100G CWDM4 MSA Technical Specifications 2km Optical Specifications

Similar documents
400G CWDM8 10 km Optical Interface Technical Specifications Revision 1.0

100G 4WDM-10 MSA Technical Specifications 10km Optical Specifications Release 1.0

400G-FR4 Technical Specification

400G-BD4.2 Multimode Fiber 8x50Gbps Technical Specifications

Comment Supporting materials: The Reuse of 10GbE SRS Test for SR4/10, 40G-LR4. Frank Chang Vitesse

DATASHEET 4.1. QSFP, 40GBase-LR, CWDM nm, SM, DDM, 6.0dB, 10km, LC

40GBd QSFP+ LR4 Optical Transceiver

QSFP28. Parameter Symbol Min Max Units Notes Storage Temperature TS degc

QSFP-40G-LR4-S-LEG. 40Gbase QSFP+ Transceiver

QSFP SFP-QSFP-40G-LR4

Proposal for 4-channel WDM (WDM4) for intermediate reach 100GbE SMF PMD

Product Specification 10km Multirate QSFP+ Optical Transceiver Module FTL4C1QM1C

QSFP SV-QSFP-40G-LR4L

Product Specification 40GBASE-LR4 Lite QSFP+ Optical Transceiver Module FTL4C1QL2C

Product Specification 40GE SWDM4 QSFP+ Optical Transceiver Module FTL4S1QE1C

DATA SHEET: Transceivers

40G-QSFP-ER4-LEG. 40Gbase QSFP+ Transceiver

100Gbs QSFP28 LR4 Optical Transceiver Module WT-QSFP28-LR4

40GBASE-ER4 Ethernet Industrial: -40 C to 85 C. Infiniband QDR and DDR Four 10G DFB base CWDM channels on. Distance * (note2) Interface Temp.

Cisco QSFP-100G-LR4-S. Part Number: QSFP-100G-LR4-S QSFP-100G-LR4-S OVERVIEW PRODUCT FEATURES APPLICATIONS. FluxLight, Inc

PROLABS XENPAK-10GB-SR-C

SO-SFP-16GFC-ER-Dxxxx

DWDM XENPAK Transceiver, 32 wavelengths, SC Connectors, 80km over Single Mode Fiber

PROLABS JD121B-C. 10 Gigabit 1550nm SingleMode XFP Optical Transceiver, 40km Reach.

CFORTH-QSFP28-100G-LR4 Specifications Rev. D00B. Product Features

Product Specification. RoHS-6 Compliant 10Gb/s 10km 1310nm Single Mode Datacom SFP+ Transceiver FTLX1475D3BTL

XQS319-10LY. 100 Gb/s QSFP28 LR4 (Ethernet) Optical Transceiver. XQS319-10LY QSFP28 LR4 Optical Transceiver. Features

40G-BASE-LR4 10km QSFP+ Optical Transceiver GTR3QP1L

T A S A 5 N B 1 F A H

Product Specification 40GBASE-LR4 QSFP+ Optical Transceiver Module FTL4C1QE1C

XFP-10GER-192IR V Operating Environment Supply Voltage 1.8V V CC V Operating Environment Supply Current 1.8V I CC1.

10GBASE-S Technical Feasibility

X2-10GB-LR-OC Transceiver, 1310nm, SC Connectors, 10km over Single-Mode Fiber.

SO-CFP4-LR4. CFP4, 103/112 Gbps, 1310nm, SM, DDM, 6.3dB, 10km OVERVIEW PRODUCT FEATURES ORDERING INFORMATION DATASHEET 4.1

Multi-rate Gigabit Ethernet & Fibre Channel SFP Transceivers with Digital Diagnostics

CFP4. Parameter Symbol Min Max Units Notes. Storage Temperature Ts degc. Relative Humidity (non-condensation) RH 85 %

Product Specification. RoHS-6 Compliant 10Gb/s 10km Single Mode Datacom SFP+ Transceiver FTLX1475D3BNV

BTI-10GLR-XN-AS. 10GBASE-LR XENPAK Transceiver,1310nm, SC Connectors, 10km over Single-Mode Fiber. For More Information: DATA SHEET

XFP-10GLR-OC192SR-C. 10 Gigabit XFP Transceiver, LC Connectors, 1310nm, SingleMode Fiber 10km

SFP28 LR 25GE Serial Optical Transceiver for up to 10 km Reach TRS5A20EN-GA001

CFP2. Parameter Symbol Min Max Units Notes. Storage Temperature Ts degc. Relative Humidity (non-condensation) RH 85 %

QSFP+ Dual LC 40G SMF 10km Transceiver. Features. Applications. Ordering Information APPLIED OPTOELECTRONICS, INC.

