Thermal Imaging, Power Quality and Harmonics

Similar documents
ECE 2006 University of Minnesota Duluth Lab 11. AC Circuits

2.0 AC CIRCUITS 2.1 AC VOLTAGE AND CURRENT CALCULATIONS. ECE 4501 Power Systems Laboratory Manual Rev OBJECTIVE

Load Isolation Transformers

Emicon Engineering Consultants L.L.C.

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

Generator Advanced Concepts

Dr.Arkan A.Hussein Power Electronics Fourth Class. 3-Phase Voltage Source Inverter With Square Wave Output

Fluke 40/41 Power Harmonics Analysers

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Polyphase Systems. Dr Gamal Sowilam

22.0 Harmonics in Industrial Power Systems

HARMONICS CAUSES AND EFFECTS

Transformer Waveforms

Power Quality Monitoring and Power Metering Tutorial

CHAPTER 5 CONCEPTS OF ALTERNATING CURRENT

Fundamentals of Power Quality

Alternating Current Page 1 30

Three-Phase, Step-Wave Inverter Circuits

ESO 210 Introduction to Electrical Engineering

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

Single-Phase Transformation Review

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

Bakiss Hiyana binti Abu Bakar JKE, POLISAS BHAB

Inductance in DC Circuits

An Infrared View of Inductive Heating

An Introduction to Power Quality

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Power Factor & Harmonics

Dry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Preface...x Chapter 1 Electrical Fundamentals

ECET Modern Power

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

Chapter 33. Alternating Current Circuits

Advanced electromagnetism and electromagnetic induction

General Description & Features Selection Charts Definition of Terms... 42

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

THE SINUSOIDAL WAVEFORM

APPLICATION NOTE - 018

Lab 1: Basic RL and RC DC Circuits

Testing Power Sources for Stability

EE42: Running Checklist of Electronics Terms Dick White

Voltage and Current Waveforms Enhancement using Harmonic Filters

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

Chapter 11. Alternating Current

1. Explain in detail the constructional details and working of DC motor.

Module 1. Introduction. Version 2 EE IIT, Kharagpur

TECHNICAL BULLETIN 004a Ferroresonance

Harmonics White Paper

A 11/89. Instruction Manual and Experiment Guide for the PASCO scientific Model SF-8616 and 8617 COILS SET. Copyright November 1989 $15.

AN EQUIVALENT CIRCUIT MODEL FOR A THREE PHASE HARMONIC MITIGATING TRANSFORMER

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

TRANSFORMER THEORY. Mutual Induction

TUNED AMPLIFIERS 5.1 Introduction: Coil Losses:

Reducing Total Harmonic Distortion with Variable Frequency Drives

DISCUSSION OF FUNDAMENTALS

UNIVERSITY OF UTAH ELECTRICAL ENGINEERING DEPARTMENT

Basic electronics Prof. T.S. Natarajan Department of Physics Indian Institute of Technology, Madras Lecture- 17. Frequency Analysis

RLC Frequency Response

Lab #5 ENG RC Circuits

Economical Solutions to Meet Harmonic Distortion Limits[4]

Contents. Core information about Unit

Inductance, capacitance and resistance

Device Interconnection

Electromagnetic Harmonic Filters Technical Guide

CHAPTER 4 HARMONICS AND POWER FACTOR

Introduction to Harmonics and Power Quality

AC Sources for IEC 1000 Harmonics and Flicker Testing

ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment)

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

Active Harmonic Filter (AF3)

BASIC ELECTRONICS PROF. T.S. NATARAJAN DEPT OF PHYSICS IIT MADRAS

Analysis of Harmonic Distortion in Non-linear Loads

POWER FACTOR CORRECTION AND ITS PITFALLS

UNIT 2. Q.1) Describe the functioning of standard signal generator. Ans. Electronic Measurements & Instrumentation

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

Basics of Electricity

Low Pass Harmonic Filters

EE351 Laboratory Exercise 4 Field Effect Transistors

Chapter Objectives: Payam zarbakhsh EElE301 Circuit Theory II Department of Electrical and Electronic Engineering Cyprus International university

Understanding Harmonics

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK UNIT I BASIC CIRCUITS ANALYSIS PART A (2-MARKS)

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

Exercise 9. Electromagnetism and Inductors EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Magnetism, magnets, and magnetic field

UNBALANCED CURRENT BASED TARRIF

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)

Experiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE

Electrical Circuits (2)

POWER- SWITCHING CONVERTERS Medium and High Power

(2) New Standard IEEE P (3) Core : (4) Windings :

Power Electronics. Exercise: Circuit Feedback

B.Tech II SEM Question Bank. Electronics & Electrical Engg UNIT-1

Analog Electronic Circuits

Chapter 33. Alternating Current Circuits

Glossary 78 LIFETIME LIMITED WARRANTY. GREENLEE Phone: (International)


Table of Contents. Introduction...2 Conductors and Insulators...3 Current, Voltage, and Resistance...6

As delivered power levels approach 200W, sometimes before then, heatsinking issues become a royal pain. PWM is a way to ease this pain.

