USER S MANUAL. Manual for Panel Mount Process Indicator. HTA INSTRUMENTATION (P) LTD. Your One Stop for Instrumentation, Calibration & Service

Similar documents
AI-501 INTELLIGENT INDICATING/ALARMING INSTRUMENT. Operation Instruction

AI-700 / 500 INTELLIGENT INDICATING/ALARMING INSTRUMENT. Operation Instruction

ONEXIS AUTOMATIONS PVT LTD B-8, First Floor, Industrial Area, Sector - 64, NOIDA , U.P, India Ph:

APPENDIX APPENDIX A 1

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition

4-20mA, 0-10V and general process measuring bargraph displays

Micro-controller X Model: PXE4. Operation Manual. INP-TN5A1887a-E

R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY

Digital indicator for panel mounting With multi-function input Model DI25

PID CONTROLLERS LT SERIES

T E L I S T E L I S reinvents conversion and transmission of measures

UL CONDITIONS OF ACCEPTABILITY

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION

General Specifications

RS232 CONTROLLER/MONITOR

7 Function description 7.1 Digital filter Alarm output

Digital Temperature Controller

DIN rail mounting temperature controller with current transformer input deltadue series D1 line

PROCESS & TEMPERATURE CONTROLLERS

MICRO-CONTROLLER X (48 48 mm)

HUMIDITY/TEMP. CONTROLLER/MONITOR

General Specifications

K3P ENG.qxd 23/10/ Pagina 1

Fuzzy Temperature Controllers E5AF

DPF-MAC Auto power factor controller

SYL-2352P Ramp and Soak PID Temperature Controller Version 1.2 (May 2016)

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

Conductivity Transmitter N-LF V AC

GL102 Intelligent Temperature Controller User s Guide

SHIMADEN PROGRAM CONTROLLER

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE

INPUT RESISTANCE OR CLAMP VOLTAGE. 2 Years 23 C ±5 Voltage mv 3 10 nv > 10 G

General Specifications

General Specifications

JUMO Wtrans Receiver with Wireless Data Transmission

SR25. SHIMADEN DIGITAL CONTROLLER Shimaden, Temperature and Humidity Control Specialists MICROPROCESSOR-BASED AUOT-TUNING PID CONTROLLER

FC-33, DC SELECTABLE SIGNAL CONDITIONER

DRG-SC Series Signal Conditioners

Fuzzy Temperature Controllers E5EF

Temperature Controller


General Specifications

CALYS Transportable documenting multifunction calibrator with high accuracy 0.01%

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

Non-Submersible Industrial Pressure Transducer

Delta Temperature Controller DT Series

High Performance Process & Temperature Controllers

Users manual. Ht40A. User - friendly programmable controller. HTH8 s.r.o. Ht40A, 08/03, soft 4.03/rev. 2

1 INTRODUCTION ORDER CODE / INFORMATION

JUMO Wtrans Receiver Universal Receiver for JUMO Wireless Measuring Probes

MPS SERIES. INSTALLATION and TECHNICAL MANUAL MPS 4 MPS 5 MPS 9 4 PV

1000TR. Instructions

Contents. English User Manual Regulators

High-precision process calibrator Model CED7000

Series F4P Communications Guide

Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems

N1040i Indicator. UNIVERSAL INDICATOR INSTRUCTIONS MANUAL V1.0x D PRESENTATION FEATURES

BATCHMATE 1500 Batch Control Computer Technical Bulletin

C C1 C2 AL1 AL2 AL3. Micro-controller X. Model: PXR SEL PXR-4. Operation Manual. ECNO:406a

Detcon Model FP Transmitter Test Fixture Operators Instruction Manual June 17, 2008 * Document 3389 * Revision 1.1

Digital Meters With A Multicolour Bargraph LEL-NA3 one-channel LEL-NA5 one-channel LEL-NA6 two-channel

ZHUHAI PILOT TECHNOLOGY CO., LTD.

RESTRICTED EARTH FAULT RELAY

ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI-208. User Manual

General Specifications

Process Meter. Applicable

GL101B Intelligent Temperature Controller User s Guide

96M0374. Instruction Manual. Analog Sensor Controller. RD Series

Agenda. At the end of this presentation, you will: 1. Know what is a temperature controller. 2. Why do we launch this offer?

DOCUMENTATION. Its affordable price allows you to meet your budget target.

Excellent low-cost Process & Temperature Controllers

CompoBus/D-type Digital Controller

User Manual Universal Process Indicator

DOCUMENTATION. The new XALIS 9000 integrates a 32 bits microprocessor offering some more of performance.

