are a continuous phenomenon. The minimum measurement period is usually 1 week since this provides a representative loading cycle for most industrial and commercial loads. Concept of point of common coupling Evaluations of harmonic distortion are usually performed at a point between the end user or customer and the utility system where another customer can be served. This point is known as the point of common coupling. The PCC can be located at either the primary side or the secondary side of the service transformer depending on whether or not multiple customers are supplied from the transformer. In other words, if multiple customers are served from the primary of the transformer, the PCC is then located at the primary. On the other hand, if multiple customers are served from the secondary of the transformer, the PCC is located at the secondary. Figure 6.1 illustrates these two possibilities.

Figure 6.1 PCC selection depends on where multiple customers are served. (a) PCC at the transformer primary where multiple customers are served. (b) PCC at the transformer secondary where multiple customers are served. Note that when the primary of the transformer is the PCC, current measurements for verification can still be performed at the transformer secondary. The measurement results should be referred to the transformer high side by the turns ratio of the transformer, and the effect of transformer connection on the zero-sequence components must be taken into account. For

instance, a delta-wye connected transformer will not allow zero-sequence current components to flow from the secondary to the primary system. These secondary components will be trapped in the primary delta winding. Therefore, zero-sequence components (which are balanced triplen harmonic components) measured on the secondary side would not be included in the evaluation for a PCC on the primary side. Harmonic evaluations on the utility system Harmonic evaluations on the utility system involve procedures to determine the acceptability of the voltage distortion for all customers. Should the voltage distortion exceed the recommended limits, corrective actions will be taken to reduce the distortion to a level within limits. IEEE Standard 519-1992 provides guidelines for acceptable levels of voltage distortion on the utility system. These are summarized in Table 6.1. Note that the recommended limits are specified for the maximum individual harmonic component and for the THD. Note that the definition of the total harmonic distortion in Table 6.1is slightly different than the conventional definition. The THD value in this table is expressed as a function of the nominal system rms voltage rather than of the fundamental frequency voltage magnitude at the time of the measurement. The definition used here allows the evaluation of the voltage distortion with respect to fixed limits rather than limits that fluctuate with the system voltage. A similar concept is applied for the current limits. There are two important components for limiting voltage distortion levels on the overall utility system Harmonic currents injected from individual end users on the system must be limited. These currents propagate toward the supply source through the system impedance, creating voltage distortion. Thus by limiting the amount of injected harmonic currents, the voltage distortion

can be limited as well. This is indeed the basic method of controlling the overall distortion levels proposed by IEEE Standard 519-1992. The overall voltage distortion levels can be excessively high even if the harmonic current injections are within limits. This condition occurs primarily when one of the harmonic current frequencies is close to a system resonance frequency. This can result in unacceptable voltage distortion levels at some system locations. The highest voltage distortion will generally occur at a capacitor bank that participates in the resonance. This location can be remote from the point of injection. Source : http://nprcet.org/e%20content/misc/e- Learning/EEE/IV%20YEAR/EE1005%20-%20POWER%20QUALITY.pdf