IDEAL Test and Measurement THE BASICS OF POWER QUALITY

Transcription:

Thermal Imaging, Power Quality and Harmonics Authors: Matthew A. Taylor and Paul C. Bessey of AVO Training Institute Executive Summary Infrared (IR) thermal imaging (thermography) is an effective troubleshooting tool, but many electricians who use IR cameras to spot overheated wires, connections and components may not be knowledgeable about the full range of causes that can cause such overheating, in particular issues of power quality and harmonics. Thermal Imaging for Troubleshooting Thermography is rapidly becoming a valuable method for detecting problems in electrical systems. Fluke TiX500 Infrared Camera Excess heat is a common byproduct of many well-understood electrical malfunctions such as loose or corroded connections or bad motor bearings. When an IR image is compared to a regular photographic image (most IR cameras will show you both), many electrical problems become quite obvious, as shown in the example below where one of the three fuses is much hotter than the others.

Visible-Light Photo (left) and IR Photo (right) Showing Hot Fuse in One Phase Possible Bad Bearing Thermal imaging can detect an issue in an electrical system before that issue significantly degrades the performance of the system, or before the issue gives rise to a safety problem such as the risk of fire. An electrician who performs routine periodic thermal inspections with an IR camera can avoid most catastrophic failures and keep the plant running smoothly. It is a good practice to keep a historical record of thermal images of various components, wires and connections taken under repeatable conditions, so that any changes in the heat signatures of these components will alert the electrician to the need for some preemptive action to correct the issue. Often this preemptive action will involve something simple like re-torqueing lug nuts, cleaning corrosion off of terminals or replacing an undersized conductor with a properly rated one. An additional advantage of thermography is that it allows the electrician to detect a problem while standing off some safe and convenient distance from the item being tested. For example, measuring

the temperature of transformers on utility poles while standing on the ground with an IR camera is much easier and safer than climbing poles. It may not be generally recognized by many plant electricians that there are whole classes of problems that show up as excess heat on an IR camera that are not due to high resistance connections or bad bearings. These problems are due to power quality issues and harmonics. This paper addresses these more complex issues. Power Factor When the current is in-phase with the voltage then the maximum power is transferred to the load and the power factor is equal to one. Many facilities have a preponderance of inductive loads such as motors. These loads, if uncompensated, will cause the current to be out of phase with the voltage, thereby reducing the power factor. When the current drifts out of phase with the voltage, the motors must draw more current in order to maintain the same work output. The extra current flowing through the conductors manifests as extra heat. An increase in the temperature of the conductors might be detectable with an IR camera, if compared with historical images taken under repeatable conditions. Banks of capacitors are often used to bring the current back into phase with the voltage, thereby bringing the power factor back close to one and reducing electric bills. Harmonics Fundamentals Consider the following simple electrical system where the Source block represents single phase electrical service provided by the power company, E S represents the source voltage, Z S represents the source impedance and Z L represents the load impedance. If the source impedance was zero (the ideal, but impossible case) then nothing one could do on the load side could distort the source voltage (E s ). Single Phase Electrical Service Driving a Single Load

Volts Amps The voltage supplied supplied by the power company is intended to be undistorted by harmonics, which means it is purely sinusoidal. In an ideal system driving a resistive load, the current is also sinusoidal. 200 60 Hz 120V Driving a 100 Ohm Resistor 100 2 1 0 0-1 -100-2 -200 0 0.005 0.01 0.015 0.02 0.025 0.03 seconds Purely Sinusoidal (Undistorted) Voltage and Current The plot above represents the voltage across and the current through a 100 ohm load resistor, plotted over time. If, instead of plotting the voltage and current versus time, you leave time out of it and plot the current versus the voltage, the resultant plot is a straight line, as shown below. This is just a plot of Ohm s Law, E = IR with R = 100 ohms. Resistive loads are called linear due to the fact that this V-I plot is a straight line.

