SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection

Similar documents
GIC Neutral Blocking System Prototype to Production

Operational Experiences of an HV Transformer Neutral Blocking Device

Geomagnetic Disturbances. IEEE PES Chicago Chapter Technical Presentation March 12, Alan Engelmann Transmission Planning ComEd.

2013 Grid of the Future Symposium. Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765 kv Power Transformer Design

GMD Voltage Collapse Study

Power Grid Protection against Geomagnetic Disturbances (GMD)

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

Effects of GIC on Power Transformers and Power Systems

The Engineering Problem. Calculating GIC Flow through the EHV System

Modeling and Evaluation of Geomagnetic Storms in the Electric Power System

Model, Monitor & Mitigate Geomagnetically Induced Currents

Power System Impacts of Geomagnetic Disturbances

Evaluating Transformer Heating due to Geomagnetic Disturbances

Dietrich Bonmann, ABB AG Bad Honnef, March 15, Impact of GIC on transformers and the transmission network

Case Study Effects of Geomagnetically Induced Current (GIC) Neutral Blocking Device

IEEE PES/IAS Joint Chapter July Technical Presentation Meeting Basics of solar phenomena & How transformers react and handle events

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

Transformer Technology Seminar GIC Capability of Power Transformers

Power transformers. Shunt reactors Proven history for future success

AORC Technical meeting 2014

GMD Impacts on Generators

Fixed Series Compensation

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems

A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

PART 1 OWNER/APPLICANT INFORMATION

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

Detecting and Managing Geomagnetically Induced Currents With Relays

Three-phase monitoring relays CM-PVS.81

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Geo-Magnetic Disturbance Analysis of HV and EHV Grids

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation

Disturbances. Their Impact on the Power Grid. By the IEEE Power & Energy Society Technical Council Task Force on

Multimeter 500CVD21 RTU500 series

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

Three-phase monitoring relays CM-PVS CM-PVS.31, CM-PVS.41 and CM-PVS.81

Three-phase monitoring relay CM-PFS

Mil Std 461E CS-115 CS-115 MIL STD 461E CS-115 CS-116 RS-105

RTU560. Multimeter 560CVD03. Power Measuring Display. Characteristics. Application. Data Sheet Multimeter 560CVD03

Investigation of Geomagnetic Induced Current Effects on Power Transformer

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/

High-Level Harmonic Distortion During Geomagnetic Disturbances - a Hidden Threat to Grid Security

Data Isolation Cards. 2-Wire HDSL/56KBS Isolation Card P Wire HDSL/56KBS Isolation Card P30050

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

GIC Analysis using PSS E. K.V. PATIL Siemens Power Technologies International Schenectady, New York, USA

Low-Frequency Protection Concepts for the Electric Power Grid: Geomagnetically Induced Current (GIC) and E3 HEMP Mitigation

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

Grid Impact of Neutral Blocking for GIC Protection:

APPLICATION FOR INTERCONNECTION & OPERATIONS OF MEMBER-OWNED GENERATION

Inverter-Based Resource Disturbance Analysis

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

Interfacing Power System Simulators with Geomagnetically Induced Currents (GIC) Simulation Programs. Luis Marti Hydro One, Canada

Three-phase monitoring relay CM-PVE

2012 Grid of the Future Symposium. Geomagnetic Disturbance Impacts and AEP GIC/Harmonics Monitoring System

Low Pass Harmonic Filters

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT

Effect of Geomagnetically Induced Currents on Protection Systems

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Three-phase monitoring relays CM-PFE and CM-PFE.2

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

WORLD LEADING PRODUCTS FOR LASER SCIENTISTS AND ENGINEERS

APPENDIX B: Generation Interconnection Application Form

Wind Power Facility Technical Requirements CHANGE HISTORY

Technical Interconnection Requirements For Transmission Voltage Customers for Service at 60,000 to 287,000 Volts R XX

Vulnerability Assessment and Planning

Impact of Solar Storms on the Swiss Transmission Network

TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

Current monitoring relays CM-SRS.1 For single-phase AC/DC currents

Stabilized Differential Relay SPAD 346. Product Guide

RAP Ripple Control Coupling for parallel injection of RC signals in Medium and High Voltage Networks

Electronic timer CT-WBS.22 Impulse generating and flashing with 2 c/o (SPDT) contacts

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

HVDC High Voltage Direct Current

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Pinhook 500kV Transformer Neutral CT Saturation

MidAmerican Energy Company Reliability Planning Criteria for 100 kv and Above

Coupling unit CM-IVN For expansion of the insulation monitoring relay CM-IWN.x measuring range up to U n = 690 V AC and 1000 V DC

Liquid level monitoring relay CM-ENS.2x

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Copyright 2008 IEEE.