Product Specification 100GBASE-SR10 100m CXP Optical Transceiver Module FTLD10CE1C APPLICATIONS

T A S A 1 E B 1 F A Q

T C W Q 1 L A A K C Q

The Price Performance Leader in 100% Compatible Optical Transceivers

The Price Performance Leader in 100% Compatible Optical Transceivers

IEEE 802.3ba 40Gb/s and 100Gb/s Ethernet Task Force 22th Sep 2009

Arista QSFP-40G-PLR4. Part Number: QSFP-40G-PLR4 QSFP-40G-PLR4 OVERVIEW PRODUCT FEATURES APPLICATIONS FUNCTIONAL DIAGRAM.

Gigabit Ethernet LC Bi-directional SFP Transceiver (80km) RBT12SZX

TRPUFEALXx000E1G Fast Ethernet 100BASE-LX10 SFP Single Mode Transceivers With Digital Diagnostics

Multi-rate Gigabit Ethernet & Fibre Channel SFP CWDM Transceivers with Digital Diagnostics

XCS319-10LY. 100GBASE-LR4 CFP4 Optical Transceiver. Features. Applications. General Description

T G W Q 1 4 B B F 8 1

XFP-10G-Z-OC192-LR2-C

T Q S Q 7 4 H 9 J C A

TPP3XGDS0x000E2G 850nm SFP+ Transceiver

Product Specification. RoHS-6 Compliant 10Gb/s Extended Temperature 10km Single Mode Datacom SFP+ Transceiver FTLX1471D3BNL

DWDM XENPAK Transceivers, 32 wavelengths, SC Connectors, 80km over Single Mode Fiber

1.25Gb/s 160km DWDM SFP Transceiver (OP340GD-D ) Hot Pluggable, Duplex LC, 100GHz, DWDM DFB & APD, Single-mode, DDM

QSFP28 Dual LC 100G SMF 2km Transceiver. Features. Applications. Ordering Information APPLIED OPTOELECTRONICS, INC.

T Q S Q 1 4 H 9 J 8 2

Shenzhen Opway Communication Co., Ltd. 100Gb/s QSFP28 LR4 Optical Transceiver (OPQE10)

Product Specification

1. General Description This product is a 100Gb/s transceiver module for optical communication applications compliant to 100GBASE-LR4 of the IEEE P802.

10G SFP+ CWDM 20km Transceiver Hot Pluggable, Duplex LC, +3.3V, 1270~1350nm CWDM DFB, DDMI PSFP-2C41SF-XX

XBR C. 8Gbs SFP+ Transceiver

SFP-1020-WA/B 10Gbps SFP+ Bi-Directional Transceiver, 20km Reach 1270/1330nm TX / 1330/1270 nm RX

SO-SFP28-LR. SFP28, 25GBASE-LR, 1310nm, SM, DDM, 10km OVERVIEW PRODUCT FEATURES APPLICATIONS ORDERING INFORMATION DATASHEET 4.1

Gigabit Ethernet LC Bi-directional SFP Transceiver (40km) RBT12SEX

Product Specification Industrial Temperature 2 Gigabit Long-Wavelength Pluggable SFP Transceiver FTRJ1319P1xTL

Specification for 100GBASE-DR4. Piers Dawe

Product Specification

10Gb/s SFP+ BX LC DDMI Optical module Tx:1330nm/Rx:1270nm 10km transmission distance

PROLABS EX-SFP-10GE-LR-C

Product Specification. 10Gb/s Multi-Rate, 10km Single Mode SFP+ Transceiver FTLX1472M3BTL

1550nm 40km SFP+ Transceiver

XFP-10GB-EZR (OC192) 10GB Multirate DDMI XFP 1550nm cooled EML with APD Receiver 120km transmission distanc 10GB Multirate DDMI XFP

LX8501CDR 100G 100m QSFP28 Transceiver 100GBASE-SR4

Parameter Symbol Min Typ Max Unit Remarks Data Rate DR GBd IEEE 802.3ae Bit Error Rate BER Input Voltage V CC

Product Specification. 10Gb/s, 40km Single Mode, Multi-Rate SFP+ Transceiver FTLX1672D3BTL APPLICATIONS

10GBd SFP+ LR Long Wavelength (1310nm) Transceiver

100G SR4 TxVEC Update. John Petrilla: Avago Technologies May 15, 2014

Product Specification. 10Gb/s DWDM 80km XFP Optical Transceiver FTRX xx

X2-10GB-Cxx-ER CWDM X2-10GBASE, 40km Reach

APSB53123xxL20. Product Features. Applications. General. 1.25Gb/s BiDi SFP Transceiver

DS-16G-ER-Cxx. SFP+, 16/8/4 Gbps FC/FICON, CWDM, SM, DDM, 13dB, 40km OVERVIEW PRODUCT FEATURES APPLICATIONS ORDERING INFORMATION DATASHEET 4.

