POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

Similar documents
POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

Southern Company Power Quality Policy

1C.4.1 Harmonic Distortion

Harmonic Distortion Evaluations

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

POWER QUALITY AND SAFETY

ELECTRICITY ASSOCIATION SERVICES LIMITED 2001

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

Roadmap For Power Quality Standards Development

Emission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System

IEEE sion/1547revision_index.html

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08

Table of Contents. Introduction... 1

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction

Power Quality Requirements for Connection to the Transmission System

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

Harmonic Requirements

Harmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients.

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

Grid Converters for Photovoltaic

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

POWER QUALITY REPORT

Final ballot January BOT adoption February 2015

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC

Harmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry

Do You Have a Harmonic Problem?

Prepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA

MidAmerican Energy Company Reliability Planning Criteria for 100 kv and Above

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

IEEE sion/1547revision_index.html

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

ECE 528 Understanding Power Quality

16B2011B1 EASY HARMONICS USER MANUAL

Power Quality and Harmonic :Causes and Effects with Paper Mill Factory

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Effects of Harmonic Distortion I

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Embedded Generation Connection Application Form

Harmonic Filters for Single Phase Equipment

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard

Wind Power Facility Technical Requirements CHANGE HISTORY

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

Southern Company Interconnection Requirements for Inverter-Based Generation

RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana

Effective Harmonic Mitigation with Active Filters

Connection Impact Assessment Application Form

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

Economical Solutions to Meet Harmonic Distortion Limits[4]

Interharmonic Task Force Working Document

Technical Interconnection Requirements For Transmission Voltage Customers for Service at 60,000 to 287,000 Volts R XX

Impact Assessment Generator Form

BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP

Contents. All Rights Reserved

Company Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes

An Introduction to Power Quality

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Embedded Generation Connection Application Form

Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System

Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

Power quality report. A Manufacturing Plant

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

THE HISTORY OF FLICKER LIMITS

ATTACHMENT - AESO FUNCTIONAL SPECIFICATION

METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE

Power Quality Summary

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Functional Specification Revision History

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Harmonic Planning Levels for Australian Distribution Systems

Power Quality in High Density Residential Distribution Grids

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Distribution Network Capacitor Resonance A Case Study

Company Directive POLICY DOCUMENT: SD4/7. Relating to 11kV and 6.6kV System Design

HARMONIC MITIGATIONCASE STUDY

GMD Voltage Collapse Study

Power Quality Basics. Presented by. Scott Peele PE

PRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Harmonic control devices. ECE 528 Understanding Power Quality

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

Harmonic Distortion Levels Measured at The Enmax Substations

IMPLICATIONS OF APPLYING DIFFERENT VAR SUPPORT TECHNOLOGIES IN THE ESKOM TRANSMISSION NETWORK WITH PARTICULAR EMPHASIS ON THE LIFECYCLE COST

Guide for Conducting a Stray Voltage Evaluation Under the MPSC Stray Voltage Rule 1

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY

T-68 Protecting Your Equipment through Power Quality Solutions

Transmission Interconnection Requirements for Inverter-Based Generation

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

Power Quality Survey in a Distribution System, Standard Procedures and Limitations. H. Mokhtari S. Hasani and M. Masoudi

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Transcription:

POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719

1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION MEAN DT ue to the increase in harmonic loads, utilities across Canada are implementing power quality limits to protect customer and utility equipment. The purpose of this document is to explain the harmonic limits and voltage flicker limits the customer must meet, the commissioning process for the specification, and the procedure that takes place to mitigate customer complaints. The limits that are described in this document reflect industry standards. 1.2 ADHERING TO THE GUIDELINES To maintain a high quality of electrical utility service, all new customers and all existing customers connected to the ENMAX power system are required to adhere to the specifications and guidelines in this document. If a customer exceeds these limits it is probable that the customer will have to be disconnected from the ENMAX power system. The conditions that determine whether a customer will be connected are listed below. The criterion for stage 1 and stage 2 are outlined in Section 3. ENMAX Power will be able to connect the customer if the customer has: completed all steps in stage one. completed all steps in stage two. does not produce harmonics and does not have to be evaluated under any of the stages of acceptance. The customer cannot be connected to the power system if the customer has been: rejected under any of the stages. 1-1