Active Harmonic Filters IPC150 AHF Series

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23

Current Probes. User Manual

Transformer Thermal Impact Assessment White Paper Project (Geomagnetic Disturbance Mitigation)

The Polytransformer. The Multivoltage Substation Power Transformer

Current monitoring relays CM-SRS.M1 For single-phase AC/DC currents

E N G I N E E R I N G M A N U A L

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Transcription:

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection

SolidGround TM GIC grid stability and harmonics mitigation system The SolidGround system automatically blocks DC currents from flowing in the neutrals of large power transformers. The system protects the grid against effects of solar storm Geomagnetic Induced Currents (GIC) and Electromagnetic Pulse (EMP) induced currents. Grid voltage collapse and component damage can occur during modest to severe solar storms. SolidGround TM installations will prevent this collapse and eliminate damage to power system components and customer equipment. New insurance studies show that even low level solar storms cause damage to customer equipment of billions of dollars per year. SolidGound TM mitigates the effect of even these low level disturbances. SolidGround TM as a GIC grid stability and harmonics mitigation system Various solutions to remediate ground currents in HV and EHV transformer neutrals have been examined over several decades. All such solutions have the disadvantage of modifying the transformer neutral grounding impedance which in turn modifies operating conditions, relay settings, and system reliability. The SolidGround TM system grounds the transformer at all times. Under all operating conditions, the presence of GIC protection is completely transparent to grid operations as the transformer neutral has a complete metallic path to the ground when in its Solid Ground mode, and a very low AC impedance path to ground when in its GIC protective mode. In addition, blocking transformer neutral GIC currents also prevents the generation of induced power line harmonics and power quality issues which can damage both power system components as well as customer equipment. 2 SolidGround TM grid stability and harmonics mitigation system

Protecting the grid against GIC and EMP currents ABB is proud to offer the SolidGround TM for grid protection against geomagnetic induced currents. Application The SolidGround TM automatically senses the presence of GIC or induced harmonics, triggering the protective mode with AC grounding through a low impedance capacitor bank. This level of protection prevents: - Transformer half wave saturation - Generation of harmonics on power lines - Unwanted extreme Reactive (MVAR) flows - Power grid instability - Thermal damage to transformers and SVCs - Harmonic damage to generator rotors Additionally, the system provides a metallic ground path which grounds a transformer neutral when geomagnetic induced currents (GIC) are not present 99.8% of the time. Transformer application Transformer configuration Two winding or Auto Neutral of single or 3-phase transformers Transformer rating kv (rms) 115 to 765 Neutral quasi DC current attenuation Neutral GIC current sensing trigger GIC induced harmonic (THD) sensing trigger db Amperes, selectable > 40 db below 0.6 Hz 6 to 100 (selectable) %, selectable 1 to 10 (selectable) Input power Volts 125 DC GIC: Geomagnetic Induced Current THD: Total Harmonic Distortion EMP: Electromagnetic Pulse IEMI: Intentional Electromagnetic Interference Benefits of ABB s advanced technology The system is designed to work on HV and EHV class transformers The system has been extensively studied and modeled by the University of Manitoba The system has been fully fault tested at KEMA High Current and Voltage Laboratories in Pennsylvania The US Government has sponsored testing in a live power grid at the Idaho National Laboratory SEL control electronics provide SolidGround TM breaker controls, monitoring functions and communications with SCADA systems The system offers triple redundant fault protection when in the GIC protective mode, providing: - DuraGap TM spark gap voltage protection - Breaker reclose if spark gap should fire The system is engineered and shipped pre-assembled from the factory, minimizing installation cost and effort. Typical installations involve concrete piers, the bolting of extension legs, completing the electrical connections, and commissioning. SolidGround TM offers financial operating advantages One means of managing the effects of GIC is to free-up capacity on long transmission lines. GIC flowing through HV transformer cores can cause large reactive power (VAR) demands when GMDs impact the earth. To make available more VARs during solar storm periods, utilities back down generation of base load (less expensive) and start up peaking (more expensive) generation. This temporary approach allows utilities to provide the same levels of service to end-users; but at a higher cost. Instead, the utilities could effectively block the GIC from entering the transformer core by implementing an ABB SolidGround TM solution. Blocking GIC means reduced GIC effects in the system which means uneconomic dispatch can be avoided. In this scenario, SolidGround TM will offer a very compelling financial benefit. Additionally, SolidGround TM prevents GIC induced harmonics/ power quality issues which can damage utility and customer equipment. By blocking GIC currents, damage caused by harmonics is avoided. SolidGround TM grid stability and harmonics mitigation system 3