1550nm 40km SFP+ Transceivers

10Gb/s SFP+, Hot Pluggable, Duplex LC, +3.3V, 1310nm, Multi Mode, 220m FP-LD Optical Transceiver PSFP MF

PROLABS SFP-10G-LR-C 10GBd SFP+ LR Transceiver

Product Specification. FWLF1524P2yxx

This 1310 nm DFB 10Gigabit SFP+ transceiver is designed to transmit and receive optical data over single mode optical fiber for link length 10km.

Part Number Operating temperature DDMI. APSCxx123CXL80 Commercial No. APSCxx123CDL80 Commercial Yes. APSCxx123IXL80 Industrial No

10GBase SFP+ LR/LW Optical Transceivers Series WST-SFP+LR-C

40Gb/s QSFP+ esr4 Optical Transceiver Module QSFP-4000-ESR4. Product Specification

Product Specifications. 10Gb/s, 1310nm 40km, Single Mode, Multi-Rate SFP+ Transceiver FTLX1772M3BCL FTLX1772M3BCL

Arista 40GBASE-XSR4-AR. Part Number: 40GBASE-XSR4-AR 40GBASE-XSR4-AR OVERVIEW APPLICATIONS PRODUCT FEATURES. FluxLight, Inc

10G CWDM SFP+ 40km ER Transceiver Hot Pluggable, Duplex LC, +3.3V, 1470~1610nm CWDM EML, DDMI PSFP10-1C41SF-XX

Product Specification OC-12 SR-1/STM I-4 or OC-12 IR-1/STM S-4.1 2x5 SFF Transceiver FTLF1322F2xTR

GBP-XXXX192-L2C 10Gbps SFP+ Bi-Directional Transceiver, 20km Reach 1270/1330nm TX / 1330/1270 nm RX

Transcription:

100G CWDM4 MSA Technical Specifications 2km Specifications Participants Editor David Lewis, LUMENTUM Comment Resolution Administrator Chris Cole, Finisar The following companies were members of the CWDM4 MSA at the release of this specification: Company Avago Finisar LUMENTUM Oclaro Sumitomo Electric Technical Contributors John Petrilla Chris Cole, Jonathan King David Lewis Kiyohisa Hiramoto Eddie Tsumura Contacts: http://cwdm4-msa.org Revisions Rev Date Description 1.0 August 27, 2014 Initial Release 1.1 November 23, 2015 Replace JDSU with Lumentum. Added Section 6 on color coding. Page 1 November 24, 2015

CONTENTS CONTENTS... 2 TABLES... 3 FIGURES... 3 1 GENERAL... 4 1.1 SCOPE... 4 1.2 CWDM4 MODULE BLOCK DIAGRAM... 4 1.3 FUNCTIONAL DESCRIPTION... 5 1.4 HARDWARE SIGNALING PINS... 5 1.5 MODULE MANAGEMENT INTERFACE... 5 1.6 HIGH SPEED ELECTRICAL CHARACTERISTICS... 5 1.7 FEC Requirements... 5 1.8 MECHANICAL DIMENSIONS... 5 1.9 OPERATING ENVIRONMENT... 5 1.10 POWER SUPPLIES AND POWER DISSIPATION... 5 2 CWDM4 OPTICAL SPECIFICATIONS... 6 2.1 WAVELENGTH-DIVISION-MULTIPLEXED LANE ASSIGNMENTS... 6 2.2 OPTICAL SPECIFICATIONS... 6 2.2.1 CWDM4 transmitter optical specifications... 7 2.2.2 CWDM4 receive optical specifications... 8 2.2.3 CWDM4 illustrative link power budget... 9 3 DEFINITION OF OPTICAL PARAMETERS AND MEASUREMENT METHODS... 10 3.1 Test patterns for optical parameters... 10 3.1.1 Square wave pattern definition... 10 3.2 Skew and Skew Variation... 10 3.3 Wavelength... 10 3.4 Average optical power... 10 3.5 Modulation Amplitude (OMA)... 11 3.6 Transmitter and dispersion penalty (TDP)... 11 3.6.1 Reference transmitter requirements... 11 3.6.2 Channel requirements... 11 3.6.3 Reference receiver requirements... 12 Page 2 November 24, 2015

