Generator Advanced Concepts

Similar documents
Sizing Generators for Leading Power Factor

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)

Spec Information. Reactances Per Unit Ohms

GENERATOR DATA JANUARY 30, 2015

SYNCHRONOUS MACHINES

Spec Information. Reactances Per Unit Ohms

Voltage and Current Waveforms Enhancement using Harmonic Filters

Code No: R Set No. 1

VALLIAMMAI ENGINEERING COLLEGE

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

WDG 12 - Technical Data Sheet

WDG 13 - Technical Data Sheet

WDG 71 - Technical Data Sheet

WDG 07 - Technical Data Sheet

DISCUSSION OF FUNDAMENTALS

WDG 12 - Technical Data Sheet

WDG 51 - Technical Data Sheet

WDG 12 - Technical Data Sheet

WDG 12 - Technical Data Sheet

Effects of Harmonic Distortion I

Introduction : Design detailed: DC Machines Calculation of Armature main Dimensions and flux for pole. Design of Armature Winding & Core.

WDG 61 - Technical Data Sheet

HARMONICS CAUSES AND EFFECTS

System Protection and Control Subcommittee

Power. Power is the rate of using energy in joules per second 1 joule per second Is 1 Watt

WDG 83 - Technical Data Sheet

Type of loads Active load torque: - Passive load torque :-

Synchronous Generator Subtransient Reactance Prediction Using Transient Circuit Coupled Electromagnetic Analyses & Odd Periodic Symmetry

Low Pass Harmonic Filters

Placement Paper For Electrical

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

CHAPTER 5 SYNCHRONOUS GENERATORS

A Practical Guide to Free Energy Devices

AGN 034 Alternator Reactance

PM734B - Technical Data Sheet. Generator Solutions AS

PI734C - Technical Data Sheet

Conventional Paper-II-2011 Part-1A

PI734A - Technical Data Sheet

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

An Introduction to Power Quality

Conventional Paper-II-2013

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

PARTNER ALTERNATORS LSA 40-4 Pole

PI734F - Winding 07. Technical Data Sheet APPROVED DOCUMENT

PI734F - Winding 28. Technical Data Sheet APPROVED DOCUMENT

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW

PI734E - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734C - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734B - Winding 312. Technical Data Sheet APPROVED DOCUMENT

TAL 044 Low Voltage Alternator - 4 pole

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 150 KW BUT LESS THAN OR EQUAL TO 550 KW

Type KLF Generator Field Protection-Loss of Field Relay

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

PM734D - Winding 312. Technical Data Sheet APPROVED DOCUMENT. Generator Solutions AS

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Electrical Machines (EE-343) For TE (ELECTRICAL)

Inductance, capacitance and resistance

PM734F - Winding 312. Technical Data Sheet APPROVED DOCUMENT

3.1.Introduction. Synchronous Machines

Preface...x Chapter 1 Electrical Fundamentals

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.


Application Guidance Notes: Technical Information from Cummins Generator Technologies

Latest Control Technology in Inverters and Servo Systems

Production power on a budget: How to generate clean reliable power, Part 2 By Guy Holt

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

Cylindrical rotor inter-turn short-circuit detection

TAL 049 Low Voltage Alternator - 4 pole

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

TAL 047 Low Voltage Alternator - 4 pole

PESIT Bangalore South Campus Hosur road, 1km before Electronic City, Bengaluru -100 Department of Electronics & Communication Engineering

UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE

Alternators Reactance for Nonlinear Loads

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad ELECTRICAL AND ELECTRONICS ENGINEERING

PART 1 OWNER/APPLICANT INFORMATION

ELG2336 Introduction to Electric Machines

Exercise 3. Doubly-Fed Induction Generators EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Doubly-fed induction generator operation

CHAPTER 6 FABRICATION OF PROTOTYPE: PERFORMANCE RESULTS AND DISCUSSIONS

Alternating Current Page 1 30

S0L1-J1 - Technical Data Sheet

Time constants ( s ) Resistance. Other data - Class H /6600 V kva. Efficiencies ( % )(3 phase - Classe H V kva)

GRAAD 12 NATIONAL SENIOR CERTIFICATE GRADE 12

Impact Assessment Generator Form

Generator Protection GENERATOR CONTROL AND PROTECTION

A Guide to Power Quality Testing

ALTERNATOR TECHNICAL DESCRIPTION 1. LSA 53.2 XL13 / 4p. Chargé d'affaire : Karthikeyan GN 1 Moteurs Leroy-Somer +33 (0) xx

Power Factor. Power Factor Correction.

