Generator Protection M 3425

Similar documents
Generator Protection M 3420

Instruction Book. M 3425A Generator Protection

Generator Protection M 3425A

Instruction Book. M-3425A Generator Protection

Digital Motor Bus Transfer System M 4272

Transformer Protection M 3310

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

Transformer Protection M-3311A

Generator Protection GENERATOR CONTROL AND PROTECTION

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

1 INTRODUCTION ORDER CODE / INFORMATION

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

NTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

PD300. Transformer, generator and motor protection Data sheet

Instantaneous Overcurrent Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring

SPECIFICATION FOR OVERCURRENT RELAYS

Overcurrent Protection / 7SJ45

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual

PQube 3 Specifications

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

Current Loop Interface Module M 2025D

GPM. Field and Stator Ground Fault Protection Modules. Instruction Manual AF1. GE Grid Solutions

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

Multimeter 500CVD21 RTU500 series

Protection components

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

BE1-32R, BE1-32 O/U DIRECTIONAL POWER RELAY

Protective Relays Digitrip 3000

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges.

LZS-A500-3 POWER SUPPLY Installation, Operation, and Maintenance Manual. IM-LZSA500-3 January 2008 Revision H

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

These drawings and single line diagrams provide an outlook of Basler Electric solutions for Excitation System installations and retrofit

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

Power Meter Series PM3200 Functions and characteristics

satech SynchroStar GPS 200 Series

O V E R V I E W O F T H E

SEL-2664 Field Ground Module Data Sheet

489 Generator Management Relay Instruction Manual

N. TEST TEST DESCRIPTION

DECS-200N-C1 Negative Forcing Digital Excitation Control System

Protection and control VIP300. Technical manual

D I G I T A L V O L T A G E R E G U L A T O R

BE1-81O/U DIGITAL FREQUENCY RELAY FEATURES

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Stabilized Differential Relay SPAD 346. Product Guide

02/11/2015

02/11/2015

System Protection and Control Subcommittee

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

Transformer Protection

PowerLogic power-monitoring units. PM700 series power meter. Technical data sheet

Type CP-S, CP-C & CP-A Switch mode

presentation contents application advantages

COPYRIGHTED MATERIAL. Index

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

Replacement solution

PROTECTION OF TRANSFORMERS M-3311A TEST PLAN

Waterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

IRIG-B Interface (De-modulated) External clock synchronization signal IRIG format B00X

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

N. TEST TEST DESCRIPTION

Instructions AVC125-10: Voltage Regulator. Voltage Range. Maximum Continuous Burden. Voltage Range. Nominal Frequency

489 Generator Management Relay

LCL Series. SIngle Output Industrial Supplies. High Efficiency. Low Cost. 150 W Convection Cooled. 300 W & 500 W with Internal Fans

Utility Communications Teleprotection Equipment TPT-200

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

489 Generator Management Relay

PQube 3 Specifications

Introduction DIN rail mounted electricity meters

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

Catastrophic Relay Misoperations and Successful Relay Operation

Power Processor - Series 700F 10KVA to 150KVA

ASHIDA Numerical 3OC + 1EF Protection Relay

ASHIDA Numerical OC/EF Protection Relay

NERC Protection Coordination Webinar Series July 15, Jon Gardell

Multimeter 560CVD11 Data sheet

BUS2000 Busbar Differential Protection System

SPAE 010, 011 High Impedance Protection Relay

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

Fuzzy Temperature Controllers E5AF

GE Power Management. Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C

Type: ADR233A (ADITYA V2 Series) (Preliminary) ASHIDA Numerical 3 Phase Tx. Differential Protection Relay

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

Substation applications

Transformer differential protection

Model Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

8V General information. 2 Order data 8V

Transcription:

PROTECTION Generator Protection M 3425 Integrated Protection System for Generators of All Sizes Unit shown with optional M 3925 Target Module and M 3931 HMI (Human Machine Interface) Module Provides all major protective functions for generator protection, including Field Ground (64F), Out-of-Step (78), and Split-Phase Differential (50DT) Expanded IPScom Communications Software provides simple and logical setting and programming Enhanced "pick and choose" functionality provides tailored applications at the lowest possible cost