Process controller Setpoint programmer 1/16 DIN - 48 x 48 mm gammadue series M5 line

Economical Digital Indicators For Process and Electrical Measurement

Monitoring Relay MR 50

g GE POWER MANAGEMENT

Module Input type Ranges TEDS Filters (LP = lowpass, HP = highpass) Piezoresistive bridge ±0.5 to mv/ma 1 ma exc

Fuji Electric Instruments Co.,Ltd

CONTA-ELECTRONICS. Converter Units

Data Acquisition Modules/ Distributed IO Modules

C4000. inline control. Photometric Converter. Real-time photometric converter. Factory zero for scattered light sensors

Basic module X-TIO FAIL/RUN RX/TX EVENT1 EVENT2 EVENT3 EVENT4 X10 FAIL/RUN RX/TX EVENT1 EVENT2 EVENT3 EVENT4 X10. Communications (RS-485)

MULTIFUNCTION GRAPHICAL UNIT MGU 800

PANEL MOUNT PROCESS METER IDP

PM8005/6 PM8005/6. Panel Meter Panel Meter. AC and DC supply options. 5 digit LED display. Direct access menu

5520A. Multi-Product Calibrator. Extended Specifications 2005

TRANSDUCER of TEMPERATURE and STANDARD SIGNALS P20 type

DC1010/DC1020/DC1030/DC1040

- SMART TUNE - PID CONTROL - UNIVERSAL, 3 WIRE - TC, RTD AND LINEAR INPUT - 2 INDEPENDENT SET POINT RAMP UP/ DOWN PROFILES - SERVO VALVE POSITIONER

Installation, Operation and Maintenance Manual

Universal Alarm Indicator

LAUREL ELECTRONICS, INC.

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

PROGRAMMABLE CONTROLLER

Micro-controller X SV C1 C2 AL1 AL2 SEL. Model: PXR3. Operation Manual TN5A2704-E

PM-311x Quick Start Ver PM-311x introduction 1.1. Caution & Warning 1.2. Product Warranty & Customer Support

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16

Transcription:

Member of SN Registrars (Holdings) Ltd 8327 USER S MANUAL Manual for Panel Mount Process Indicator EQ-DS8B-IRRB EQ-DS8B-IRRB HTA INSTRUMENTATION (P) LTD. Your One Stop for Instrumentation, Calibration & Service # 73, Ramachandra Agrahara, Near T.R. Mills, Chamarajpet, Bangalore - 56008, INDIA Phone: 080-26749750, 26759253, 2675379 Fax: 080-2674068 Website : www.htaipl.com E-mail : sales@htaipl.com ISO900:205 ISO 900:205 CERTIFIED Page - /

<< Applications The Instrument can measure any range of Current or Voltage signal input. The user can select data remained or top value remained. The instrument can be use with 2 wire transmitter, Pressure Sensor, 4 wire weight Sensor and so on. For Nonlinear input, the instrument can process for 20 stages. As well the instrument can be with RS485 communication. The input, output and the power supply is isolated. Name of Parts 2. When used with Pressure sensor. The Instrument can supply DC2V auxiliary power & the sensor output is 2mV/V. Select input signal mv. 2 90~260V AC 6 3. When used with Ohm meter. Input 0-400Ù Select input signal rt. 8 24V+ 8 Gnd +mv 20 PV SV <</RST V(mV) AL Ù(ºC) AL2 V (ma)al3 << Malfunction Estimate:. No Display : Check all the connection & wiring if it is correct. Specially pay attention to the power supply terminals & signal input terminals, please do not wrong connect. As well pay attention to do not short the output terminals by strong current. 2. Wrong Display : Check it the PVF=0.00 Check if the input signal is conformity with the selected symbol. For RTD input, please use low impedance cable. The 3 wire should at the same length. 3. Wrong Control : When the instrument lost control, please check if the output diagram connection is correct. Or check if the components for output part damaged. 4. UUUU, LLLL : When the instrument displays "UUUU", it means the input signal exceeds the measured Usp range. When the instrument displays "LLLL", it means the input signal lower the measured Lsp range, or input signal terminal connection is Measured Value (PV) / Various Parameter Symbols Parameter Value / Rate Value / ct / AL Indication Lamps for Alarm V(mV) AL ON : Output OFF : No Alarm Indication Lamps for Alarm 2 Ù (ºC) AL2 ON : Output OFF : No Alarm Output Unit Indication Lamp / Alarm 3 (ma) Select / Confirm Key Shift / Clear / Reset Key Up Key Down Key 2 Page - 02/ V 9 20 R 90~260V AC 2 Page - /