Amps 2 V-I Curve for 100 ohm Resistor 1.5 1 0.5 0-0.5-1 -1.5-2 -200-150 -100-50 0 50 100 150 200 Volts V-I Curve for Linear Load Semiconductor loads such as computers, switching power supplies, electronic ballasts and variable frequency motor drives are non-linear loads, which results in a distorted sine wave. The following plot is an example of a distorted sine wave, which could represent the voltage across and/or the current through a load impedance.

200 Distorted Sine Wave 150 100 50 0-50 -100-150 -200 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 seconds Distorted Sine Wave (Voltage or Current) This common form of distortion is called clipping because the tops and bottoms of the sine waves are clipped off. The resulting V-I curve (see plot below) is no longer a straight line (the left and right sides of the line level out), so we say that the load is non-linear. This is just one type (out of many types) of distortion.

Volts 200 V-I Curve for Non-Linear Load 150 100 50 0-50 -100-150 -200-2 -1.5-1 -0.5 0 0.5 1 1.5 2 Amps V-I curve for a Non-Linear Load A Frenchman named Fourier figured out (in the early 1800 s) that you can create any continuous periodic signal with frequency f (such as our clipped sine wave) by adding together a series of pure sine waves whose frequencies are integer multiples of f. The main frequency f is called the fundamental frequency. The second harmonic is the sine wave with frequency 2 f, the third harmonic has frequency 3 f, etc. i When sine waves are distorted symmetrically about their average values (like our clipped signal) then they are composed of odd harmonics only. Most often this is the case so that odd harmonics are much more commonly observed than even harmonics. Below is an example of how the fundamental and two odd harmonics might add up for an arbitrarily chosen distorted voltage or current waveform shape.

current or voltage 200 150 100 Distorted Wave is a Sum of Pure Sine Waves fundamental 3rd harmonic 5th harmonic sum 50 0-50 -100-150 -200 0 0.005 0.01 0.015 0.02 0.025 0.03 seconds Distorted Wave Composed of a Sum of Harmonics These harmonics are a power quality problem because electrical systems and components are (typically) designed for 60 Hertz (or 50 Hertz in some countries) and several undesirable things may happen when they are subjected to 180 Hertz (the 3 rd harmonic), 300 Hertz (the 5 th harmonic) and higher frequencies. We tend to think of the resistance of conductors as independent of frequency. However, that is not strictly true. At higher frequencies (or higher harmonics of the fundamental frequency) the current moves away from the center towards the skin of the conductor. This skin effect, since it crowds more current in a smaller cross-sectional area, results in increased conductor resistance at higher frequencies. Increased resistance results in more power lost as heat, potentially contributing to overheating of conductors, terminations and components. Thermography may provide our first clue that we are having such problems. The Method of Symmetrical Components In order to analyze three-phase electrical systems we re going to need to understand some mathematics developed by a man named Fortescue in the early 1900 s called the Method of Symmetrical Components. ii Consider the three-phase Y system shown below which consists of some three-phase loads (Z AB, Z AC, and Z BC ) and some single-phase loads (Z a, Z b and Z c ).

Three-Phase Electrical System A balanced three-phase system with no harmonics has E a, E b and E c equal in amplitude and 120 degrees apart, and the same goes for the respective currents. This is not true for an unbalanced system and in real life all systems are to some extent unbalanced. Unbalanced current draws give rise to unbalanced voltages and phase angles between phases that are not exactly 120 degrees. This can cause problems that will often show up on IR images. To make analysis of unbalanced systems easier, the method of symmetrical components is used. This method can be elegantly expressed using the branch of mathematics that deals with vectors and matrices, called linear algebra. If you are not familiar with linear algebra, feel free to skip the next few paragraphs. Here s how it works. Unbalanced phasors representing the complex voltages (E a, E b and E c ) or the complex currents (I a, I b and I c ) can be represented as the vector sum of three sets of balanced phasors. These three sets of balanced phasors are called the zero sequence, positive sequence and negative sequence components, represented in the following equations by the subscripts 0, 1 and 2. Let s concentrate on the voltage equations first. ii E a E abc = [ E b ] = [ E c E a,0 E b,0 E a,1 E b,1 E a,2 E b,2 ] + [ ] + [ ] E c,0 E c,1 E c,2 The rightmost 3 vectors in the equation above are the zero sequence, positive sequence and negative sequence vectors. We define the operator (used to shift the phases of the component phasors so that they are 120 degrees apart) as: = e j(2/3)