Standard Protective Functions Dual zone phase distance protection for phase fault backup (21) Overexcitation (V/Hz) protection (24) Phase Undervoltage (27) protection 100% Stator Ground Fault protection via third harmonic neutral undervoltage (27TN) Sensitive dual setpoint Reverse Power, Low Forward Power or Overpower detection, one of which can be used for sequential tripping (32) Dual zone, offset mho Loss-of-Field protection (40) Sensitive Negative Sequence Overcurrent protection and alarm (46) Instantaneous Overcurrent (50) protection Inadvertent Generator Energizing protection (50/27) Generator Breaker Failure protection (50BF) Definite Time Overcurrent (50DT) can be used for split phase differential Instantaneous Overcurrent (50N) protection Neutral Inverse Time Overcurrent (51N) Three-phase Inverse Time Overcurrent (51V) Phase Overvoltage (59) Generator Ground Fault protection (59N) VT Fuse Loss detection and blocking (60FL) Out of Step protection (78) Four step Over/Underfrequency (81) protection Two-step Rate of Change of Frequency (81R) Generator Phase Differential protection (87) Ground Differential (87GD) protection External Function allows external devices to trip through M 3425 Generator Protection Relay Removable printed circuit board and power supply Both 50 and 60 Hz models available Both 1A and 5 A rated CT inputs available Additional trip inputs for externally connected devices IRIG-B time synchronization Operating Temperature: 20 C to +70 C Optional Features Redundant power supply M 3925 Target Module M 3931 Human-Machine Interface (HMI) Module M 3801D IPSplot PLUS Oscillograph Analysis Software Optional Protective Functions Stator Thermal protection using positive sequence inverse time overcurrent (51T) Field Ground protection (64F) Standard Features Eight programmable outputs and six programmable inputs Oscillography recording Time-stamped target storage for 24 events Metering of all measured parameters Three communications ports (two RS-232 and one RS-485) M 3820C IPScom Communications Software Includes MODBUS and BECO 2200 protocols Standard 19" rack-mount design 2

STANDARD PROTECTIVE FUNCTIONS Device Setpoint Number Function Ranges Increment Accuracy Phase Distance (dual-zone mho characteristic) 21 Circle Diameter #1, #2 0.1 to 100.0 Ω 0.1 Ω 0.1 Ω or 5% (0.5 to 500.0 Ω) ( 0.5 Ω or 5%) Offset #1, #2 100.0 to 100.0 Ω 0.1 Ω 0.1 Ω or 5% ( 500.0 to 500.0 Ω) ( 0.5 Ω or 5%) Impedance Angle #1, #2 0 to 90 1 1 Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% 24 Volts / Hz Definite Time Pickup #1, #2 100 to 200% 1% 1% Time Delay #1, #2 30 to 8160 Cycles 1 Cycle 25 Cycles Inverse Time Characteristic Curves Inverse Time #1 #4 Pickup 100 to 200% 1% 1% Time Dial: Curve #1 1 to 100 1 Time Dial: Curves #2 #4 0.0 to 9.0 0.1 Reset Rate 1 to 999 Sec. 1 Sec..02 Sec. or 1% (from threshold of trip) The percent pickup is based on nominal VT secondary voltage and nominal system frequency settings. The pickup accuracy stated is only applicable from 10 to 80 Hz, 0 to 180 V, 100 to 150% V/Hz and a nominal voltage setting of 120 V. Third-Harmonic Undervoltage, Neutral 27 TN 27 32 Pickup #1, #2 0.3 to 20.0 V 0.1 V 0.15 V or 1% Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% Undervoltage Inhibit #1,#2 5 to 180 V 1 V 0.5 V or 0.5% (positive sequence) Underpower Inhibit #1,#2 0.002 to 3.000 PU 0.001 PU 0.002 or 2% RMS Undervoltage 27 Pickup #1, #2 5 to 180 V 1 V 0.5 V or 0.5% 0.8 V or 0.75%* Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 0.5%** * When both RMS and Line Ground to Line Line is selected. ** When RMS (total waveform) is selected, timing accuracy is +20 cycles or 1%. 32 Directional Power Pickup #1, #2 3.000 to +3.000 PU 0.001 PU 0.002 PU or 2% Time Delay #1, #2 1 to 8160 Cycles 1 Cycle +16 Cycles or 1% The per-unit pickup is based on nominal VT secondary voltage and nominal CT secondary current settings. The 32 function can be selected as low forward power, reverse power, or overpower function. Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating. 3

STANDARD PROTECTIVE FUNCTIONS (cont.) Device Setpoint Number Function Ranges Increment Accuracy 40 Loss of Field (dual-zone offset-mho characteristic) Circle Diameter #1, #2 0.1 to 100.0 Ω 0.1 Ω 0.1 Ω or 5% (0.5 to 500.0 Ω) ( 0.5 Ω or 5%) Offset #1, #2 50.0 to 50.0 Ω 0.1 Ω 0.1 Ω or 5% ( 250.0 to 250.0 Ω) ( 0.5 Ω or 5%) Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% Voltage Control 5 to 180 V 1 V 0.5 V or 0.5% (positive sequence) Directional Element Fixed at 13 Voltage control for each zone can be individually enabled. 46 Negative Sequence Overcurrent Definite Time Pickup 3 to 100% 1% 0.5% of 5 A ( 0.5% of 1 A) Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% Inverse Time Pickup 3 to 100% 1% 0.5 % of 5 A ( 0.5% of 1 A) Time Dial Setting 1 to 95 1 3 Cycles or 3% (K= I 22 t) Definite Maximum Time to Trip 600 to 65,500 Cycles 1 Cycle 1% Definite Minimum Time 12 Cycles fixed Reset Time (Linear) 4 minutes (from threshold of trip) Pickup is based on the generator nominal current setting. 50 BF 50 BF-Ph 50 BF-N Breaker Failure Pickup Phase Current 0.10 to 10.00 A 0.01 A 0.1 A or 2% (0.02 to 2.00 A) ( 0.02 A or 2%) Neutral Current 0.10 to 10.00 A 0.01 A 0.1 A or 2% (0.02 to 2.00 A) ( 0.02 A or 2%) Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% 50BF can be initiated from designated M 3425 output contacts or programmable inputs. Instantaneous Overcurrent 50 Pickup 0.1 to 240.0 A 0.1 A 0.1 A or 3% (0.1 to 48.0 A) ( 0.02 A or 3%) Trip Time Response < 2 Cycles Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating. 4