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems

1. Explain in detail the constructional details and working of DC motor.

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

LSA R & LSA H 49.1 Low Voltage Alternators - 4 pole

DC Machine Construction. Figure 1 General arrangement of a dc machine

1. (a) Determine the value of Resistance R and current in each branch when the total current taken by the curcuit in figure 1a is 6 Amps.

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

Electrical Workstation Nvis 7089A

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

ENGINEERING ACADEMY X V

Transcription:

Generator Advanced Concepts

Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves Used for System Coordination Thermal Damage Curve Decrement Curve Reactive Capability Efficiency Parallel Operation

What Determines Voltage Output? E = 4 f fb kd kp N F, where f = Frequency of operation which correlates to the difference in relative speeds of the field and conductors fb = Shape of the magnetic flux wave arising from rotor lamination design kd = Winding distribution factor related to winding details kp = Winding pitch N = Number of turns per phase in winding F = Total magnetic flux per pole, which includes machine stack length and operating magnetic flux density

Application of V Output Equation E = 4 f fb kd kp N F What if we want a 60 Hz machine to run at 50 Hz too? f decreases by a ratio of 50/60 E will also decrease by a ratio of 50/60 unless another factor changes: Increase magnetic flux densities (F)? May not be possible due to material characteristics. Can cause excess heating. Increase stack length (F) Increases cost. Change other aspect of the design, including different laminations and different winding configuration or turns.

Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves Used for System Coordination Thermal Damage Curve Decrement Curve Reactive Capability Efficiency Parallel Operation

Pitch: Pole and Winding Pole pitch is the mechanical angle between adjacent poles, e.g. 4 pole = 90º. Winding pitch is the coil span divided by the pole pitch, e.g. 60º / 90º = 2/3. Key design factors include number of poles, number of slots, and number of slots spanned by coils. 1-9 coil span

Pitch: Common Values Specified Optimum pitch allows the designer flexibility used to balance generator performance to effectively utilize the generator s active materials. 2/3 pitch is often specified because it reduces 3rd harmonic content. However this may require a larger machine to meet the power ratings. Lower pitches E = 4 f fb kd kp N F kp decreases with lower pitch. If the voltage is to remain the same, something else has to increase. Increase magnetic flux densities Increase stack length Increase turns Use a different lamination set

Pitch: Effects When Reduced Coils spanning anything less than the full distance from pole to pole are called short-pitched. Reactances are reduced as pitch decreases (keeping all other design factors). Harmonics are generally reduced more than the fundamental, and specific harmonics can be cancelled entirely. 2/3 pitch reduces 3rd harmonic L-N at the expense of increasing 5th and 7th harmonics. There is never a 3rd harmonic L-L on a balanced system. Generator may need to be oversized to meet its rated power output and temperature.

Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves Used for System Coordination Thermal Damage Curve Decrement Curve Reactive Capability Efficiency Parallel Operation

Harmonics Purely sinusoidal (clean and smooth) waveforms are desirable. Clean and smooth waveforms minimizes sudden changes in voltages, currents and power. Power system waveforms typically are NOT clean and smooth. Pure sinusoidal waveform Note: Example is for demonstration purpose only and is not typical of generator waveforms. It shows exaggerated harmonics without phase shift. Waveform with harmonics

Harmonics (cont.) Signals can be broken into a main (fundamental) sinusoidal (smooth) waveform and a series other smooth waveforms at frequencies that are multiples of the fundamental waveform frequency. Signal Main Harmonics Harmonics are the extra signals other than the fundamental waveform. Lowest harmonic usually has highest amplitude. Specifications call out individual harmonic limits as well as total harmonic distortion (THD).

Harmonics (cont.): Signal Breakdown Signal --- fundamental --- Signal --- fund+3 rd +5th --- Signal --- fund+3rd --- Signal --- fund+3 rd +5 th +7th ---

Load-Induced Distortion Example Pictured below is a real waveform that has notching caused by SCR loads This increased harmonic content and the issues associated with higher harmonics.

Harmonics (cont.): Resultant Problems Insulation systems may stress and get damaged. Generator components may overheat, requiring derating of the generator. Motors on the system may experience overheating, high audible noise or increased torque ripple. Transformers may overheat due to harmonic flux core losses. Power factor correction capacitors and other electronic equipment may receive excess currents and/or voltages. Telephone systems may get interfered with by higher order harmonics - telephone-influence factor (TIF).