1 GENERAL OVERVIEW 1.3 What is the Connection process? A customer may be disconnected from the power system if: the customer exceeds the limits described in the specifications; and other customers and/or utility equipment is being adversely affected. 1.3 WHAT IS THE CONNECTION PROCESS? Found below is a brief description of the stages of the process that harmonic producing customers must follow in order to be connected to the ENMAX power system. A detailed description of this process is found in Section 3. Step 1: Step 2: Step 3: Step 4: Step 5: Step 6: Step 7: A new customer, consultant, or Energy Service Provider contacts a Planner at ENMAX Power for connection of a new service or an upgrade. The planner gives the customer, consultant, or Energy Service Provider the power quality specifications and informs the engineer that a customer has been given the document. The engineer contacts the customer and the two parties discuss the customer s operation and the specifications. If required, the engineer administers the specifications. The customer submits a report which demonstrates that it will adhere to the specifications. The engineer reviews the report and confirms all electrical utility standards are met. The customer is connected to the power system. 1-2

2 POWER QUALITY LIMITS........................................ 2.1 HARMONIC CURRENT DISTORTION LIMITS All of the ENMAX customers that are connected to the ENMAX Power distribution and network systems are responsible for complying with the harmonic current limits, at the point of common coupling, that have been stipulated by ENMAX Power Corporation. The current harmonics created by the customer cannot exceed the limits that are outlined in Tables 2.1 and 2.2, at the point of common connection (PCC). These limits are applied to each phase current individually and are expressed as a percentage of the customer s maximum demand load current. Table 2.1 Harmonic Current Distortion Limits 69kV and Below I SC /I L h < 11 11 h < 17 17 h < 23 23 h < 35 35 h THD <20 4.0 2.0 1.5 0.6 0.3 5.0 20-50 7.0 3.5 2.5 1.0 0.5 8.0 50-100 10.0 4.5 4.0 1.5 0.7 12.0 100-1000 12.0 5.5 5.0 2.0 1.0 15.0 > 1000 15.0 7.0 6.0 2.5 1.4 20.0 1 See Section 4 for explanations of the symbols. 2 The symbol h is for odd harmonics only. 3 Triplen harmonics are limited to 1/3 of the limits for odd-order harmonics. 4 All power generation equipment applications are limited to these values of current distortion regardless of the actual short circuit ratio I SC /I L. 2-3

2 POWER QUALITY LIMITS 2.2 Harmonic Voltage Distortion Limits Table 2.2 Harmonic Current Distortion Limits I SC /I L 138kV h < 11 11 h < 17 17 h < 23 23 h < 35 35 h THD <20 See note 4 2.0 1.0 0.75 0.3 0.15 2.5 20-50 3.5 1.75 1.25 0.5 0.25 4.0 50-100 5.0 2.25 2.0 1.25 0.35 6.0 100-1000 6.0 2.75 2.5 1.0 0.5 7.5 > 1000 7.5 3.5 3.0 1.25 0.7 10.0 All of the information found in the notes below Table 2.1 also pertain to Table 2.2 2.2 HARMONIC VOLTAGE DISTORTION LIMITS ENMAX Power has the responsibility to supply voltage at the PCC that does not exceed the distortion limits listed in the table below. Table 2.3 Harmonic Voltage Distortion Limits Bus Voltage at PCC (V n ) Voltage IHD (%) Voltage THD (%) V n 69kV 3.0 5.0 138kV 1.5 2.5 The above information, as with all information found in this document, should be verified with ENMAX Power Corporation. 2-4 Power Quality Specifications and Guidelines for Customers

POWER QUALITY LIMITS 2.3 Short Duration Harmonic Limits..... 2.3 SHORT DURATION HARMONIC LIMITS The harmonic limits listed in the tables in Sections 2.1 and 2.2 refer to steady state conditions. However, due to the time-varying nature of harmonics and certain facility operations, such as start-up, harmonics may exceed the limits given in the previously mentioned tables. The table below shows the acceptable limits for harmonic bursts. Table 2.4 Short Duration Voltage and Current Harmonic Levels Acceptable Harmonic Distortion Levels (THD and IHD) Maximum Duration of a Single Harmonic Burst in a 24 Hour Period (T maximum ) Total Duration of All Harmonic Bursts in a 24 Hour Period (T total ) 3.0 X Steady State Limit 1 sec. < T maximum < 5 sec 15 sec. < T total < 60 sec. 2.0 X Steady State Limit 5 sec. < T maximum < 10 min. 60 sec. < T total < 40 min. 1.5 X Steady State Limit 10 min. < T maximum < 30 min. 40 min. < T total < 120 min. 1.0 X Steady State Limit 30 min. < T maximum 120 min. < T total The limits mentioned in the table above are allowed only if the other customers are not adversely affected by the harmonic bursts. 2.4 EVALUATING CONCERNS FOR HARMONIC FILTERS AND POWER FACTOR CORRECTION Power factor correction capacitors and harmonic filters at customer facilities may absorb harmonic currents from the system or magnify harmonic currents created by the customer load equipment. These installations should be coordinated with ENMAX Power. Section 2 Power Quality Limits 2-5