STANDARD PROTECTIVE FUNCTIONS (cont.) Device Setpoint Number Function Ranges Increment Accuracy Instantaneous Overcurrent, Neutral 50N Pickup 0.1 to 240.0 A 0.1 A 0.1 A or 3% (0.1 to 48.0 A) ( 0.02 A or 3%) Trip Time Response < 2 Cycles 50 DT Definite Time Overcurrent Pickup Phase A #1, #2 0.20 A to 240.00 A 0.01 0.1 A or 3% (0.04 A to 48.00 A) ( 0.02 A or 3%) Pickup Phase B #1, #2 Pickup Phase C #1, #2 (same as above) (same as above) Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% When 50DT function is used for split-phase differential protection, 50BF, 87, and 87GD functions are not available. Inadvertent Energizing 50/ 27 51N 51V 50 27 Overcurrent Pickup 0.5 to 15.00 A 0.01 A 0.1 A or 2% (0.1 to 3.00 A) ( 0.02 A or 2%) Undervoltage Pickup 40 to 130 V 1 V 0.5 V Pick-up Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% Drop-out Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% Inverse Time Neutral Overcurrent Pickup 0.25 to 12.00 A 0.01 A 0.1 A or 1% (0.05 to 2.40 A) ( 0.02 A or 1%) Characteristic Curve Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC Curves Time Dial 0.5 to 11.0 0.1 3% or 3 Cycles 0.05 to 1.10 (IEC curves) 0.01 Inverse Time Overcurrent, with Voltage Control or Voltage Restraint Pickup 0.5 to 12.0 A 0.01 A 0.1 A or 1% (0.10 to 2.40 A) ( 0.02 A or 1%) Characteristic Curve Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC Curves Time Dial 0.5 to 11.0 0.1 3% or 3 Cycles 0.05 to 1.10 (IEC curves) 0.01 Voltage Control (VC) 5 to 180 V 1 V 0.5 V or 0.5% or Voltage Restraint (VR) Linear Restraint Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating. 5

STANDARD PROTECTIVE FUNCTIONS (cont.) Device Setpoint Number Function Ranges Increment Accuracy 59 RMS Overvoltage Pickup #1, #2 5 to 180 V 1 V 0.5 V or 0.5% 0.8 V to 0.75%* Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1%** * When both RMS and Line Ground to Line Line is selected. ** When RMS (total waveform) is selected, timing accuracy is +20 cycles or 1%. RMS Overvoltage, Neutral 59N Pickup #1, #2 5.0 to 180.0 V 0.1 V 0.5 V to 0.5% Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% VT Fuse-Loss Detection 60 FL A VT fuse-loss condition is detected by using the positive and negative sequence components of the voltages and currents. VT fuse-loss output can be initiated from internally generated logic or from input contacts. Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% Out of Step (mho characteristic) 78 Circle Diameter 0.1 to 100.0 Ω 0.1 Ω 0.1 Ω or 5% (0.5 to 500.0 Ω) ( 0.5 Ω or 5%) Offset 100.0 to 100.0 Ω 0.1 Ω 0.1 Ω or 5% ( 500.0 to 500.0 Ω) ( 0.5 Ω or 5%) Impedance Angle 0 to 90 1 1 Blinder 0.1 to 50.0 Ω 0.1 Ω 0.1 Ω or 5% (0.5 to 250.0 Ω) ( 0.5 Ω or 5%) Time Delay 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% Trip on mho Exit Enable/Disable Pole Slip Counter 1 to 20 1 Pole Slip Reset 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% 81 Frequency Pickup #1,#2,#3,#4 50.00 to 67.00 Hz 0.01 Hz 0.02 Hz 40.00 to 57.00 Hz* Time Delay #1 #4 2 to 65,500 Cycles 1 Cycle 2 Cycles or 1% The pickup accuracy applies to 60 Hz models at a range of 57 to 63 Hz, and to 50 Hz models at a range of 47 to 53 Hz. Beyond these ranges, the accuracy is 0.1 Hz. * This range applies to 50 Hz nominal frequency models. Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating. 6

