ELECTRICAL POWER TRANSMISSION TRAINER

Similar documents
ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

148 Electric Machines

Protection of Electrical Networks. Christophe Prévé

MV network design & devices selection EXERCISE BOOK

Transformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Substation applications

Hours / 100 Marks Seat No.

Power systems 2: Transformation

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

2 Grounding of power supply system neutral

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

In Class Examples (ICE)

Earth Fault Protection

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

IVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc.

AEL-TI-01. Analysis of Three-phase Power Lines Application INTRODUCTION. Configuration example of AEL-TI with AEL-TI-01 application included

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Notes 1: Introduction to Distribution Systems

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM I (EE, EN, EC, CE)] QUIZ TEST-3 (Session: ) Time: 1 Hour ELECTRICAL ENGINEE

Digital Fault Recorder Deployment at HVDC Converter Stations

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

ECE 421 Introduction to Power Systems. Lab 02 Power System Feeding Different Loads

Experiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE

G. KOEPPL Koeppl Power Experts Switzerland

Look over Chapter 31 sections 1-4, 6, 8, 9, 10, 11 Examples 1-8. Look over Chapter 21 sections Examples PHYS 2212 PHYS 1112

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

High voltage shunt capacitor banks HIGH VOLTAGE COMPENSATION AND HARMONIC FILTERING PRODUCTS

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

Fatima Michael college of Engineering and Technology

AC Power Instructor Notes

Y-0035 POWER ELECTRONICS TRAINING SET

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

N. TEST TEST DESCRIPTION

, ,54 A

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

Electricity Fundamentals Training System

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

TRANSFORMER OPERATION

A 11/89. Instruction Manual and Experiment Guide for the PASCO scientific Model SF-8616 and 8617 COILS SET. Copyright November 1989 $15.

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly

The power transformer

Line protection with transformer in the protection zone

Question Paper Profile

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

EXPERIMENT 1 TITLE: SINGLE PHASE TRANSFORMERS - TRANSFORMER REGULATION

Short Circuit Current Calculations

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Impact Assessment Generator Form

Capacitor Switching Contactors

ENCORE 300 SERIES INSTALLATION AND OPERATING INSTRUCTIONS

Industrial Electrician Level 3

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

Downloaded from / 1

Note: 1. All the students must strictly follow all the safety precautions. 2. In case of any question or concern, please contact LAB INSTRUCTOR or TA.

Universal Protective Relay Test Set

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

INTEGRATED TRANSMISSION PLAN Glossary

Back to the Basics Current Transformer (CT) Testing

EH2741 Communication and Control in Electric Power Systems Lecture 2

EASUN REYROLLE LIMITED

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Power. Power is the rate of using energy in joules per second 1 joule per second Is 1 Watt

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Embedded Generation Connection Application Form

Low Voltage Products. Third Harmonic Filter THF and THF star System components for assembly and retrofitting. Catalogue THFS2GB 03_05 1SCC330004C0201

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

AC Power Transmission Training System Add- On to ( )

Design a Power System Simulator Model and Implement the Generator and Motor Controlling

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

Preface...x Chapter 1 Electrical Fundamentals

STS Fully automatic. Large graphic display. Primary injection testing capabilities: up to 3000 A, with the optional module BUX 3000

Electromagnetic Oscillations and Currents. March 23, 2014 Chapter 30 1

Electrical Workstation Nvis 7089A

The CABLETROLL 3600 FCI is capable of discriminating between PTP and PTG faults, and indicating the direction of the latter type.

Fault Analysis of ITER Coil Power Supply System

AEL-TI-05. Parallel and Series Transmission Lines Application INTRODUCTION. Configuration example of AEL-TI with AEL-TI-05 application included

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009

3Ø Short-Circuit Calculations

Improving High Voltage Power System Performance. Using Arc Suppression Coils

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

86 chapter 2 Transformers

Electrical And Electronics Engg

Power Quality enhancement of a distribution line with DSTATCOM

1. THREE-PHASE TRANSFORMER. SHORT CIRCUIT TEST

1. General Instructions 2 2. Safety 2 3. Lamp Starting Test Instrument LSTI 5 3

Installation/operation instructions. Insulation monitor type SIM-Q/SIM-Q LF D (UK) Measuring range 1...0Mohm or 10...