2 POWER QUALITY LIMITS 2.5 Flicker Limits for Motor Starting and Cyclical Loads It is not the purpose of these guidelines to penalize customers for harmonic currents that are absorbed from the power system. More detailed evaluation is necessary to assess the impact of a customer that is applying either harmonic filters or power factor correction capacitors. Please note that the harmonic filters or power factor correction capacitors applied in customer facilities should be designed assuming background voltage distortion levels as specified in Table 2.3 2.5 FLICKER LIMITS FOR MOTOR STARTING AND CYCLICAL LOADS The voltage flicker limits for customers connected to the ENMAX power system are shown in the figure below. In the case where there is a single customer on a transformer, the voltage fluctuations may not exceed the limits in Figure 2.1 on the utility side of the transformer. If there is more than one customer connected to a transformer, the voltage fluctuations may not exceed the limits found in Figure 2.1 on the customer side of the transformer. Voltage Flicker Limits 6 5.0 5 4.2 Voltage Change (120V) 4 3 2 3.3 2.5 1.7 Voltage Change (%) 1 0.8 0 0 6 12 18 24 6 12 18 24 30 36 42 48 54 60 6 12 18 24 30 36 42 48 54 60 0.0 Per Day Per Hour Per Minute Per Sec Figure 2.1Voltage Flicker Limits Rate of Flicker 2-6 Power Quality Specifications and Guidelines for Customers

POWER QUALITY LIMITS 2.6 General Flicker Limits..... 2.6 GENERAL FLICKER LIMITS Customers that have loads with random fluctuation characteristics will be evaluated according to the procedures in IEC 1000-4-15. The weighting curves for 60Hz, 120 volt systems will be used. A customer with fluctuating loads should not result in Pst value exceeding 1.0 at the 99% probability level recorded during an interval of at least one week. Section 2 Power Quality Limits 2-7

2 POWER QUALITY LIMITS 2.6 General Flicker Limits 2-8 Power Quality Specifications and Guidelines for Customers

COMMISSIONING PROCESS & GUIDELINES 3........................................ 3.0 CRITERIA FOR STAGED ACCEPTANCE OF NEW INSTALLATION OA nly harmonic-producing customers are required to be evaluated under staged acceptance. The commissioning process for applying the Power Quality Specifications is a cooperative effort between the customer and the utility. Each party will provide the relevant information necessary to determine the impact on the power system. Refer to Figure 3.2 for the commissioning process and Figure 3.3 for the staged acceptance process. 3.1 STAGE 1 - AUTOMATIC ACCEPTANCE Customers that have a small amount of harmonic load may be allowed to connect to the system without detailed evaluation. In order to be automatically accepted the customer must satisfy the following two criteria. Criterion 1: The first requirement is that the customer shall satisfy S Dw / S SC < 0.1% S Dw is the amount of weighted disturbing load within the customer s facility and is calculated by using the following: Where: S Dw = ( SDi Wi ) S Di = power rating for an individual disturbing load (kva) W i = weighting factor for the disturbing load (pu) S SC = actual three phase short capacity at the PCC The weighting factors for various types of loads are given in Figure 3.1. If the type of load is unknown, a weighting factor of 1.0 should be used. 3-9

3 COMMISSIONING PROCESS & GUIDELINES 3.2 Stage 2 - Evaluation of Harmonic Emissions Criterion 2: The second requirement is the customer s capacitors cannot cause a harmonic resonance. The parallel resonant frequency, h r, only needs to be checked out for the two harmonic orders that are adjacent to h r. The following equation may be used to calculate h r, if all capacitors are connected to the same busbar. h r = ( MVA sc ) ( MVARcap ) Since MVA sc and MVAR cap may change with loading, this criterion must satisfy all system conditions. 3.2 STAGE 2 - EVALUATION OF HARMONIC EMISSIONS In order to be accepted at Stage 2, the customer must adhere to the ENMAX Power Harmonic Specification by performing a detailed harmonic analysis and submitting a report to ENMAX Power. If the harmonic distortion exceeds the limits in the specification, then the customer must install harmonic control equipment to remedy the situation. 3.3 INFORMATION REQUIREMENTS Table 3.1 Responsibilities to Supply Information Customer will supply the following information ENMAX will supply information pertaining to A single line diagram, a list of linear load and nonlinear loads, a list of transformers, and a list of capacitors and filters PCC location, fault current at PCC, and supply system impedance. 3-10 Power Quality Specifications and Guidelines for Customers