The 3 components of the zero sequence vector are of equal amplitude and in-phase, so the zero sequence vector simplifies to: E a,0 [ E b,0 ] = [ E c,0 The 3 positive sequence phasors are of the same amplitude (call that amplitude E 1 ) but are 120 degrees apart from each other. Multiplying by imposes a 120 degree phase shift, and multiplying by and 2 imposes a 240 degree phase shift, so E 0 E 0 E 0 ] E a,1 E 1 [ E b,1 ] = [ α 2 E 1 ] E c,1 αe 1 The 3 negative sequence vectors are of the same magnitude (call that amplitude E 2 ) but the sequence is reversed, so E a,2 E 2 [ E b,2 ] = [ αe 2 ] E c,2 α 2 E 2 E 0 1 1 1 Then if we define E 012 = [ E 1 ] and A = [ 1 α 2 α ], we can express our decomposition into E 2 1 α α 2 symmetrical components quite compactly as AE 012 such that: E abc = AE 012 E 012 is a real 3-vector (not complex) representing the amplitudes of the 3 symmetrical components and E abc is a complex 3-vector representing the (perhaps unbalanced) phasors of the actual voltages. In real life, the 3 complex numbers in the vector E abc may have been obtained by an electrician using a power quality meter to measure the voltage phasors off of the Y-configured secondary of a 3 phase transformer. If we have measurements of the 3 phasors from a 3 phase transformer and wish to compute the magnitude of the zero, positive and negative sequence components, then we can do it using the inverse of the A matrix. E 012 = A 1 E abc 1 1 1 where A 1 = 1 [ 1 α α 2 ] 3 1 α 2 α The math applies in analogous manner to the currents, so the equivalent current formulation is

I abc = AI 012 and I 012 = A 1 I abc If the legs of the original three-phase system are sequenced as A-B-C, then the three equal positive sequence phasors will also be sequenced A-B-C, but the negative sequence phasors will be sequenced A- C-B. The zero sequence phasors are all in-phase. A balanced system with no harmonics will have only the positive sequence vectors. In other words, the magnitude of the negative sequence vectors and the zero sequence vectors will be zero. The following plot shows the zero, positive and negative sequence component phasors (the bottom row of the figure) for some unbalanced system (the top row of the figure). Each color phasor in the top plot is the vector sum of the same color in the lower 3 plots. The zero-sequence plot shows only one phasor but that s because all 3 phasors are in phase and therefore lie right on top of each other on the plot. All of these phasor diagrams rotate counterclockwise over time (one complete rotation in 1/60 th of a second if the frequency is 60 Hertz). Unbalanced 3-Phase Voltage or Current Zero-Sequence Component Positive-Sequence Component Negative-Sequence Component Method of Symmetrical Components You can experiment with plots like this using a free, downloadable learning tool called the Power Quality Teaching Toy created by Alex McEachern at Power Standards Laboratory. It can be used to explore the method of symmetrical components, harmonics and power quality issues. It can be downloaded from http://www.powerstandards.com/pqteachingtoyindex.php.

current or voltage In the case of a three-phase motor being driven by unbalanced voltages, the negative sequence phasors, because they are sequenced opposite to the positive sequence phasors, will exert a motor torque in the opposite direction from the motor rotation. In other words, they will work against the motor. This wasted power working against the motor gets dissipated as excess heat which may be detected with an IR camera. Therefore thermal imaging may be a good troubleshooting tool to indicate the presence of an unbalanced load condition on the secondary of a 3-phase transformer. A perfectly balanced 3-phase Y system will have no current on the neutral wire. In an unbalanced system, the zero sequence currents will add in-phase on the neutral wire to cause excess heat on that wire which may be detected with an IR camera. The symmetrical component phasors are valid only for a single frequency at a time, so if there are harmonics then the plot for each harmonic frequency must be considered independently. For example, let us consider the third harmonic. The third harmonic poses particular problems in a three-phase system. Harmonics in a Three-Phase System Consider a three-phase system that has well balanced loads but has a third harmonic because of some electronic ballasts used in the fluorescent lighting or some other non-linear loads. The following plot shows the fundamentals of the three phases (the 3 larger sine waves) and the third harmonics (the smaller sine wave). The third harmonic of each of the three phases all lie right on top of each other (they are in-phase), so they show up on the plot below as a single red line. 200 150 100 phase A fundamental phase B fundamental phase C fundamental 3rd harmonics all 3 phases 50 0-50 -100-150 -200 0 0.005 0.01 0.015 0.02 0.025 0.03 seconds Third Harmonic of All Three Phases Adds In-Phase Although in this well-balanced system there is no zero-sequence energy at the fundamental frequency, at the third harmonic frequency all of energy adds in-phase, which is just another way of saying that all of the 3 rd harmonic energy goes into the zero-sequence phasors. Remember that zero-sequence energy results in excess current (and heat) on the neutral wire, potentially overheating the wire and associated