Chapter 7 Conclusion 7.1 General

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Transcription:

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation of the various subsystems forming a complete electrical power system, from power generation to energy utilization. High voltage components have been scaled down for obvious reasons: a real 380 kv power transmission line is represented by a 380 V line in the laboratory. However, the same low voltage industrial equipment which is normally used in real systems has been used also in this laboratory, whenever this was feasible. Page 0 of 9

Page 1 of 9 POWER TRANSMISSION AND DISTRIBUTION The major advantage of ac and three-phase technology over dc technology is that the electrical power is generated economically in large power stations relatively far from the end users, transported at high voltage over long distances with very little power loss and finally made available to the consumers the way they need it. This is possible only by using transformers. In this laboratory a three-winding transformer is investigated. It consists of three individual poles with different connection possibilities on the primary side and variable secondary voltage. The third winding (tertiary winding) is designed as the delta stabilizing winding needed for asymmetrical loads. Overhead power lines are mainly used to transmit electrical energy from the power stations to the consumers. However, in densely populated areas the power can only be supplied via cables. Also busbars, disconnectors, power circuit breakers, voltage and current transformers are studied; these, in fact, are among the most important components of a switching station. EXPERIMENTS Three-Phase Transformer Experiments Determination of the vector group of the three-phase transformer. Determination of the voltage transformation ratio of the transformer operating at no-load. Determination of the current transformation ratio of the transformer operating with short-circuit. Determination of the equivalent circuit quantities based on the consumed active and reactive power. Measurement of the effect of the load type and magnitude on the performance of the secondary voltage. Determination of the efficiency of the transformer. Investigation of the zero-impedance of the three-phase transformer with various connection modes. Examination of the load capacity of the secondary side using a single-phase load with different connection modes on the primary side. Determination of the influence of a delta stabilizing winding. Demonstration of the possibility of utilizing a three-phase transformer in economy connection (auto-transformer).

Page 2 of 9 EXPERIMENTS Overhead Line Model Experiments Measurement of the voltage in no-load operation. Concept of operating capacitance. Line model with increased operating capacitance. Measurement of current and voltage relationship of an overhead line in matchedload operation, interpretation of the terms: characteristic wave impedance, lagging and leading operation, efficiency and transmission losses. Measurement and interpretation of the current and voltage ratios of a transmission line during a three-phase short-circuit. Measurement and interpretation of the current and voltage ratios of a transmission line with mixed ohmic-inductive and pure inductive loads. Measurement and interpretation of the current and voltage ratios of a transmission line with mixed ohmic-capacitive and pure capacitive loads. Investigation on the performance of a transmission line with isolated neutral point connection in the case of a fault to earth. Measurement of the earth-fault current and the voltage rise of the fault phases. Determination of the inductance of an earth-fault neutralizer for the overhead line model. Investigation on the performance of a transmission line with a fault and comparison of the current values with those determined during earth-fault with isolated neutral point system. Measurement of the fault currents of the results with those for a three-phase fault. Investigation on the effect of parallel compensation on the voltage stability at the load and the transmission losses of the line. Investigation on the effect of series compensation on the voltage stability at the load. Use of measurement techniques to determine the zero-phase sequence impedance of the overhead line model and comparison of this value with the theoretical one. Series and Parallel Connections of HV Lines Measurement of the voltage distribution in the series connection of two lines without operating capacitance. Measurement of the voltage distribution in the series connection of two lines with operating capacitances. Measurement of the voltage distribution in the parallel connection of two lines without operating capacitances. Measurement of the voltage distribution in the parallel connection of two lines with operating capacitance.

Page 3 of 9 EXPERIMENTS Busbar System Experiments Operation of a switching station with two bushars and different voltage. Busbar transfer with interruption of the power supply to the consumer. Busbar coupling and bus transfer without interruption of the power supply to the consumer. Switching sequence for disconnectors and power circuit breakers.

Page 4 of 9 Summary of Modules Required for all above Experiments Sr. Item Name Model No. Qty No. 1 Variable Three-phase power supply EST-1013T1 1 2 Overhead line model EST-7901TT 2 3 Three-phase transformer EST-1080TT 1 4 Resistive load EST-1017R 1 5 Inductive load EST-1017L 1 6 Capacitive load EST-1017C 1 7 Three-phase power supply EST-2108TAL 1 8 Power circuit breaker EST-2108T02 4 9 Double busbar with two disconnections EST-2108T02/2 1 10 Double busbar with four disconnections EST-2108T02/4 1 11 Line capacitor EST-2108T03 2 12 Petersen coil EST-2108T04 1 13 Digital ammeter (1000mA) EST-2109T1A 1 14 Digital ammeter (2.5A) EST-2109T2A5 3 15 Digital voltmeter (600V) EST-2109T1PV 2 16 Digital voltmeter (125-250-500V) EST-2109T3PV 3 17 Digital Power meter EST-2109T26 2 18 Digital Power factor meter EST-2109T27 1 19 Connecting Leads 1 set 20 Two level Frame with table 1 21 Experimental Manuals 1 set