STANDARD PROTECTIVE FUNCTIONS (cont.) Device Setpoint Number Function Ranges Increment Accuracy Rate of Change of Frequency 81R Pickup #1, #2 0.10 to 20.00 Hz/Sec. 0.01 Hz/Sec. 0.05 Hz/Sec. or 5% Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 20 Cycles Negative Sequence Voltage Inhibit 0 to 99% 1% 0.5% 87 Phase Differential Current Pickup 0.20 A to 3.00 A 0.01 A 0.1 A or 5% (0.04 to 0.60 A) ( 0.02 A or 5%) Percent Slope 1 to 100% 1% 2% Time Delay* 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% * When a time delay of 1 cycle is selected, the response time is less than 1 1/2 cycles. 87 GD Ground (zero sequence) Differential Pickup 0.20 to 10.00 A 0.01 A 0.1 A or 5% (0.04 to 2.00 A) ( 0.02 A or 5%) Time Delay 1 to 8160 Cycles* 1 Cycle +1 to -2 Cycles or 1% CT Ratio Correction (R C ) 0.10 to 7.99 0.01 * The Time Delay setting should not be less than 2 cycles. The 87GD function is provided primarily for low-impedance grounded generator applications. This function operates as a directional differential. If 3I 0 or I n is extremely small (less than 0.2 secondary Amps), the directional element is disabled. External Functions EXT Two functions are provided for externally connected devices to trip through the relay to provide additional logic and target information. Any one or more of the input contacts (IN1 IN6) can be programmed to activate designated output contacts after a selected time delay. Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 Cycle or 1% Nominal Settings Nominal Voltage 50 to 140 V 1 V Nominal Current 0.50 to 6.00 A 0.01 A VT Configuration Line-Line/Line-Ground/ Line-Ground to Line-Line* Seal-In Delay 2 to 8160 Cycles 1 Cycle 1 Cycle or 1% * When Line-Ground to Line-Line is selected, the relay internally calculates the line-line voltage from the line-ground voltages for all voltage-sensitive functions. This Line-Ground to Line-Line selection should only be used for a VT nominal secondary voltage of 69 V (not 120 V). Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating. 7

OPTIONAL PROTECTIVE FUNCTIONS Device Setpoint Number Function Ranges Increment Accuracy 51T Inverse Time Positive Sequence Overcurrent (I 2 t=k), for Stator Thermal Protection Pickup 0.50 to 15.00 A 0.01 A 0.1 A (0.10 to 3.00 A) ( 0.02 A) Time Delay @6X* 0.10 to 10.00 Sec 0.01 Sec 3% or 3 Cycles Reset Characteristics 4 minutes 3% (Linear) (from threshold of trip) * This time delay setting is at six times the pickup current. 64F 64B Field Ground Protection Pickup #1, #2 5 to 100 KΩ 1 KΩ 10% or ±1KΩ Time Delay #1, #2 1 to 8160 Cycles 1 Cycle ( 2 +1) Sec. IF Injection Frequency (IF) 0.10 to 1.00 Hz 0.01 Hz Brush Lift-Off Detection (measuring control circuit) Pickup 0 to 5000 mv 1 mv Time Delay 1 to 8160 Cycles 1 Cycle ( 2 +1) Sec. IF When 64F is purchased, an external Coupler Module (M 3921) is provided for isolation from dc field voltages. Figure 7, Typical Field Ground Connection Diagram, illustrates a typical connection utilizing the M 3921 Field Ground Coupler. Hardware dimensional and mounting information is shown in Figure 8, M 3921 Field Ground Coupler Mounting Dimensions. Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating. 8