3.6.4 Test procedure... 12 3.7 Extinction ratio... 12 3.8 Transmitter optical waveform (transmit eye)... 12 3.9 Receiver sensitivity... 12 3.10 Stressed receiver sensitivity... 13 4 FIBER OPTIC CABLING MODEL... 14 5 CHARACTERISTICS OF THE FIBER OPTIC CABLING (CHANNEL)... 15 5.1 fiber cable... 15 5.2 fiber connection... 15 5.2.1 Connection insertion loss... 15 5.2.2 Maximum discrete reflectance... 15 5.3 Medium Dependent Interface (MDI) requirements... 15 6 CWDM4 Module Color Coding... 16 TABLES Table 2-1: Wavelength-division-multiplexed lane assignments... 6 Table 2-2: CWDM4 operating range... 6 Table 2-3: CWDM4 transmit characteristics... 7 Table 2-4: CWDM4 receive characteristics... 8 Table 2-5: CWDM4 illustrative power budget... 9 Table 3-1: Patterns for optical parameter testing... 10 Table 3-2: Transmitter compliance channel specifications... 11 Table 4-1: Fiber optic cabling (channel) characteristics... 14 Table 5-1: fiber and cable characteristics... 15 Table 6-1: CWDM4 Module Color Coding... 16 FIGURES Figure 1-1: Block diagram for CWDM4 transmit/receive paths... 4 Figure 3-1 Test setup for measurement of receiver sensitivity... 13 Figure 4-1: Fiber optic cabling model... 14 Page 3 November 24, 2015

1 GENERAL CWDM4 MSA Technical Specifications Rev 1.1 1.1 SCOPE This Multi-Source Agreement (MSA) defines 4 x 25 Gbps Coarse Wavelength Division Multiplex (CWDM) optical interfaces for 100 Gbit/s optical transceivers for Ethernet applications including 100 GbE. Forward error correction (FEC) is required to be implemented by the host in order to ensure reliable system operation. Two transceivers communicate over single mode fibers (SMF) of length from 2 meters to at least 2 kilometers. The transceiver electrical interface is not specified by this MSA but can have, for example, four lanes in each direction with a nominal signaling rate of 25.78125 Gbps per lane. Different form factors for the transceivers are possible. Initial implementations are expected to use either the CFP4 or the QSFP28 module form factors. Other form factors are possible and are not precluded by this MSA. 1.2 CWDM4 MODULE BLOCK DIAGRAM TP4<0:3> TP3 TP1<0:3> CWDM4 Module CWDM4 Module RX0 receiver TP2 transmitter TX0 RX1 RX2 receiver receiver WD demux fiber cable Patch cord WD mux transmitter transmitter TX1 TX2 RX3 receiver transmitter TX3 TX3 transmitter receiver RX3 TX2 TX1 transmitter transmitter WD mux Patch cord fiber cable WD demux receiver receiver RX2 RX1 TX0 transmitter TP2 receiver RX0 TP1<0:3> TP3 TP4<0:3> WD = Wavelength division NOTE Specification of the retime function is beyond the scope of this MSA. Figure 1-1: Block diagram for CWDM4 transmit/receive paths Page 4 November 24, 2015

