Bauart gepruft Sicherheit egelma ge od o s be wac g www. tuv.com ID 00000000 240W Constant Voltage Constant Current LED Driver IP65 IP67 Metal housing with class I design Ⅰ current output. HLG240H operates from 90~305VAC and offers models with different rated voltage ranging between 12V and 54V. Thanks to the high efficiency up to 93.5%, with the fanless design, the entire series is able to operate for 40 ~ 90 case temperature under free air convection. The design of metal housing and IP67/IP65 ingress protection level allows this series to fit both indoor and outdoor applications. HLG240H is equipped with various function options, such as dimming methodologies, so as to provide the optimal design flexibility for LED lighting system. I I B C D File Name:HLG240HSPEC 161025
SPECIFICATION MODEL HLG240H12 HLG240H15 HLG240H HLG240H24 HLG240H30 HLG240H36 HLG240H42 HLG240H48 HLG240H54 DC VOLTAGE 12V 15V V 24V 30V 36V 42V 48V 54V CONSTANT CURRENT REGION Note.4 6 ~12V 7.5 ~ 15V 10 ~ V 12 ~ 24V 15 ~ 30V 18 ~ 36V 21 ~ 42V 24 ~ 48V 27 ~ 54V RATED CURRENT RATED POWER 16A 192W 15A 225W 12A 240W 10A 240W 8A 240W 6.7A 241.2W 5.72A 240.24W 5A 240W 4.45A 240.3W RIPPLE & NOISE (max.) Note.2 150mVpp 150mVpp 150mVpp 150mVpp 0mVpp 250mVpp 250mVpp 250mVpp 350mVpp OUTPUT VOLTAGE ADJ. RANGE Adjustable for A/CType only (via builtin potentiometer) 11.2 ~ 12.8V 14 ~ 16V 18.6 ~ 21.4V 22.4 ~ 25.6V 28 ~ 32V 33.5 ~ 38.5V 39 ~ 45V 44.8 ~ 51.2V 50 ~ 57V CURRENT ADJ. RANGE Adjustable for A/CType only (via builtin potentiometer) 8 ~ 16A 7.5 ~ 15A 6 ~ 12A 5 ~ 10A 4 ~ 8A 3.3 ~ 6.7A 2.86 ~ 5.72A 2.5 ~ 5A 2.23 ~ 4.45A VOLTAGE TOLERANCE Note.3 ±2.5% ±2.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% LINE REGULATION LOAD REGULATION ±2.0% ±1.5% ±1.0% SETUP, RISE TIME Note.6 1000ms,80ms/115VAC 500ms,80ms/230VAC HOLD UP TIME (Typ.) 15ms / 115VAC, 230VAC VOLTAGE RANGE Note.5 90 ~ 305VAC 127 ~ 431VDC (Please refer to "STATIC CHARACTERISTIC" section) FREQUENCY RANGE POWER FACTOR (Typ.) 47 ~ 63Hz PF 0.98/115VAC, PF 0.95/230VAC @ full load (Please refer to " POWER FACTOR (PF) CHARACTERISTIC" section) THD< % (@ load 50% / 115VAC,230VAC; @ load 75% / 277VAC) TOTAL HARMONIC DISTORTION INPUT (Please refer to " TOTAL HARMONIC DISTORTION (THD)" section) EFFICIENCY (Typ.) 90% 90% 91.5% 92.5% 92.5% 92.5% 92.5% 93% 93.5% AC CURRENT (Typ.) 4A / 115VAC 2A / 230VAC 1.2A / 277VAC INRUSH CURRENT (Typ.) MAX. No. of PSUs on 16A CIRCUIT BREAKER COLD START 75A(t width=570 μs measured at 50% I peak) at 230VAC; Per NEMA 410 2 units (circuit breaker of type B) / 4 units (circuit breaker of type C) at 230VAC LEAKAGE CURRENT <0.75mA / 277VAC OVER CURRENT 95 ~ 108% Constant current limiting, recovers automatically after fault condition is removed SHORT CIRCUIT Hiccup mode, recovers automatically after fault condition is removed PROTECTION 13.5 ~ 18V 17.5 ~ 21.5V 23.5 ~ 27.5V 27 ~ 34V 33 ~ 39V OVER VOLTAGE Shut down and latch off o/p voltage, repower on to recover 43 ~ 49V 48 ~ 54V 55 ~ 63V 60 ~ 67V OVER TEMPERATURE Shut down o/p voltage, recovers automatically after temperature goes down WORKING TEMP. Tcase= 40 ~ 90 (Please refer to "OUTPUT LOAD vs TEMPERATURE" section) MAX. CASE TEMP. Tcase= 90 ENVIRONMENT WORKING HUMIDITY ~ 95% RH noncondensing STORAGE TEMP., HUMIDITY 40 ~ 80, 10 ~ 95% RH TEMP. COEFFICIENT VIBRATION ± 0.03%/ (0 ~ 50 ) 10 ~ 500Hz, 5G 12min./1cycle, period for 72min. each along X, Y, Z axes SAFETY STANDARDS Note.8 UL1012, CAN/CSAC22.2 No. 107.101, UL8750(type HL ), CSA C22.2 No. 250.008; TUV EN613471, EN61347213 independent (except for HLG240H C type); UL609501, UL8750, TUV EN609501; IP65 or IP67; J613471, J61347213 approved SAFETY & WITHSTAND VOLTAGE I/PO/P:3.75KVAC I/PFG:2KVAC O/PFG:1.5KVAC EMC ISOLATION RESISTANCE I/PO/P, I/PFG, O/PFG:100M Ohms / 500VDC / 25 / 70% RH OTHERS NOTE EMC EMISSION Note.8 Compliance to EN55015, EN55022 (CISPR22) Class B, EN6100032 Class C (@ load 50% ) ; EN6100033 EMC IMMUNITY Compliance to EN6100042,3,4,5,6,8,11, EN61547, EN55024, light industry level ( surge immunity LineEarth 4KV, LineLine 2KV) MTBF 7.9K hrs min. MILHDBK217F (25 ) DIMENSION 244.2*68*38.8mm (L*W*H)(HLG240HBlank/A/B) 251*68*38.8mm (L*W*H)(HLG240H CType) PACKING 1.3Kg; 12pcs/16.6Kg/0.84CUFT(HLG240Blank/A/B) 1.23Kg; 12pcs/15.8Kg/1.16CUFT(HLG240 C Type) File Name:HLG240HSPEC 161025
BLOCK DIAGRAM Fosc : 100KHz I/P FG EMI FILTER & RECTIFIERS PFC CIRCUIT PFC CONTROL O.L.P. POWER SWITCHING PWM & PFC CONTROL RECTIFIERS & FILTER O.L.P. DETECTION CIRCUIT O.V.P. V V DIM DIM (B Type) DRIVING METHODS OF LED MODULE This series is able to work in either Constant Current mode (a direct drive way) or Constant Voltage mode (usually through additional DC/DC driver) to drive the LEDs. 100 In the constant current region, the highest voltage at the output of the driver depends on the configuration of the end systems. Vo(%) (A) Constant Voltage area (B) Constant Current area Should there be any compatibility issues, please contact MEAN WELL. 50 (min.) (C) Hiccup Protection 50 100 Io (%) Typical output current normalized by rated current (%) File Name:HLG240HSPEC 161025
DIMMING OPERATION FG (Green/Yellow) AC/L(Brown) AC/N(Blue) HLG240H V(Black) V(Red) DIM(Blue) DIM(White) 3 in 1 dimming function (for BType) Output constant current level can be adjusted by applying one of the three methodologies between DIM and DIM: 1 ~ 10VDC, or 10V PWM signal or resistance. Direct connecting to LEDs is suggested. It is not suitable to be used with additional drivers. Dimming source current from power supply: 100μA (typ.) Applying additive 1 ~ 10VDC V V DIM DO NOT connect "DIM to V" Additive Voltage Output current (%) 100% 90% 80% 70% 60% 50% 40% 30% % 10% 1V 2V 3V 4V 5V 6V 7V 8V 9V 10V Dimming input: Additive voltage DIM Applying additive 10V PWM signal (frequency range 100Hz ~ 3KHz): V V DIM Additive PWM signal DIM DO NOT connect "DIM to V" Output current (%) 100% 90% 80% 70% 60% 50% 40% 30% % 10% 10% % 30% 40% 50% 60% 70% 80% 90% 100% Duty cycle of additive 10V PWM signal dimming input Applying additive resistance: V V DIM DIM Additive Resistance Output current (%) 100% 90% 80% 70% 60% 50% 40% 30% DO NOT connect "DIM to V" % 10% 10K/N K/N 30K/N 40K/N 50K/N 60K/N 70K/N 80K/N 90K/N 100K/N (N=driver quantity for synchronized dimming operation) Dimming input: Additive resistance File Name:HLG240HSPEC 161025
Note: In the case of turning the lighting fixture down to 0% brightness, please refer to the configuration as follow, or please contact MEAN WELL for other options. N FG L Relay Switch Adjuster 10K/N~100K/N Ohms resistance 1~10V DC Voltage 10V PWM Signal Green/ Yellow Brown Blue AC/L AC/N HLG240H BType DIM DIM V() V() Blue White Black Red LED Lighting Fixture Using a switch and relay can turn ON/OFF the lighting fixture. File Name:HLG240HSPEC 161025