Description The M 3425 Generator Protection Relay is suitable for all generator ratings and prime movers. Typical connection diagrams are illustrated in Figure 2, M 3425 Typical One-Line Connection Diagram, Figure 3, M 3425 Typical One-Line Connection Diagram (Configured for Split-Phase Differential), and Figure 4, M 3425 Typical Three-Line Connection Diagram. Configuration Options The M 3425 Generator Protection Relay is available with Standard Protective Functions, Optional Protective Functions, and Optional Features. This provides the user flexibility in selecting a protective system to best suit the application. The relay may be purchased as a Protection System which includes all Standard Protective Functions. Additional Optional Protective Functions may be added at the time of purchase at per-function pricing. The relay may also be purchased as a Base System, with the user selecting any ten (10) Standard Protective Functions. Additional Standard Functions and/or Premium Protective Functions may be added at the time of purchase at per-function pricing. The user can select the Human-Machine Interface (HMI) Module, Target Module, or redundant power supply at time of purchase for either the Protective System or Base System options. When the user purchases the Field Ground (64F) Premium Protective Function, an external coupler module (M 3921) is provided for isolation from the dc field voltages. Metering The relay provides metering of voltages (phase, neutral and sequence quantities), currents (phase, neutral and sequence quantities), real power, reactive power, power factor and impedance measurements. Metering accuracies are: Voltage: Current: Power: Frequency: 0.5 V or 0.5%, whichever is greater 0.8 V or 0.75%, whichever is greater (when both RMS and Line Ground to Line Line are selected) 5 A rating, 0.1 A or 3%, whichever is greater 1 A rating, 0.02 A or 3%, whichever is greater 0.01 PU or 2%, whichever is greater 0.02 Hz (from 57 to 63 Hz for 60 Hz models; from 47 to 53 Hz for 50 Hz models) Oscillographic Recorder The oscillographic recorder provides comprehensive data recording of all monitored waveforms, storing up to 170 cycles of data. The total record length is user-configurable for 1, 2, 3 or 4 partitions. The sampling rate is 16 times the power system nominal frequency (50 or 60 Hz). The recorder may be triggered either via the designated status inputs, trip outputs, or via serial communications. The recorder continuously stores waveform data, keeping the most recent data in memory. When triggered, the recorder stores pre-trigger data, then continues to store data in memory for a user-defined, post-trigger delay period. The records may be analyzed or viewed using Beckwith Electric M 3801D IPSplot PLUS Oscillograph Analysis software or M 3813 ComVert software, which converts Beckwith Electric oscillographic files to COMTRADE format. Target Storage A total of 24 targets can be stored. The information will include the function(s) operated, the functions picked up, input/output status, time stamp, and phase and neutral currents at the time of trip. Calculations Current and Voltage RMS Values: Uses discrete Fourier transform algorithm on sampled voltage and current signals to extract fundamental frequency phasors for relay calculations. RMS phase voltages for the 59 and 27 functions (when total RMS is selected), and the 24 function are obtained using the time domain approach to obtain accuracy over a wide frequency band. When the RMS option is selected, the magnitude calculation is accurate over a wide frequency range (10 to 80 Hz). When the DFT option is selected, the magnitude calculation is accurate near nominal frequency (50 or 60 Hz). 9

Power Input Options Nominal 110/120/230/240 V ac, 50/60 Hz, or nominal 110/125/220/250 V dc. UL/CSA rating 85 V ac to 265 V ac and from 80 V dc to 288 V dc. Burden 20 VA at 120 V ac/125 V dc. Withstands 300 V ac or 300 V dc for 1 second. Nominal 24/48 V dc, operating range from 18 V dc to 56 V dc. Burden 20 VA at 24 V dc and 20 VA at 48 V dc. Withstands 65 V dc for 1 second.an optional redundant power supply is available. Sensing Inputs Four Voltage Inputs: Rated nominal voltage of 60 V ac to 140 V ac at 60 Hz or 50 Hz. Will withstand 240 V continuous voltage and 360 V for 10 seconds. Source voltages may be line-to-ground or line-to-line connected. Phase sequence ABC or ACB is selectable. Voltage transformer burden less than 0.2 VA at 120 V ac. Seven Current Inputs: Rated nominal current (I R ) of 5.0 A or 1.0 A at 60 Hz or 50 Hz. Will withstand 2I R continuous current and 100I R for 1 second. Current transformer burden is less than 0.5 VA at 5 A, or 0.3 VA at 1 A. Control/Status Inputs The control/status inputs, INPUT1 through INPUT6, can be programmed to block any relay functions, to trigger the oscillographic recorder, or to operate one or more outputs. The control/status inputs should be dry contacts and are internally connected (wetted) to a 24 V dc power supply. To provide breaker status LED indication on the front panel, the INPUT1 control/status input must be connected to the 52b breaker status contact. The minimum current value to initiate/pickup an Input is >25 ma. Output Contacts The eight programmable output contacts (six form a and two form c ), the power supply alarm output contact (form b ), and the self-test alarm output contact (form c ) are all rated per IEEE C37.90 (See Tests and Standards section for details). Any of the functions can be individually programmed to activate any one or more of the eight programmable output contacts. Target/Status Indicators and Controls The RELAY OK LED reveals proper cycling of the microcomputer. The BRKR CLOSED LED will turn on when the breaker is closed (when the 52b contact input is open). The OSC TRIG LED indicates that oscillographic data has been recorded in the unit's memory. The TARGET LED will turn on when any of the relay functions operate. Pressing and releasing the TARGET RESET button resets the target LED if the conditions causing the operation have been removed. Holding the TARGET RESET button displays the present pickup status of the relay functions. The PS1 and PS2 LEDs will remain on as long as power is applied to the unit and the power supply is operating properly. Communication Communications ports include rear panel RS 232 and RS-485 ports, a front panel RS-232 port, and a rear-panel IRIG B port. The communications protocol implements serial, byte-oriented, asynchronous communication, providing the following functions when used with the Windows -compatible M 3820C IPScom Communications Software package. MODBUS and BECO 2200 protocols are supported providing: Interrogation and modification of setpoints Time-stamped trip target information for the 24 most recent events Real-time metering of all quantities measured Downloading of recorded oscillographic data 10