1.3 FUNCTIONAL DESCRIPTION CWDM4 modules comply with the requirements of this document and have the following common features: four optical transmitters; four optical receivers with signal detect; wavelength division multiplexer and demultiplexer; and a duplex optical connector for singlemode fiber. The optical connector type is vendor specific but can include SC or LC types. 1.4 HARDWARE SIGNALING PINS Hardware signaling pins are specified in the respective module form factor MSAs. 1.5 MODULE MANAGEMENT INTERFACE The contents of the various ID registers shall comply with the requirements of the module MSA and the respective standards. In the case of QSFP28 modules, the management interface complies with SFF-8636. For CFP4 modules, the management interface complies with the CFP MSA Management Interface Specification. 1.6 HIGH SPEED ELECTRICAL CHARACTERISTICS The detailed high speed electrical characteristics are not defined by this MSA. 100GE modules could be implemented in compliance with IEEE 802.3bm Annex 83E, CAUI-4 chip-to-module, or OIF CEI-28G-VSR or other interfaces to be defined. 1.7 FEC REQUIREMENTS The optical link is specified to operate at a bit error ratio (BER) of 5 x 10-5. The host system is required to enable RS(528,514) FEC in accordance with clause 91 of IEEE-Std TM 802.3bj in order to comply with the IEEE 100G Mean Time to False Packet Acceptance (MTTFPA) requirements. The option to bypass the Clause 91 RS-FEC correction function is not supported. 1.8 MECHANICAL DIMENSIONS Mechanical dimensions are defined in the module form factor MSA specifications. QSFP28 is defined in SFF-8661. CFP4 is defined in the CFP4 Hardware Specification. 1.9 OPERATING ENVIRONMENT All specified minimum and maximum parameter values shall be met when the host system maintains the operating case temperature and supply voltages within the module vendor specified operating ranges. All minimum and maximum limits apply over the operating life of the system. 1.10 POWER SUPPLIES AND POWER DISSIPATION Module vendors shall specify the module power supply requirements in accordance with the module MSA. Page 5 November 24, 2015

2 CWDM4 OPTICAL SPECIFICATIONS 2.1 WAVELENGTH-DIVISION-MULTIPLEXED LANE ASSIGNMENTS The wavelength range for each lane of the CWDM PMD is defined in Table 2-1. The center wavelengths are spaced at 20 nm. Table 2-1: Wavelength-division-multiplexed lane assignments Lane Center wavelength Wavelength range Module electrical lane L 0 1271 nm 1264.5 to 1277.5 nm Tx0, Rx0 L 1 1291 nm 1284.5 to 1297.5 nm Tx1, Rx1 L 2 1311 nm 1304.5 to 1317.5 nm Tx2, Rx2 L 3 1331 nm 1324.5 to 1337.5 nm Tx3, Rx3 2.2 OPTICAL SPECIFICATIONS The operating range for a CWDM4 PMD is defined in Table 2-2. A CWDM4 compliant PMD operates on single-mode fibers according to the specifications defined in Table 4-1 and characteristics in 5.1. A PMD that exceeds the required operating range while meeting all other optical specifications is considered compliant (e.g., operating at 2.5 km meets the operating range requirement of 2 m to 2 km). Table 2-2: CWDM4 operating range PMD type 100GE-CWDM4 Required operating range 2 m to 2 km Page 6 November 24, 2015

2.2.1 CWDM4 transmitter optical specifications The CWDM4 transmitter shall meet the specifications defined in Table 2-3. Table 2-3: CWDM4 transmit characteristics Description Value Unit Signaling rate, each lane (range) 100GE 25.78125 ± 100 ppm GBd Line wavelengths (range) 1264.5 to 1277.5 1284.5 to 1297.5 1304.5 to 1317.5 1324.5 to 1337.5 Side-mode suppression ratio (SMSR), (min) 30 db Total average launch power (max) 8.5 dbm Average launch power, each lane (max) 2.5 dbm Average launch power, each lane a (min) -6.5 dbm Modulation Amplitude (OMA), each lane (max) 2.5 dbm Modulation Amplitude (OMA), each lane (min) b -4.0 dbm Launch power in OMA minus TDP, each lane (min) -5.0 dbm Transmitter and dispersion penalty (TDP), each lane (max) d 3.0 db Average launch power of OFF transmitter, each lane (max) -30 dbm Extinction ratio (min) 3.5 db return loss tolerance (max) 20 db Transmitter reflectance c (max) -12 db {0.31, 0.4, 0.45, 0.34, Transmitter eye mask definition {X1, X2, X3, Y1, Y2, Y3} 0.38, 0.4} a Average launch power, each lane (min) is informative and not the principal indicator of signal strength. A transmitter with launch power below this value cannot be compliant; however, a value above this does not ensure compliance. b Even if the TDP < 1.0dB, the OMA (min) must exceed this value. c Transmitter reflectance is defined looking into the transmitter. d TDP does not include a penalty for multi-path interference (MPI). nm Page 7 November 24, 2015

