Buck-Boost 9 0 VA to 10 Applications n A comprehensive line of transformers for low voltage applications. n Economical for stepping voltages up or down n Solve over/under voltage problems efficiently n Low voltage lighting applications n International voltage adaptation Specifications n Encapsulated with electrical grade resin n 0 Hz standard n Single-phase encapsulated isotransformer / autotransformer 0 x 0V /V 0 x 0V 1/3V 0 x 80V /8V n Three phase autotransformer configurations, using multiple single phase units n 13ºC temperature rise n 180ºC insulation class n NEMA3R-rated enclosures n Heat-cured ASA-1 gray powder coat finish n Cores of high quality electrical steel Features, Functions, Benefits n Slotted mounting holes for quick and easy installation n Convenient wall mount design with lifting hooks for units and above n NOTE: Buck-Boost transformers do not compensate for fluctuating line voltages Standards n Built in accordance with NEMA, ANSI, UL and CSA standards Options and Accessories n Other sizes, voltages available n 0/0 Hz options n Copper windings n CE Marked units available as custom Approvals Buck-Boost transformers are low voltage isolation transformers that can be connected in an autotransformer arrangement to provide a convenient and economical way to raise or lower single and three-phase voltages from -0%. The autotransformer arrangement allows smaller and less expensive Buck-Boost transformers to supply large power loads. 9-1
9- Buck-Boost Transformers Solve over/under line voltage problems efficiently and economically. Electrical equipment is manufactured to operate most efficiently when the line voltage is close to the nameplate rating of the equipment. A motor operated at a voltage substantially under its nameplate rating may run constantly on the starting windings, resulting in overheating and possible burn-out. The same motor operated at a voltage substantially over its nameplate rating is subject to excessive heat rise, often higher than the insulation temperature limits, which may eventually cause the motor to burn out. The difference between an autotransformer and an isolation transformer. In an autotransformer, the input (or primary) and the output (or secondary) are electrically connected. In an isolation transformer they are completely separated, as shown to the right. Only a portion of the electrical energy is changed in an autotransformer, the remainder flows directly between the primary and secondary. In an isolation transformer, all the energy is transformed. For these reasons, an autotransformer is smaller, lighter and less costly than a comparable isolation transformer. Autotransformer Isolation (or Insulating) Transformer Model Numbers Defined Buck-Boost Models Primary Secondary 0x0 / 0x0 1/3 0x80 /8 1 0x0 / 1 0x0 1/3 0x80 /8 Rating YY =,, 1 YY = 1,, Digit XX Digit XX 00 0.0 01 7.0 01 0.10 10.00 0.1 1 0. 31 0.0 1 0.7 1 1.00 1 1.0 71.00 81 3.00 91.00 Default 0 Copper 8 Temperature Rise 13 C 0 C 1 Shield No shield 0 Shield 1-YYXX-ABC Caution: Buck-Boost transformers will not compensate for fluctuating line voltages. They should only be used when line voltage is relatively constant. Jefferson Electric Dry-Type Transformers jeffersonelectric.com 800-89-37
Buck-Boost Transformers 9-3 How to Use the Buck-Boost Rapid Selector Charts You will need the following information: Line voltage: This can be determined by measuring the supply line voltage with a voltmeter. Load voltage: The voltage at which your equipment was designed to operate. Usually listed on the equipment nameplate. Load or load amps: One of these will usually be listed on the nameplate. You do not need both. Supply line and equipment frequencies: This will be either 0 or 0 Hertz. The supply line frequency must be the same as the frequency of the equipment to be operated. Supply line and equipment phase: Either single-phase or three-phase. The line phase must be the same as the equipment. The type of electrical configuration: Delta or Wye. Follow These Five Easy Steps: 1. Find the appropriate single-phase, three-phase delta or three-phase wye table.. Read down the voltage column and find the nearest ratio of required load voltage to line voltage for the application desired. (High and low voltage may be either input or output voltage depending on the circumstances.) 3. Reading horizontally across the line beginning with your application voltage ratio, locate in one of the columns a capacity equal to or larger than your load requirement.. Note the two digit number at the top of the column listing the capacity you require.. In the catalog number column, add these two digits to the catalog number next to the voltage ratio you found in step one. Example: Assume the following information 1. A reasonably constant line voltage of 0 volts.. A required equipment voltage of 80 volts. 3..0 load capacity needed.. Single-phase line and equipment. In the voltage column, 37 is closest to our line voltage of 0. The 80 high voltage meets our requirements exactly. Reading horizontally across this line, find 30.0, the closest larger to our required.0. Going to the very top of this column, take the two digit number, 81, and add it on the end of the catalog number on the same line as our high/low voltage. The catalog number 1-1, with 81 added on the end, is 1-181.