Harmonics (cont.): Sources Arc furnaces Transformers Fluorescent lamps Rotating machines SCR (thyristor)-controlled devices Pulse width modulated devices Switch-mode power supplies Battery chargers Adjustable-speed drives

Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves Used for System Coordination Thermal Damage Curve Decrement Curve Reactive Capability Efficiency Parallel Operation

Circulating Currents When Paralleling Circuit diagram is of two generators in parallel. When there are differences in specific harmonics (3rd harmonic in this diagram) then circulating currents will flow through the generators + Ic + _ V 3A X o A _ V 3B X o B I C = V 3A -V 3B 3 (X 0A + X 0B ) V 3 is L-N third harmonic voltage. X 0 is zero-sequence reactance of each source (including external grounding reactance).

Circulating Currents When Paralleling For non-2/3 pitch generators, the key harmonic is the third The difference in third harmonic voltage is the driving force behind circulating currents. It flows in neutral and can cause false tripping of the differential protection relay and other problems. The grounding method used can greatly decrease current magnitudes. Identical generator pitch does NOT guarantee successful parallel operation. + Ic + _ V 3A X o A _ V 3B X o B

Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves Used for System Coordination Thermal Damage Curve Decrement Curve Reactive Capability Efficiency Parallel Operation

Reactances Reactance is the opposition to AC current flow (like resistance, but recall that there are more than just simple toasters in power systems). Reactances are used to describe the behavior of a generator during certain operating conditions. X d is used in motor starting calculations. - lower X d results in better motor starting (i.e. lower voltage dip). X d is used in short-circuit current and arc flash calculations. - lower X d results in higher short circuit currents. There are other reactances for different situations. - e.g. direct and quadrature axis, zero and negative sequence, saturated and unsaturated.

Reactances (Cont.) Test method to obtain X d, X d: Machine operating at rated voltage, no-load, manual excitation Short circuit is applied across all three phases simultaneously Current envelope in each phase is captured over time as it decays Sample data

Time Constants Time constants characterize the length of time that currents flow during a specific instant in time of a given configuration. The two most common are the subtransient time constant T d and the transient time constant T. Sub-transient time constant T d determines length of time sub-transient (damper) current flows. Transient time constant T d determines length of time transient current flows.

Time Constants

Time Constants (cont.) Another time constant example: Open circuit transient T d0. This represents the decay in armature output voltage when main field excitation is lost This requires a different test setup than previously mentioned time constants: slip rings to manually control the main field.

Reactances, Time Constants: Why are they Important? Very useful to predict performance in large system simulations because they simplify and speed up calculations. Now, for many users, the reactances and time constants are plugged into simulators used for system modeling and coordination studies. Generator manufacturers use this information to produce three curves commonly used for system coordination: Thermal damage curve Short-circuit decrement curve Reactive Capability

Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Two Generator Curves Used for System Coordination Thermal Damage Curve Decrement Curve Reactive Capability Efficiency Parallel Operation

Thermal Damage Curve Plot of armature current vs. time for the class of insulation provided. Sample damage curve for a Class-H insulated, Class F rise machine.

Short-Circuit Decrement Curve Plot of fault current vs. time that the generator produces for various fault conditions. 25.00 20.00 3PH, SYM, NL, MAN, HOT PER UNIT LINE CURRENT 15.00 10.00 5.00 3PH, SYM, NL, REG, HOT 3PH, ASYM, FL, REG, COLD L-L, SYM, NL, MAN, HOT L-L, ASYM, FL, REG, HOT L-N, SYM, NL, MAN. HOT L-N, ASYM, FL, REG, HOT 0.00 0.001 0.010 0.100 1.000 10.000 TIME IN SECONDS

Reactive Capability Curve 3000 Inductive Load Capacitive Load 2000 1000 Leading -- Reactive Load kvar -- Lagging 0-1000 -2000-3000 (Power Factor) 0.4 0.6 0 500 1000 1500 2000 2500 3000 0.4 0.6 Power (kw) 0.7 0.7 0.8 0.9 0.9 0.8 Limited by rotor heating Limited by stator heating Limited by control stability Limited by dynamic stability

Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves Used for System Coordination Thermal Damage Curve Decrement Curve Reactive Capability Efficiency Parallel Operation