IRIG-B The M 3425 Generator Protection Relay can accept either modulated or demodulated IRIG B time clock synchronization signal. The IRIG B time synchronization information is used to correct the hour, minutes, seconds, and milliseconds information. HMI Module (optional) Local access to the relay is provided through an optional M-3931 HMI (Human-Machine Interface) Module, allowing for easy-to-use, menu-driven access to all functions via six buttons and a 2-line by 24 character alphanumeric LED. Features of the HMI Module include : User-definable access codes allow three levels of security Interrogation and modification of setpoints Time-stamped trip target information for the 24 most recent events Real-time metering of all quantities measured Target Module (optional) An optional M-3925 Target Module provides 24 target and 8 output LEDs. Appropriate target LEDs will light when the corresponding function operates. The targets can be reset with the TARGET RESET pushbutton. The OUTPUT LEDs indicate the status of the programmable output relays. Tests and Standards The relay complies with the following type tests and standards: Voltage Withstand Dielectric Withstand IEC 255-5 Impulse Voltage IEC 255-5 Insulation Resistance IEC 255-5 3,500 V dc for 1 minute applied to each independent circuit to earth 3,500 V dc for 1 minute applied between each independent circuit 1,500 V dc for 1 minute applied to IRIG-B circuit to earth 1,500 V dc for 1 minute applied between IRIG-B to each independent circuit 1,500 V dc for 1 minute applied between RS-485 to each independent circuit 5,000 V pk, +/- polarity applied to each independent circuit to earth 5,000 V pk, +/- polarity applied between each independent circuit 1.2 by 50 µs, 500 ohms impedance, three surges at 1 every 5 seconds > 40 Megaohms Electrical Environment Electrostatic Discharge Test IEC 1000-4-2 Class 4 (8 kv) point contact discharge Fast Transient Disturbance Test IEC 1000-4-4 Class 4 (4 kv, 2.5 khz) 11

Surge Withstand Capability ANSI/IEEE C37.90.1 Radiated Susceptibility ANSI/IEEE C37.90.2 2,500 V pk-pk oscillatory applied to each independent circuit to earth 2,500 V pk-pk applied between each independent circuit 5,000 V pk Fast Transient applied to each independent circuit to earth 5,000 V pk Fast Transient applied between each independent circuit 25-1000 Mhz @ 35 V/m (with 64F option, 20 V/m) Output Contacts Ratings IEEE C37.90 UL 508 CSA C22.2 No. 14 Atmospheric Environment Temperature IEC 68-2-1 IEC 68-2-2 IEC 68-2-3 30 A make for 0.2 seconds at 250 Vdc resistive 8 A carry at 120 Vac, 50/60 Hz 6 A break at 120 Vac, 50/60 Hz 0.1 A break at 125 Vdc 0.1 A break at 120 Vac Cold, 20 C for 96 hours Dry Heat, +70 C for 96 hours Damp Heat, +40 C @ 93% RH, for 96 hours Mechanical Environment Vibration IEC 255-21-1 Compliance Vibration response Class 1, 0.5 g Vibration endurance Class 1, 1.0 g UL-Listed per 508 Industrial Control Equipment CSA-Certified per C22.2 No. 14-95 Industrial Control Equipment Physical Size: 19.00" wide x 5.21" high x 10.20" deep (48.3 cm x 13.2 cm x 25.9 cm) Mounting: The unit is a standard 19", semiflush, three-unit high, rack-mount panel design, conforming to ANSI/EIA RS-310C and DIN 41494 Part 5 specifications. Vertical or horizontal panel-mount options are available. Approximate Weight: 17 lbs (7.7 kg) Approximate Shipping Weight: 25 lbs (11.3 kg) Recommended Storage Parameters Temperature: 5 C to 40 C Humidity: Maximum relative humidity 80% for temperatures up to 31 C, decreasing to 31 C linearly to 50% relative humidity at 40 C. Environment: Storage area to be free of dust, corrosive gases, flammable materials, dew, percolating water, rain and solar radiation. See Instruction Book, Appendix E, Layup and Storage for additional information. 12

Patent & Warranty The M 3425 Generator Protection Relay is covered by U.S. Patents 5,592,393 and 5,224,011. The M 3425 Generator Protection Relay is covered by a five year warranty from date of shipment. External Connections M 3425 external connection points are illustrated in Figure 1, External Connections, on the facing page. 13