9- Buck-Boost Transformers Single-phase capacity of encapsulated Buck-Boost autotransformers Maximum load capabilities Low (LV) High (HV) Catalog Number Load Required 01.100.10 1.0 Enclosure Figures Use Figure Use Figure 3 9 0 1-XX 100 0 1-XX 10 0 1-XX 109 0 1-XX 0 13 1-XX 0 13 1-XX 0 1 1-XX 0 1 1-XX 00 0 1-1XX 08 3 1-XX 0 1-XX 08 30 1-XX 18 0 1-XX 0 1-XX 30 7 1-1XX 0 1-XX 0 1-XX 0 7 1-XX 0 88 1-1XX 37 80 1-1XX 7 80 1-1XX 80 0 1-1XX 80 8 1-1XX 31.00 1.70.37..9 1.8.8 3.7. 7.. 18.8 AMPS 3.9.93 9.89 19.7 9. 39. 9.3 79.1 8 197.0.7 1..0 3.7.0 7. 10.0 1.0.0 AMPS.0 7...0 37.0 0.0 7.0 100 10 0.7 1. 1.87 3.7. 7.. 1.0. 37.0 AMPS 7.07 10. 17. 3.9.8 70.7 10 39 1.00 1.0.0.0 7. 10.0 1.0 0.0 30.0 0.0 AMPS 9.17 13.7.9.8 8.8 91.7 137 183 7 8 1.10 1..7. 8..0 1..0 33.0.0 AMPS 9.17 13.7.9.8 8. 91.7 137 183 7 8.8 1.7...3 8..7 17.0..0 AMPS 7.08 10. 17. 3.0. 70.8 10 30.0.90 1.0 3.0..0 9.0.0 18.0 30.0 AMPS.0 7...0 37. 0.0 7.0 100 10 0.7.71 1.18.3 3..7 7.1 9. 1. 3.0 AMPS 3.91.91 9.83 19.1 9.1 39.1 9.1 79.1 8 191.0.7 1.. 3.7.0 7. 10.0 1.0.0 AMPS.0 3.7.. 18.7.0 37. 0.0 7.0.7 1.10 1.8 3.. 7.3.0 1.7.1 3.8 AMPS 3.3.8 8.8 17.. 3.3.8 70.7 10 17.7 1. 1.87 3.7. 7.. 1.0. 37 AMPS 3.3.8 8.8 17.. 3.3.8 70.7 10 17.9 1..3.7 7.1 9. 1.3 19.0 8. 7. AMPS.8.88..9 3..8 8.8 91.7 137 9 1.00 1...0 7. 10.0 1.0 0.0 30.0 0.0 AMPS.8.88..9 3..8 8.8 91.7 137 9 1.. 3.7 7.. 1.0. 30.0.0 7.0 AMPS. 10.0 1. 33.3 9.7. 100 133 00 333.7.8 1.3.8.3.7 8.. 17. 8.7 AMPS.0 3.7.. 18.7.0 37..0 7.0.1 3.1. 10. 1.7 1.0 31..0 3.0 10 AMPS 8.7 13.1 1.8 3.7. 87. 131 17 37 1.1 1..7. 8..0 1..0 33.0.0 AMPS.8.87..9 3.1.8 8.7 91. 137 9.8 1.7...3 8..7 17.0..0 AMPS 3..9 8.83 17.. 3..9 70.8 10 17.0.90 1.0 3.0..0 9.0.0 18.0 30.0 AMPS. 3.7.. 18.7.0 37. 0.0 7.0 1.00 1.0.0.0 7. 10.0 1.0 0.0 30.0 0.0 AMPS.8 3.3.7. 17.1.8 3.3.7 8..0 3.0.0 10.0 1.0 0.0 30.0 0.0 0.0 100 AMPS.37. 