2.2.2 CWDM4 receive optical specifications The CWDM4 receiver shall meet the specifications defined in Table 2-4. Table 2-4: CWDM4 receive characteristics Description Value Unit Signaling rate, each lane (range) 100GE 25.78125 ± 100 ppm GBd Line wavelengths (range) 1264.5 to 1277.5 1284.5 to 1297.5 1304.5 to 1317.5 1324.5 to 1337.5 Damage threshold, each lane (min) a 3.5 dbm Average receive power, each lane (max) 2.5 dbm Average receive power, each lane b (min) -11.5 dbm Receive power, each lane (OMA) (max) 2.5 dbm Receiver reflectance (max) -26 db Receiver sensitivity (OMA), each lane (max) at 5 x 10-5 BER c -10.0 dbm Stressed receiver sensitivity (OMA), each lane d (max) -7.3 dbm Conditions of stressed receiver sensitivity test: Vertical eye closure penalty, e each lane 1.9 db Stressed eye J2 Jitter, e each lane 0.33 UI Stressed eye J4 Jitter, e each lane 0.48 UI SRS eye mask definition e { X1, X2, X3, Y1, Y2, Y3} {0.39, 0.5, 0.5, 0.39, 0.39, 0.4} a The receiver shall be able to tolerate, without damage, continuous exposure to an optical signal having this average power level b Average receive power, each lane (min) is informative and not the principal indicator of signal strength. A received power below this value cannot be compliant; however, a value above this does not ensure compliance. c Receiver sensitivity (OMA), each lane (max) at 5 x 10-5 BER is a normative specification. d Measured with conformance test signal at TP3 (see 3.10) for BER = 5x10-5. e Vertical eye closure penalty, stressed eye J2 Jitter, stressed eye J4 Jitter, and SRS eye mask definition are test conditions for measuring stressed receiver sensitivity. They are not characteristics of the receiver. nm Page 8 November 24, 2015

2.2.3 CWDM4 illustrative link power budget An illustrative power budget and penalties for CWDM4 are shown in Table 2-5. Table 2-5: CWDM4 illustrative power budget Description Value Unit Power budget (for max TDP) 8.0 db Operating distance 2.0 km Channel insertion loss a 5.0 db Maximum discrete reflectance -26 db Allocation for penalties (for max TDP) 3.0 db Additional insertion loss allowed 0 db a The channel insertion loss budget may include up to 1 db MPI loss penalty with worst case transmitter and worst case connector MPI. Page 9 November 24, 2015

3 DEFINITION OF OPTICAL PARAMETERS AND MEASUREMENT METHODS All optical measurements shall be made through a short patch cable, between 2 m and 5 m in length, unless otherwise specified. 3.1 TEST PATTERNS FOR OPTICAL PARAMETERS Table 3-1: Patterns for optical parameter testing Parameter Pattern Sub-clause a Wavelength PRBS31 3.3 Side mode suppression ratio PRBS31 -- Average optical power PRBS31 3.4 modulation amplitude (OMA) Square wave 3.5 Transmitter and dispersion penalty (TDP) PRBS31 3.6 Extinction ratio PRBS31 3.7 Transmitter optical waveform PRBS31 3.8 Stressed receiver sensitivity PRBS31 3.10 Calibration of OMA for receiver tests PRBS9 3.10 Vertical eye closure penalty calibration PRBS31 3.10 a These sub-clauses make reference to relevant clauses of IEEE Std 802.3-2012. Note that the PRBS pattern generator and pattern checker are defined in IEEE Std 802.3-2012 clauses 49.2.9 and 49.2.12 respectively. 3.1.1 Square wave pattern definition A pattern consisting of eight ones followed by an equal run of zeroes may be used as a square wave. 3.2 SKEW AND SKEW VARIATION Refer to IEEE Std 802.3-2012 Clause 87.8.2. CWDM4 MSA transceivers shall comply with the skew and skew variation limits of clause 88.3.2. 3.3 WAVELENGTH Measure per TIA/EIA-455-127-A or IEC 61280-1-3. 3.4 AVERAGE OPTICAL POWER Measure using the methods given in IEC 61280-1-1 with all channels not being measured turned off. Page 10 November 24, 2015