- M 3425 Generator Protection Relay MODEL: FIRMWARE: D-0070 B EC K W IT H ELECT RIC C O. INC. W A R N IN G! C O N T A C T W IT H T E R M IN A L S M A Y C A U S E E L E C T R IC S H O C K 5 0 Hz 6 0 Hz S ERIA L NO. Danger! Contact avec les terminaux peut causer un choc electrique F O R C O N T A C T R A T IN G S S E E IN S T R U C T IO N M A N U A L U.S. PATENT 5,592,393, 5,224,011 6 19 0 118 t h AV E NO. L A RG O, F L 3 3 7 7 3 US U L 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 NRTL /C LR 89464 IRIG B CO M 2 RS 2 3 2 - + IN IN IN IN IN IN 6 5 4 3 2 1 8 IN RT N 7 6 5 4 3 2 1 OUT PUTS S ELF- T EST A LA RMS P/ S! ( 5 2 b ) INPUT S RS 4 8 5 C O M 3 PS2 PS1 F2 V V V FIELD GND A B C N I I I V A B V B C V A B C I I N a I b I c P S 2 P S 1 C A COUPLER + - + - V 3 A MP,2 5 0 V ( 3 A B ) 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 6 4 F s CAUTION: Application of external voltages to the IN PUTS terminals may result in damage to the unit. NOTES: 1. All relays are shown in the de energized state. 2. Output contacts #1 through #4 are high speed operation contacts. 3. The power supply relay (P/S) is energized when the power supply is OK. 4. The self test relay is energized when the relay has performed all self tests successfully. To fulfill requirements for UL and CSA listing, terminal block connections must be made with No. 22 12 AWG solid or stranded copper wire inserted in an AMP #324915 (or equivalent) connector and wire insulation used must be rated at 75 C minimum. Torque Requirements: Terminals 1 34: 12.0 in lbs Terminals 35 63: 8.0 in lbs, minimum, and 9.0 in lbs, maximum. s CAUTION: Over torquing may result in terminal damage.! - C R 6 1 9 0 1 1 8 t h A V E N O. 1 2 3 4 5 6 7 8 9 10 6 2 6 1 - F 1 F 3 P S 2 P S 1 F 2 3 A M P, 2 5 0 V ( 3 A B ) LISTED IND.CONT.EQ. 83F4 F1 F 4 1 8-5 8 5 5 18-5 6 8 5 2 6 5 RA T ED V O L T A GE RAT ED C URRENT 1A,NO M 5 A,NO M 6 0-14 0,5 0 / 6 0 Hz F4 F3 Figure 1 External Connections 14

Typical Connection Diagram This function is available as a standard protective function. This function is available as a optional protective function. This function provides control for the function to which it points. NOTE: Some functions are mutually exclusive; see Instruction Book for details. Utility System 52 Unit 50 BFPh 50 DT CT 52 Gen VT 81R 81 27 59 24 87 M-3921 + - 64F 64B 27 60FL 21 78 32 51V 40 50/27 51T 46 50 CT 27 32 27 TN 59N R VT 87 GD 50 BFN 50N 51N CT R High impedance Grounding with Third Harmonic 100% Ground Fault Protection Low impedance Grounding with Overcurrent Stator Ground Fault Protection Figure 2 One Line Connection Diagram 15

Typical Connection Diagram (Configured for Split-Phase Differential) This function is available as a standard protective function. This function is available as a optional protective function. This function provides control for the function to which it points. NOTE: Some functions are mutually exclusive; see Instruction Book for details. Utility System 52 Unit VT 52 Gen 81R 81 27 59 24 50 DT CT M-3921 + - 64F 64B 27 60FL 21 78 32 51V 40 50/27 51T 46 50 CT 27 32 27 TN 59N R VT 50N 51N CT R High impedance Grounding with Third Harmonic 100% Ground Fault Protection Low impedance Grounding with Overcurrent Stator Ground Fault Protection Figure 3 Typical One Line Connection Diagram (configured for split-phase differential) 16

UTILITY SYSTEM A B C Other Relays 50 51 A B C Three VT Wye-Wye Connection 39 Three VT Wye-Wye Connection - Alternate A B C 39 48 49 38 41 OR 38 41 46 47 40 43 40 43 52 Gen A B C 42 OR 42 Generator M 3921 Field Ground Coupler Module A B C Two VT Open-Delta Connection A B C 52b Other Relays 10 11 58 59 A B C 59 58 A B C 59 58 39 38 41 40 56 57 OR 57 56 OR 57 56 43 42 54 55 55 54 55 54 52 53 45 44 OR High Impedance Grounding Low Impedance Grounding Example of Control / Output Connections + DC: 24 V 48 V OR DC: 110 V 125 V 220 V 250 V AC: 110 V 120 V 230 V 240 V + POWER 60 62 SUPPLY 61 6311 10 52b BREAKER FAILURE INITIATE 60FL OSCILLOGRAPH RECORDER INITIATE 16 15 TRIP ALARM 12 13 SELF TEST FAILURE ALARM POWER OK STATUS ALARM TRIP VT FUSE LOSS 52G EXTERNAL INPUTS ALARM OUTPUTS CONTROL OUTPUTS TRIP OUTPUT Figure 4 M 3425 Typical Three Line Connection Diagram NOTE: M 3425 current terminal polarity marks ( ) indicate "entering" current direction when primary current is "from" the generator. If CT connections differ from those shown, adjust input terminals. NOTE: Wire to split phase differential CTs for use with 50DT split phase function. 17