Diagram Connections : * Please subject to the diagram on the product if any changes Application Examples. When used with 2 wire Transmitter. The Instrument can supply DC 24V auxiliary power, and isolate analogue output 4 ~ 20mA. Select input signal ma. 90~260V AC 2 6 7 4~20mA +24V 8 24V 0 9 + ma 7 Gnd 8 Page -0/ Input Signal Specification: Input Signal Types A(AA/DA) ma V(AV/DV) mv Rt Pt TC Range 0~5A, 0~2A 0~mA, 0~0mA, 4~20mA 0~5V, 0~0V, 0~500V 0~0mV, ±00mV 0~400, 0~0K Cu50, Cu00, 50~50 C 200~650 C K : 0~320 C J : 0~300 C E : 0~000 C T : 50~400 C B : 0~820 C R : 0~700 C S : 0~600 C Input Impedance CT configurable 3 50 200K 2M 0.2mA 0.2mA 2M Factory Setting Indicate when order 4~20mA DC 0~0V 0~75mV 0~400 Indicate when order Pt00 High Voltage / Current Input or data remained function need special order. Al3 also can be use as analogue output, but you can select only one of them. but not both Non-Linerar Input need special order EQ - DS8B Ordering Code EQ-DS8B I R R R 4 B Default : Input signals : ma, V, mv, rt and pt for option Auxiliary Power Supply : A : DC +2V / 30mA B : DC + 24V / 30mA Communication : Non : No communication 2 : RS232 4 : RS485 AL3 : R : Relay S : SSR / Logic T : SCR N : No Alarm AL2 : R : Relay S : SSR / Logic T : SCR N : No Alarm AL : R : Relay S : SSR / Logic T : SCR N : No Alarm Analogue : Default : No Analogue I : DC 0 ~0mA or DC 4 ~ 20mA Power Supply : Default : AC 90 ~ 260V 50 / 60Hz E : DC 24V DS8B Series of process Indicator Size : 48H x 96W X80L K Page - 03/

Specifications : Power Supply : 90~260V AC or 8-30V AC/DC Consumption : 5VA Accuracy : 0.3% F.S. ± 2 digit Sampling Rate : 8 Times / Second Alarm Relay : NO AC 250V/3A or DC 30V /3A cos = Input : Refer the input signal selection Analogue : 0-0V or 4-20mA, free set for control O/P Range by software Auxiliary Power : DC 2 / 24V / 30mA Communication : RS232 or RS485 (Optional) Dimensions : Analogue Low Value Setting Range : LSP brl USP Analogue High Value Setting Range : LSP brh USP Baud Rate select :9 2K Bit/ s 2/3 (reserve) Factory Setting = 9.6Kbit/s 96 84 Communication Address Selection Range : 000~255 48 46.5 F/C NO= º C Yes = º F 9 +0.5 0 30 Parameter Lock 46 +0.5 0 25 96W 48H 84L 4 Page -04/ 9 Page - 09/

<< Press / V key for more than 3 seconds. can enter / quit from the V second grade parameters setting Input Signal Selection : ma V mv Rt Pt Tc Low Display Setting Range : 999~9999 Input High Display Setting Range : 999~9999 Parameter Setting :. Alarm Setting : In the displaying estate, press and hold key for more than 3 seconds, enter alarm mode parameters setting menu. Press << / RST key. LED flashes. Press / key to modify, and then press key to confirm. Press key to read the following parameters one by one. 2. Rate Setting : In displaying estate, press <</RST key and LED flashes, then you can modify the value by Up and Down key. The factory setting is.00. Once the user want to set it to be other value, then PV=Rate (USP-LSP) + LSP USP means Up limit, LSP means Down limit. << Decimal Point Setting : 0~3 Stands for 0000, 000.0, 00.00 and 0.000 AL Hysteresis Range : ± 50.0 AL2 Hysteresis Range : ± 50.0 AL3 Hysteresis Range : ± 50.0 3. Zero Point Clear : In the displaying estate, without key operation, when the input zero point, press and hold <</RST key for more than 2 seconds. It is for the sensor zero point clear. 4. The instrument will return to the measuring estate without any operation for 25 seconds. Special Function : The instrument can be input by up to 2 signals, the up and down LED can display the measuring value. The instrument can calculate the two input value, so it also can be used as a watt meter. 8 Page -08/ 5 Page - 05/

Operation Process : Power ON Alarm 2 Setting, Range LSP AL2 USP All LED on Alarm 2 Mode Setting H : High L : Low Input Signal Type Alarm 2 Hysteresis Value Setting Range : ±50.0 Up limit Down limit PV display Rate Setting Alarm 3 Setting, Range LSP AL3 USP Alarm 3 Mode Setting H : High L : Low Alarm Parameter Setting Alarm 3 Hysteresis Value Setting Range : ±50.0 >3S Measuring Display Rate Setting Offset Value : Display = PV PVF : ± 50 Alarm Setting Range LSP AL USP Alarm mode Setting H : High L : Low Alarm Hysteresis Value Setting. Range : ±50.0 Offset Value : Display = PV PVF : ± 50 Parameter Lock password LCK=000 means the parameter can be modified LCK=00 is for read only 6 Page -06/ 7 Page - 07/