current or voltage terminations. This condition could potentially be detected with thermography before it led to significant risk of fire. All harmonics that are integer multiples of three are also zero-sequence harmonics (3 rd, 6 th, 9 th, etc). These are also called triplen harmonics. These harmonics tend to decrease in amplitude as they go up in frequency, so the 3 rd harmonic is usually the worst. Other undesirable things happen with the second harmonic. 200 Second Harmonic Causes Negative Sequence Components 150 100 50 0-50 -100-150 -200 0 0.0042 0.0083 0.0125 0.0167 0.0208 0.025 0.0292 0.0333 seconds 3-Phase: Dashed Lines Represent the Fundamental, Solid Lines the 2 nd Harmonic On the plot above, the fundamental frequency waves are represented by the dashed lines. Notice that the sequence of the peaks, traveling from left to right on the plot is blue, green, red. However, if you look at the 2 nd harmonics (represented by the smaller solid line waves) you will notice that the order is blue, red, green. The fact that the sequence is reversed means that the 2 nd harmonic is a negativesequence harmonic. The 5 th, 8 th, 11 th, etc. harmonics are also negative-sequence harmonics. The even harmonics are typically close to zero in amplitude so that the 2 nd harmonic is usually very small. The higher the frequency the lower the magnitude tends to be, so the first odd negative-sequence harmonic (the 5 th harmonic) tends to me the most disruptive.

Remember that negative-sequence harmonics produce motor torque that works against the desired rotation of the motor, wasting energy that manifests as excess heat potentially identifiable with an IR camera. Variable Frequency Drives Variable speed (also called variable frequency ) motor drives (VFDs) typically use a pulse width modulated (PWM) voltage to control the speed of a motor. The pulses out of a typical PWM module is shown in blue in the figure below. The red line is the integral of the pulses, meant to be an approximation to a sine wave. Output of a Pulse Width Modulator (PWM) Used in a Variable Frequency Drive (VFD) iii Because the red waveform is not a pure sine wave, we have harmonics. The relative amplitudes of the harmonics caused by the motor drive typically look something like the following. Harmonic Components of a Typical VFD iv VFD s such as the one described above do not produce a third harmonic component or any triplen harmonics, but that 5 th and 11 th harmonics are negative sequence harmonics and therefore manifest as

reverse torque. v Once again, a disciplined program of periodic thermographic surveys may catch problems due to negative sequence harmonics caused by VFD s and allow one to take corrective action such as the installation of harmonic filters. Transformers Transformers use iron cores to contain the magnetic fields essential to their operation. Stray currents called eddy currents are undesirable electric currents that circulate in the iron core to varying degrees depending on the design of the transformer. These eddy currents waste energy and produce heat in the iron core. Eddy currents increase in proportion to the square of the frequency, so that in a transformer designed for 60 Hertz, higher frequency harmonics may cause significant heating of the core. Besides wasting energy these eddy currents could cause safety problems due to overheating. vi Hysteresis in a transformer core refers to the fact that the magnetic field lags the energizing current in time. Hysteresis losses are worse at higher frequencies, so harmonics cause additional hysteresis loss. Skin effect in the conductors of a transformer cause an additional copper loss at higher harmonic frequencies. Some transformers are designed to operate in the presence of significant harmonics. These are called K-rated transformers. The higher the K-rating, the more harmonics the transformer can handle. These three factors: eddy current losses, hysteresis losses and skin effect losses can be big problems for transformers subjected to harmonics. All three problems result in excess heat, therefore they can be detected with a properly designed program of periodic thermographic inspection. Conclusion Thermography is fast becoming a valuable troubleshooting tool for electricians. However, the electrician armed with an IR camera will not be fully effective until he or she combines thermography with in-depth knowledge of the often subtle problems caused by power quality and harmonics issues. AVO Training Institute (http://www.avotraining.com/) offers courses in Thermal Imaging and Power Quality & Harmonics.

References i https://en.wikipedia.org/wiki/fourier_series ii https://en.wikipedia.org/wiki/symmetrical_components gives a more in-depth treatment of the method of symmetrical components. iii https://en.wikipedia.org/wiki/pulse-width_modulation iv http://www.ab.com/support/abdrives/documentation/techpapers/harmonicsbasics.pdf v http://www.ab.com/support/abdrives/documentation/techpapers/harmonicsbasics.pdf vi Power Quality Measurement and Troubleshooting, Glen A. Mazur, Second Edition, pages 136-139