17.68 [44.91] 17.50 [44.45] ACTUAL 5.21 [13.23] ACTUAL 5.28 [13.41] RECOMMENDED CUTOUT WHEN RELAY IS NOT USED AS STANDARD RACK MOUNT 17.50 [44.45] 10.20 [25.91] 19.00 [48.26] 18.31 [46.51] 0.35 [0.89] 0.40 [1.02] X 0.27 [0.68] Slot (4X) 2.25 [5.72] 1.48 [3.76] Standard 19" Horizontal Mount Chassis NOTE: Dimensions in brackets are in centimeters. Figure 5 Horizontal Mounting Dimensions NOTE: Panels for vertical mounting are available. When mounted vertically, the target module will be located at the top and all front-panel text will be horizontally aligned. Consult Beckwith Electric Co. for details. 18

OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 M 3425 Generator Protection Relay 5.65 [14.40] 0.35 [0.89] 6.19 [15.7] 2.25 [5.72] 1.97 [5.0] 0.28 [0.71] Dia. (4X) 5.59 [14.20] Actual 2.25 [5.72] 1.67 [4.24] 0.03 [0.076] TARGETS 19.00 [48.26] OUTPUTS 18.30 [46.51] 17.5 [44.45] ACTUAL 17.68 [44.91] EXIT ENTER TARGET RESET PS 2 PS 1 TARGET DIAG BRKR CLOSED OSC. TRIG RELAY OK TIME SYNC COM 1 17.50 [44.45] Recommended cutout when relay is not used as standard rack mount and is panel cut out mounted. 10.20 [25.91] 19.00 [48.26] NOTE: Dimensions in brackets are in centimeters. Figure 6 Vertical Mounting Dimensions 19

M 3921 Field Ground Coupler NOTES: 1. The above circuit measures insulation resistance (R f ) between rotor field winding and ground (64F). 2. Relay injects 15 V squarewave (V out ) and measures return signal (V f ) to calculate R f. 3. The injection frequency can be set (0.1 to 1.0 Hz) based on the rotor capacitance, in order to improve accuracy. 4. Analyzing signal rise time can determine if shaft brushes are open (64B). Function Specification Field/Exciter Supply Voltage Rating (Terminal (3) to (2)): 60 to 1200 V dc, continuous 1500 V dc, 1 minute Operating Temperature: 20 to +70, Centigrade Patent & Warranty The M 3921 Field Ground Coupler is covered by a five year warranty from date of shipment. Tests and Standards M 3921 Field Ground Coupler complies with the following tests and standards: Voltage Withstand Isolation 4 kv ac for 1 minute, all terminals to case Impulse Voltage IEC 255 5, 5,000 V pk, 1.2 by 50 ms, 0.5 J, 3 positive and 3 negative impulses at 5 second part 5 intervals per minute 20

Electrical Interference Electrostatic Discharge Test IEC 1000-4-2 Class 4 (8 kv) point contact discharge Fast Transient Disturbance Tests IEC 1000-4-4 Class 4 (4 kv, 2.5 khz) Surge Withstand Capability ANSI/IEEE 2,500 V pk-pk oscillatory applied to each independent circuit to earth C37.90.1 2,500 V pk-pk applied between each independent circuit 5,000 V pk Fast Transient applied to each independent circuit to earth 5,000 V pk Fast Transient applied between each independent circuit Radiated Susceptibility ANSI/IEEE 25-1000 Mhz @ 20 V/m C37.90.2 Atmospheric Environment IEC 68 2 1 Cold, 20 C for 96 hours IEC 68 2 2 Dry Heat, +70 C for 96 hours IEC 68 2 3 Damp Heat, +40 C @ 93% RH, for 96 hours Enclosure Protection NEMA 1, IEC IPC-65 21

PROTECTION RELAY PROCESSOR Field Ground Detection Squarewave Generator Signal Measurement and Processing 37 35 36 V out V f Rear Terminal Block Pin No. TB3 TB5 TB4 TB2 COUPLING NETWORK (M-3921) Shield Cable TB1 TB1 SUPPLY VOLTAGE Gen. Rotor Rf.Cf Ground/Machine Frame Brushes Shaft Ground Brush Figure 7 Typical Field Ground Connection Diagram 22

3.54 [9.0] 4.72 [11.99].18 DIA [0.46] 4 X 7.87 [19.99] M-3921 Field Ground Coupler BECKWITH ELECTRIC CO. INC. Made in U.S.A. 9.06 [23.01].18 DIA [0.46] 4 HOLES 3.54 [9.0] nnote: Dimensions in brackets are in centimeters. 7.40 [18.79] MOUNTING PATTERN WITHOUT TABS 2.96 REF [7.52] Figure 8 M 3921 Field Ground Coupler Mounting Dimensions 23

1998 Beckwith Electric Co. Printed in U.S.A. (10.16.02) 800 3425 SP 13MC7 08/15