3.5 OPTICAL MODULATION AMPLITUDE (OMA) Refer to IEEE Std 802.3-2012 Clause 52.9.5. OMA is measured with a square wave (8 ones, 8 zeros) test pattern. Each lane may be tested individually with all other lanes turned off, or by using an optical filter as defined in 3.6 if the other lanes are active. 3.6 TRANSMITTER AND DISPERSION PENALTY (TDP) TDP shall be as defined in IEEE Std 802.3-2012 Clause 52.9.10 with the exception that each optical lane is tested individually using an optical filter to separate the lane under test from the others. The optical filter pass band ripple shall be limited to 0.5 db peak-to-peak and the isolation is chosen such that the ratio of the power in the lane being measured to the sum of the powers of all the other lanes is greater than 20 db (see ITU-T G.959.1 Annex B). The lanes not under test shall be operating with PRBS31 bit streams. 3.6.1 Reference transmitter requirements Refer to IEEE Std 802.3-2012 Cl. 88.8.5.1. 3.6.2 Channel requirements The transmitter is tested using an optical channel that meets the requirements listed in Table 3-2. Type Table 3-2: Transmitter compliance channel specifications Dispersion a (ps/nm) Minimum Maximum Insertion loss b return loss c CWDM4 0.0465* *[1-(1324/ ) 4 ] 0.0465* *[1-(1300/ ) 4 ] Minimum 20 db a The dispersion is measured for the wavelength of the device under test ( in nm). The coefficient assumes 2 km for CWDM4. b There is no intent to stress the sensitivity of the BERT s optical receiver. c The optical return loss is applied at TP2, i.e. after a 2 meter patch cord. A transmitter is to be compliant with a total dispersion at least as negative as the minimum dispersion and at least as positive as the maximum dispersion columns specified in Table 3-2 for the wavelength of the device under test. This may be achieved with channels consisting of fibers with lengths chosen to meet the dispersion requirements. To verify that the fiber has the correct amount of dispersion, the measurement method defined in IEC 60793-1-42 may be used. The measurement is made in the linear power regime of the fiber. The channel provides an optical return loss specified in Table 3-2. The state of polarization of the back reflection is adjusted to create the greatest RIN. Page 11 November 24, 2015

3.6.3 Reference receiver requirements Refer to IEEE Std 802.3-2012 Cl. 88.8.5.3. 3.6.4 Test procedure The test procedure is as defined in IEEE Std 802.3-2012 Cl. 52.9.10.4 with the exception that all lanes are operational in both directions (transmit and receive), each lane is tested individually using an optical filter to separate the lane under test from the others, and the BER of 5 x 10-5 is for the lane under test on its own. 3.7 EXTINCTION RATIO Extinction ratio is measured using the methods specified in IEC 61280-2-2, with the lanes not under test turned off. 3.8 TRANSMITTER OPTICAL WAVEFORM (TRANSMIT EYE) Refer to IEEE Std 802.3-2012 Cl. 88.8.8. 3.9 RECEIVER SENSITIVITY The nominal sensitivity of each receiver lane, is measured in OMA using the setup of Figure 3-1. The sensitivity must be corrected for any significant reference transmitter impairments including any vertical eye closure. It should be measured at the eye center or corrected for offcenter sampling. The reference transmitter wavelength(s) shall comply with the ranges in Table 2-4. The reference transmitter is a high-quality instrument grade device, which can be implemented by a CW laser modulated by a high-performance modulator. It should have the following basic requirements: a) The rise/fall times should be less than 12 ps at 20% to 80%. b) The output optical eye is symmetric and passes the transmitter optical waveform test of 3.8. c) In the center 20% region of the eye, the worst-case vertical eye closure penalty as defined in 802.3-2012 87.8.11.2 is less than 0.5 db. d) Total jitter less than 0.2 UI peak-to-peak e) RIN of less than -138 db/hz. Center of the eye is defined as the time halfway between the left and right sampling points within the eye where the measured BER is greater than or equal to 1 x 10-3. The clock recovery unit (CRU) used in the sensitivity measurement has a corner frequency of less than or equal to 10 MHz and a slope of 20 db/decade. When using a clock recovery unit as Page 12 November 24, 2015

a clock for BER measurement, passing of low frequency jitter from the data to the clock removes this low-frequency jitter from the measurement. PPG Data PPG PPG PPG Reference CWDM Transmitter Attenuator CWDM Receiver (DUT) CRU Clock BERT Lanes not under test Figure 3-1 Test setup for measurement of receiver sensitivity 3.10 STRESSED RECEIVER SENSITIVITY Refer to IEEE Std 802.3-2012 Cl. 88.8.10. Note that for CWDM4 transceivers J9 is replaced by J4 and also that the test BER is 5x10-5 instead of 1x10-12. J4 jitter is defined in IEEE 802.3bm Cl. 95.8.8.4. Each lane is tested individually with all other Rx and Tx channels turned ON and receiving or transmitting PRBS31 signals. The maximum OMA difference between the Rx lane under test and the other Rx lanes not under test is 4.5 db. The Gaussian noise generator, the amplitude of the sinusoidal interferers, and the low-pass filter are adjusted so that the VECP, stressed eye J2 Jitter, and stressed eye J4 Jitter specifications given in Table 2-4 are met simultaneously while also passing the stressed receiver eye mask in Table 2-4 according to the methods in 802.3-2012 clause 88.8.8 (the random noise effects such as RIN, or random clock jitter, do not need to be minimized). Page 13 November 24, 2015