Page 5 of 9 MODULES SPECIFICATIONS Note: Every effort has been made to ensure that the information contained in this catalogue is accurate; however no labiality is accepted for errors. Should an error be discovered please inform the company in writing, giving full details. All modular images given are for guidance only and are not guaranteed as exact supplied they may have different shape components and parts according to the market availability. Variable three-phase power supply (EST- 1013T1) Line model (EST-7901TT) Power supply unit for variable 3-phase voltage suitable for supplying AC machines. 16 A, 30 ma differential magneto-thermal main switch key operated emergency push-button start and stop push-buttons motor protection circuit breaker: 6.3 to 10 A digital ammeter and digital switchable voltmeter ac output: 3 x 0... 380 V, 8 A The output voltage is set by a rotary knob with 0-100% scale. Supply voltage: three-phase from mains. Three-phase transformer (EST-1080TT) Three-phase model of an overhead power transmission line 360 km long, voltage 380 kv and current 1000 A. Scale factor: 1:1000 Line resistance: 13 Ω Line inductance: 290 mh Mutual capacitance: 1 μf Earth capacitance: 2 μf Earth resistance: 11 Ω Earth inductance: 250 mh Resistive load (EST-1017R)

Page 6 of 9 Three-phase transformer for feeding a transmission line model 380 kv with scale factor 1:1000 Primary: 3 x 380 V windings with tap at 220 V star or delta connection Secondary: 3 x 220 V windings with taps at +5%, - 5%, -10%, -15% star connection for 3 x 380 V various star connections possible rated power: 800 VA Tertiary: 3 x 220 V windings delta connection for stabilizing the third harmonic voltage components rated power: 266 VA Composed of three resistances, with possibility of star, delta and parallel connection, controlled by three switches with seven steps each. Max. power in single or three-phase connection: 1200 W Rated voltage: 380/220 V Y/D Rated voltage in single-phase: 220 V Capacitive load (EST-1017C) Inductive load (EST-1017L) Composed of three batteries of capacitors, with possibility of star, delta and parallel connection, controlled by three switches with seven steps each. Max. reactive power in single or three-phase connection: 825 VAr Rated voltage: 380/220 V Y/D Rated voltage in single-phase: 220 V Composed of three inductances, with possibility of star, delta and parallel connection, controlled by three switches with seven steps each. Max. reactive power in single or three-phase connection: 900 VAr Rated voltage: 380/220 V Y/D Rated voltage in single-phase: 220 V Three-phase power supply (EST-2108TAL) Power circuit breaker (EST-2108T02)

Page 7 of 9 Power supply unit for three-phase connection with 4-pole cam mains switch. 25 A current operated earth leakage circuit breaker, sensitivity 30 ma. Triple-pole motor protection switch: 6.3 to 10 A. Three-phase indicator lamps. Output through 5 safety terminals: L1, L2, L3, N and PE. Three-phase power circuit breaker with normally closed auxiliary contact. Contact load capability: 400 Vac, 3 A Supply voltage: single-phase from mains Double busbar with two disconnectors (EST- 2108T02/2) Double busbar with four disconnectors (EST-2108T02/4) 2 Busbars for parallel lines operation Having 2 outgoing feeders for connection / disconnection Line capacitor (EST-2108T03) 2 Busbars for parallel lines operation Having 4 outgoing feeders for connection / disconnection Petersen coil (EST-2108T04) Three-phase capacitors in star connection with exactly half of the operating capability of the 380 kv transmission line model with a length of 360 km. Capacitance: 3 x 2.5 μf, 450 Vac Inductance with 20 taps for earth fault compensation in transmission lines. Inductance: 0.005... 2 H Rated voltage: 220 V Rated current: 0.5 A

Page 8 of 9 Digital ammeter (EST-2109T1A) Digital ammeter (EST-2109T2A5) AC/DC Digital Ammeter with 1A Fuse. AC/DC Digital Ammeter with 2.5A Fuse. Digital Voltmeter (EST-2109T1PV) Digital Voltmeter (EST-2109T3PV) AC/DC Voltmeter. AC/DC Voltmeter.

Page 9 of 9 Power Factor meter (EST-2109T27) Three Phase Power meter (EST-2109T29) Digital Single-phase panel meter for power factor and phase-angle of the connected load. Microprocessor controlled three-phase power analyzer. Measurement of voltages, currents, frequencies, active power, reactive power, apparent power. Input voltage: 450 V (max 800 Vrms) Input current: 5 A (max 20 Arms) Operating frequency: 47 63 Hz Auxiliary supply: single-phase from mains Connecting leads Aluminium Frame