Operation Sequence of operations The breaker assembly is comprised of two separate breakers: a DC disconnect breaker and an AC vacuum breaker. The DC breaker is designed to break DC and quasi-dc currents. The AC breaker has a high voltage stand-off that is opened second and protects the DC breaker. When a flow of GIC is detected, the control electronics opens the breaker assembly. Once both the breakers are opened, the DC disconnect breaker is reclosed but the AC breaker remains open until the control electronics sense that the GIC event is over. The unit then automatically closes the AC breaker and the system is then ready for the next GIC event. When the AC break is open the system is in the GIC protective mode and the capacitor bank blocks the neutral quasi-dc currents in the transformer while providing a continuous AC ground connection. A low impedance, high power series resistor is utilized to effectively damp neutral voltage transients. In the unlikely event that a ground fault should occur while in the GIC protection mode, a spark gap provides a grounding path to protect the transformer. If fault current through the spark gap is detected the AC breaker is reclosed to handle any repeated ground fault current events. As back-up protection, a triple spark gap provides a grounding path for faults. If current through the spark gap is detected a relay is used to reclose the AC breaker which takes the SolidGround TM system out of the GIC protection mode and places it into its normal SolidGround TM operational mode. Since the system will operate in its normal mode of operation (i.e. breaker assembly closed ) most of the time (99.8% of the time), a SCADA system can be used to perform self-testing of SolidGround TM on a predetermined schedule e.g. once every month or once every week, to ensure all the components and the system continue to be operational. 4 SolidGround TM grid stability and harmonics mitigation system

Features Triple DuraGap TM spark gap protection A triple spark gap assembly provides transformer and system protection in the unlikely event of a simultaneous ground fault while the system is in its GIC protection mode. This spark gap assembly has been extensively tested at the KEMA laboratories in Pennsylvania and shown to provide highly redundant fault protection suitable for large numbers of faults. Power resistor A 50 kwatt, one (1) ohm power resistor effectively dampens neutral and phase transients while the system is in the GIC protection mode. Maintenance/bypass switch Maintenance/bypass switch is provided with Kirk Key Interlock, so the transformer ground connection is in place at all times. Capacitor bank During a GIC event, the capacitor bank effectively blocks the quasi-dc GIC currents in the transformer neutral while providing a continuous AC transformer grounding path. The standard SolidGround TM system comes with two series connected capacitor banks to provide full EMP stand-off voltage (8 kv) protection. Sensing and control electronics Electronics continuously monitor and measure for both DC currents and GIC induced harmonics. User settable thresholds allow for site-specific customization. System can be operated in automatic or manual modes. Shielding protection can be provided for IEMI and EMP E 1 as desired. AC and DC breaker Upon sensing either a quasi DC GIC current or phase harmonics, the system DC and AC breakers are automatically opened to leave the transformer grounded through the power resistor and capacitor bank, maintaining a continuous effective grounding path while blocking the quasi DC GIC currents. These breakers are highly reliable industry proven components used in numerous power equipment applications. Transformer neutral conductivity monitor An unique monitoring feature has been incorporated into the SolidGround TM system. A conductivity monitor now continuously assures operators that the neutral grounding connection has not been compromised. SolidGround TM grid stability and harmonics mitigation system 5

Testing and conclusions Live power grid testing The system was tested at the KEMA high current testing facility in Chalfont, PA proving the robustness of the design and its readiness for live power grid testing. SolidGround TM was then inserted in live grid testing sponsored by the US Defense Threat Reduction Agency (DTRA). A snap shot of some of the data collected is shown in the adjacent figure. The system operated successfully in the live power grid under all testing scenarios conducted. No neutral blocking unintended consequences A question regarding the potential for neutral blocking to cause unintended power grid consequences has been raised by some individuals in the power industry. A NERC sponsored study performed by the Electric Power Research Institute (EPRI) in 2014 concluded that the SolidGround TM has no unintended consequences when introduced into a typical power grid network. The report is available to the public and can be found on the EPRI web site. KEMA high ground fault current testing GIC Protection Switched On GIC Currents without Neutral Blocking Injected DC Currents GIC Detection at 6 Amps 0.7 Sec Time Delay 1.7 Second Time Delay SolidGround TM testing results at the Idaho National Laboratories 6 SolidGround TM grid stability and harmonics mitigation system

Drawings and dimensions Physical data Dimensions and weights Height of upper equipment platform 9 10 Height of platform extension legs 2 4 Overall assembled height 12 2 Width of platform 7 9 Length of platform 7 9 Length of optional disconnect switches 3 8 Overall length with disconnect switches 11 5 Shipping weight (lbs) 8,200 Minimum height to unguarded parts 9 0 Left Right Front Rear SolidGround TM grid stability and harmonics mitigation system 7

Contact us ABB Inc. High Voltage Products - Dead Tank Breakers 100 Distribution Circle Mount Pleasant, Pennsylvania 15666, USA Phone: +1 (724) 696-1500 Fax: +1 (724) 696-1502 www.abb.us/highvoltage Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction in whole or in parts is forbidden without ABB s prior written consent. Copyright 2015 ABB. All rights reserved. Document Number: 2GNM110098 / February 2015