COMMISSIONING PROCESS & GUIDELINES 3.4 Weighting Factors for Different Types of Harmonic Producing Loads..... 3.4 WEIGHTING FACTORS FOR DIFFERENT TYPES OF HARMONIC PRODUCING LOADS The following figure shows various weighting factors. Figure 3.1 Weighting Factors Section 3 Commissioning Process & Guidelines 3-11

3 COMMISSIONING PROCESS & GUIDELINES 3.5 The Commissioning Process 3.5 THE COMMISSIONING PROCESS New customer / consultant / ESP contacts planner at ENMAX Power. Planner gives customer the harmonic specification and informs engineer about new customer Planner proceeds with normal planning process Customer and engineer exchange information for harmonic specs. Does the customer s facility produce harmonics? No Yes Engineer administers spec and executes criteria for staged acceptance Was customer accepted under staged acceptance? Yes Connect the customer No Do not connect the customer. Figure 3.2 Commissioning Process 3-12 Power Quality Specifications and Guidelines for Customers

COMMISSIONING PROCESS & GUIDELINES 3.6 Staged Acceptance..... 3.6 STAGED ACCEPTANCE Stage 1 Is a detailed evaluation required? Yes No Customer produces reports demonstrating Stage 1 requirements. Stage 2 Customer performs harmonic analysis and submits report to ENMAX Power. Stage 2 Do the customer s calculations comply with harmonic limits? Yes No Customer must install harmonic control equipment. ENMAX Power verifies the customer s calculation. Do actual harmonic measurements satisfy the harmonic spec? Yes Customer accepted No Customer not accepted. Figure 3.3 Staged Acceptance Section 3 Commissioning Process & Guidelines 3-13

3 COMMISSIONING PROCESS & GUIDELINES 3.6 Staged Acceptance 3-14 Power Quality Specifications and Guidelines for Customers

4 SYMBOLS AND DEFINITIONS........................................ 4.1 SYMBOLS h Harmonic order (2, 3, 4, 5,...) h r I h I L I sc MVA sc Parallel resonant frequency as a multiple of the fundamental frequency. Magnitude of individual harmonic components (rms amps). Maximum demand load current (fundamental frequency component) at PCC (rms amps). (Calculated as the average of the maximum monthly demand currents for the previous 12 months or estimated based on predicted load profiles.) Actual system short circuit current at PCC under normal circumstances. System short circuit MVA at the capacitor bus. MVAR cap MVAR rating of capacitor bank. P st V h V n Short-term flicker assessed in a 10 minute interval. Magnitude of individual harmonic components (rms volts). Nominal system rms voltage (rms volts). 4.2 DEFINITIONS Harmonic: A harmonic is a sinusoidal component of a periodic wave form having a frequency that is an integral multiple of the 60 Hz fundamental frequency. For example, the second, third, and fourth 4-15

4 SYMBOLS AND DEFINITIONS 4.2 Definitions IHD: PCC: THD: order harmonics have frequencies of 120, 180, and 240 Hz respectively. Individual harmonic distortion (IHD) is the magnitude of distortion at each individual harmonic. The IHD can be expressed in both voltage and current as a percentage of the fundamental component. Point of common coupling (PCC) is the location on the ENMAX power system that is electrically closest to the specified customer and is common to other ENMAX customers. Total harmonic distortion (THD) Voltage: THD= 50 V 2 h --------------------------- h= 2 ( 100percent) V n Current: 50 I 2 h THD= ----------------------- h= 2 ( 100percent) I L 4-16

5 REFERENCES........................................ 1. Allard, G. et al, New Hydro-Quebec Guide for Limiting Harmonic Current Emissions at the Distribution Level: Principles and Applications. CEA Distribution Planning Conference #16, 1996. 2. Guide and Requirements for Harmonic Control for Customers Supplied at a Voltage Level from 69kV to 287 kv. British Columbia Hydro, June 1994. 3. Guide for Applying Harmonic Limits on Power Systems, IEEE Std 519a/D5, May 1996. 4. Nesbitt, R., City of Calgary Electric System Standard for Voltage Flicker, ENMAX Power Corporation, October 1989. 5. Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Std 519-1992, April 1996. 5-17

5 REFERENCES 5-18