4 FIBER OPTIC CABLING MODEL The fiber optic cabling model is shown in Figure 4-1. MDI MDI Fiber optic cabling (channel) PMD Patch cord Connection Link Connection Patch cord PMD Figure 4-1: Fiber optic cabling model The channel insertion loss is given in Table 4-1. A channel may contain additional connectors as long as the optical characteristics of the channel, such as attenuation, dispersion, reflections and polarization mode dispersion meet the specifications. Insertion loss measurements of installed fiber cables are made in accordance with IEC 61280-4-2 using the one-cord reference method. The fiber optic cabling model (channel) defined here is the same as a simplex fiber optic link segment. The term channel is used here for consistency with generic cabling standards. Table 4-1: Fiber optic cabling (channel) characteristics Description CWDM4 Unit Operating distance (max) 2 km Channel insertion loss a,b (max) 5 db Channel insertion loss (min) 0 db Positive dispersion b (max) 6.7 ps/nm Negative dispersion b (min) -11.9 ps/nm DGD_max c 3.0 ps return loss (min) 21 db a) These channel loss values include cable, connectors and splices. b) Over the wavelength range 1264.5 to 1337.5 nm. c) Differential Group Delay (DGD) is the time difference at reception between the fractions of a pulse that were transmitted in the two principal states of polarization of an optical signal. DGD_max is the maximum differential group delay that the system must tolerate. Page 14 November 24, 2015

5 CHARACTERISTICS OF THE FIBER OPTIC CABLING (CHANNEL) The CWDM4 fiber optic cabling shall meet the specifications defined in Table 4-1. The fiber optic cabling consists of one or more sections of fiber optic cable and any intermediate connections required to connect sections together. 5.1 OPTICAL FIBER CABLE The fiber optic cable requirements are satisfied by cables containing IEC 60793-2-50 type B1.1 (dispersion un-shifted single-mode), type B1.3 (low water peak single-mode), or type B6_a (bend insensitive) fibers and the requirements in Table 5-1 where they differ. Table 5-1: fiber and cable characteristics Description Value Unit Nominal fiber specification wavelength 1310 nm Cabled optical fiber attenuation (max) 0.5 a db/km Zero dispersion wavelength ( 0 ) 1300 0 1324 nm Dispersion slope (max) (S 0 ) 0.093 ps/nm 2 km a The 0.5 db/km attenuation is provided for Outside Plant cable as defined in ANSI/TIA 568-C.3. 5.2 OPTICAL FIBER CONNECTION An optical fiber connection, as shown in Figure 4-1, consists of a mated pair of optical connectors. 5.2.1 Connection insertion loss The maximum link distances for single-mode fiber are calculated based on an allocation of 3.89 db total connection and splice loss. For example, this allocation supports seven connections with an average insertion loss per connection of 0.5 db. Connections with different loss characteristics may be used provided the requirements of Table 4-1 are met. 5.2.2 Maximum discrete reflectance The maximum discrete reflectance shall be less than -26 db. 5.3 MEDIUM DEPENDENT INTERFACE (MDI) REQUIREMENTS The PMD is coupled to the fiber optic cabling at the MDI. The MDI is the interface between the PMD and the fiber optic cabling (as shown in Figure 4-1). Examples of an MDI include the following: Page 15 November 24, 2015

a) Connectorized fiber pigtail b) PMD receptacle When the MDI is a connector plug and receptacle connection, it shall meet the interface performance specifications of IEC 61753-1-1 and IEC 61753-021-2. NOTE---Transmitter compliance testing is performed at TP2 i.e. after a 2 meter patch cord, not at the MDI. 6 CWDM4 Module Color Coding Transceiver modules compliant to the CWDM4 MSA Specifications use a color code to indicate the application. This color code can be on a module bail latch, pull tab, or other visible feature of the module when installed in a system. The color code scheme is specified in Table 6-1. Table 6-1: CWDM4 Module Color Coding Green Color Code Application 100 Gb/s CWDM4 2 km reach Page 16 November 24, 2015