Efficiency Ratio of electrical energy output against the required mechanical energy input. Usually expressed as a percentage and always less than 100 percent. Usually improves with increasing sizes. For a 5 kw output, a typical efficiency is about 80%. For a 500 kw output, efficiency is typically 93% or better. Reduced by losses: Fixed losses (independent of load current) Variable losses (directly proportional to load current)

Efficiency: Fixed Losses Fixed losses Friction and windage losses: Bearing friction and wind resistance spinning rotor and associated fans Reduce by optimizing fan blade pitch Laminated core losses: Hysteresis Heat losses in the stator core due to change in magnetic flux flow Reduce by using low-loss silicon steel Eddy-current losses Loses due to induced current in the stator core Reduce by using low-loss silicon steel

Efficiency: Variable Losses Variable losses I 2 R losses in the armature and field coils Losses in the form of heat due to resistance in the windings Main armature I 2 R losses can be reduced by using insulation with higher dielectric strength and adding more copper. Main field I 2 R losses can be reduced by controlling the load power factor and reducing excitation requirements. Brushless exciter losses are typically negligible. Stray losses Due to changes in the flux distribution, eddy currents, and highorder harmonics. Can be reduced by using higher cost materials for the lamination clamping plates and stranding the armature copper into thinner cross sections.

Efficiency: Example Assume a generator is 90 percent efficient; that means if 1000 kw is applied to the generator shaft, only 900 kw can be extracted as electrical energy. The prime mover must provide the real power of the alternator. One horsepower is equal to 0.746 kw. So, for a generator to deliver 900 kw of three-phase power at 90% efficiency, a prime mover with the following horsepower is required (no capability for overload is included): 900 kw = 1340 HP 0.9 efficiency x 0.746 kw per HP

Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves Used for System Coordination Thermal Damage Curve Decrement Curve Reactive Capability Efficiency Parallel Operation

Parallel Operation: Basics The generators share the power needed by the load. The operating points will depend on the load and set ups Why? To increase the power of an installation, To add flexibility, reliability or dependability. G1 Load G2

Requirements Must have +/- the same Frequency Voltage Phase angle Phase sequence The voltage regulator must have parallel operation capability and fitted with a paralleling CT or be controlled by a bias signal coming from the genset controller. The active and reactive power sharing must be balanced or prorated if they are of different sizes.

Metering Required V A kw Volts 60 Amperes Watts Hz Frequency Cos ᵠ or A PF or exciter field current

Synchronizing Parameters: Frequency 100 0 DF = +/- 0.2% Ex. For 60 Hz: Period min = 16.67 ms Period max = 16.70 ms (Speed must be practically equal!) -100 t Maximum frequency shift: ± 0.12 Hz

Synchronizing Parameters: Voltage 150 %(Un) 100 U 50 0 0 10 20 30 40 50 60-50 -100-150 t Maximum voltage difference: ±5%

Synchronizing Parameters: Phase 125 100 75 50 25 %(Un) 0-25 0 10 20 30 40 50 60-50 -75-100 -125 t Maximum phase offset: ±10

Synchronizing Parameters: Phase Order Clockwise rotation from drive end Generator terminals U1 -V1 -W1 T1 -T2 -T3 Network connections L1 - L2 - L3 U2 V2 W2 CCW rotation From drive end Generator terminals U1 -V1 -W1 T1 -T2 -T3 Network connections L3 - L2 - L1 U2 V2 W2 U1 V1 W1 U1 V1 W1 L1 L2 L3 L3 L2 L1

Sequence 1. Verify the wiring and polarity of the sensing voltage and paralleling CT. 2. Equalize perfectly the no-load voltage of each generator. 3. Set the same droop for each generator. 4. Run the generators at the same voltage, phase sequence, frequency and phase angle. 5. Monitor the meters as you close the breaker and open it if the Amp meter fluctuates wildly. 6. After closing the breaker, adjust the engine governors per their power. 7. Ensure the reactive power of identical sets is roughly the same without any voltage adjustment.

Summary When an generator is running in island mode supplying power to a load or a factory, there is no requirement to synchronize it. The engine will regulate the RPM or the frequency and voltage regulator will regulate the voltage and the load connected will dictate how much power is drawn. When more than one generator run together or with the utility, it is necessary to synchronize them together. In order to synchronize one generator with another unit or with the mains, both sinusoidal wave forms must match. Any greater-than-rated difference could damage the generator to be synchronized.