OUTPUT LOAD vs TEMPERATURE 100 230VAC 100 80 80 60 100VAC 60 LOAD (%) 40 LOAD (%) 40 40 25 10 0 15 30 50 60 70 (HORIZONTAL) 40 25 0 45 55 65 75 90 (HORIZONTAL) AMBIENT TEMPERATURE,Ta ( ) Tcase ( ) STATIC CHARACTERISTICS POWER FACTOR(PF) CHARACTERISTIC Tcase at 80 100 Constant Current Mode LOAD (%) 90 80 70 60 50 40 90 100 125 135 145 155 165 175 180 0 230 305 INPUT VOLTAGE (V) 60Hz PF 1.00 0.98 0.96 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 0.78 50% 60% 70% 80% 90% 100% 277Vac 230Vac 115Vac (240W) LOAD Derating is needed under low input voltage. TOTAL HARMONIC DISTORTION (THD) 48V Model, Tcase at 80 14 EFFICIENCY vs LOAD possess superior working efficiency that up to 93.5% can be reached in field applications. 48V Model, Tcase at 80 96 12 92 THD(%) 10 8 6 4 277VAC 230VAC 115VAC EFFICIENCY (%) 88 84 80 277Vac 230Vac 115Vac 2 76 0 50% 60% 70% 80% 90% 100% 72 10% % 30% 40% 50% 60% 70% 80% 90% 100% LOAD LOAD File Name:HLG240HSPEC 161025
LIFETIME 1 100 80 LIFETIME(Kh) 60 40 0 30 40 50 60 70 80 90 Tc a s e ( ) File Name:HLG240HSPEC 161025
MECHANICAL SPECIFICATION Case No.994C Unit:mm Blank/DType 12 9.6 244.2 2.2 FG (Green/Yellow) AC/L(Brown) AC/N(Blue) AType FG (Green/Yellow) AC/L(Brown) AC/N(Blue) SJTW 18AWG 3C SJTW 18AWG 3C 12 9.6 9.4 34.2 9.4 9.4 34.2 9.4 68 68 Tcase 34 tc : Max. Case Temperature tc 244.2 2.2 Tcase 34 tc : Max. Case Temperature tc 110.1 110.1 Vo ADJ. Io ADJ. SJTW 14AWG 2C ψ 4.2 4PL SJTW 14AWG 2C ψ 4.2 4PL V(Black) V(Red) 38.8 38.8 V(Black) V(Red) BType 244.2 12 2.2 FG (Green/Yellow) AC/L(Brown) AC/N(Blue) SJTW 18AWG 3C 9.6 9.4 34.2 9.4 68 Tcase tc 34 110.1 V(Black) V(Red) DIM(Blue) DIM(White) 38.8 SJTW 14AWG 2C SJTW 18AWG 2C ψ 4.2 4PL tc : Max. Case Temperature File Name:HLG240HSPEC 161025
CType 15.4 8 251 2.2 8 I/P 7.5 9.5 1 2 3 37 68 8 Tcase tc 34 110.1 Vo ADJ. 1 2 Io ADJ. O/P 38.8 ψ 4.2 4PL tc : Max. Case Temperature AC Input Terminal Pin No. Assignment DC Output Terminal Pin No. Assignment Pin No. Assignment Pin No. Assignment 1 FG 1 V 2 AC/L 2 V 3 AC/N File Name:HLG240HSPEC 161025
WATERPROOF CONNECTION Waterproof connector Waterproof connector can be assembled on the output cable of HLG240H to operate in dry/wet/damp or outdoor environment. AC source I/P HLG240H O/P Size Pin Configuration (Female) Size Pin Configuration (Female) M12 Order No. Suitable Current 4PIN 5A/PIN M1204 10A max. 5PIN 5A/PIN M1205 10A max. M15 Order No. Suitable Current 2PIN 12A/PIN M1502 12A max. LED Lamp Cable Joiner 66 26 CJ041 suitable for 14AWG~16AWG CJ042 suitable for 18AWG~22AWG ψ25 Up to four wires can be connected through this cable joiner by soldering or clamping by tools. LED Lamp HLG240H O/P Wires CJ04 cable joiner can be purchased independently for user's own assembly. MEAN WELL order No. : CJ041, CJ042. Junction Box Option 2.2 382.2 76 10 5 FG (Green/Yellow) AC/L(Brown) AC/N(Blue) SJTW 18AWG 3C 68 61 8.5 32 8.5 6 V(Black) V(Red) 2ψ5 3 PF 1/2" 150± 35 38.8 SJTW 14AWG 2C 3 PF 1/2" 150± Junction box option is available for A / Blank Type. Please contact MEAW WELL for details. 86 INSTALLATION MANUAL Please refer to : http://www.meanwell.com/manual.html File Name:HLG240HSPEC 161025