10.9 1.8 3.8 3.7. 87. 131 18.1 3.1. 10. 1.7 1.0 31..0 3.0 10 AMPS.37. 10.9 1.8 3.8 3.7. 87. 131 18 1.1 1..7. 8..0 1..0 33.0.0 AMPS.9 3.3.7. 17.0.9 3.3.8 8.7 1 1 1.0 1 1. 71.0 81 3.0 91.0 1 1 1 1 3 3 3 3 3 Jefferson Electric Dry-Type Transformers jeffersonelectric.com 800-89-37
Buck-Boost Transformers 9- Three-phase capacity of encapsulated Buck-Boost autotransformers connected in open-delta Maximum load capabilities requiring two Buck-Boost Transformers Low (LV) High (HV) Catalog Number Load Required 01.100.10 1.0 Enclosure Figures Use Figure Use Figure 3 00 0 1-1XX 08 3 1-XX 0 1-XX 08 30 1-XX 18 0 1-XX 0 1-XX 9 0 1-XX 30 3 1-1XX 30 7 1-1XX 0 1-XX 0 1-XX 0 7 1-XX 0 88 1-1XX 37 80 1-1XX 7 80 1-1XX 80 0 1-1XX 80 8 1-1XX 31.00 1.70.8 1.9.1.3. 8..9 17..0 3.0 AMPS.1 3.1.1 10.3 1. 0.7 31.0 1. 0.1 103. 1.7 1.91 3.1.3 9..7 19.1. 38. 3.7 AMPS 3.1.7 7. 1. 3. 31.1.7. 93. 1.8 1.9 1.9 3.. 9.7.9 19..8 38.0.0 AMPS 3.1.7 7.7 1. 3.3 31.0.7.1 91. 1.0 1..7.1 8..3 1..7 33.0 9. 8. AMPS.1. 10.3 0. 30.9 1..0 8.8.3 07.1 1.73.9.3 8..9 17.3.9 3. 1.0 8.0 AMPS.. 10.3 0.7 31.0 1..3 83..7 0.9.9 3.89..9 19..9 38.9 1.9 77.0 9 AMPS. 9. 1. 31.0.7.3 93..8 18. 310.3 3..18 8. 17.3.9 3. 1.8 9. 103 173 AMPS 8.3. 0.7 1..3 83.. 1. 7.8 1. 1.81.7. 9.0 13. 18.1 7. 3.3.0 90.0 AMPS.1. 10.3 0. 31.0 1.3.1 8.8 3. 0. 0.99 1.9..9 7. 9.9 1.9 19.9 9.0 9.0 AMPS.1 3.1.0 10. 1. 0.7 31. 1. 0.7 10. 3..7 9.1 18. 7. 3..7 7.8 109 18 AMPS 8.3. 0.8 1.7.3 83..3 1.8 9.7 17.0 1.9.8.7 9. 1. 19.0 8. 38.1 7.0 9.0 AMPS..3 10.3 0.8 31.1 1.. 83.3.7 07.8 1.7. 3. 7.3.0 1.7.0 9..1 73. AMPS 3.1.7 7. 1. 3.3 31..7. 93. 1. 1.03 1...1 7.7 10.3 1. 0.7 31.0 1.0 AMPS.1 3.1.0 10. 1. 0. 31.1 1..3 10. 1.73.9.3 8..9 17.3.9 3. 1.0 8.0 AMPS.1 3.1. 10.3 1. 0.8 31. 1. 1.3 103. 3..18 8. 17.3.9 3. 1.8 9. 103 173 AMPS.. 10.3 0.8 31. 1..3 83. 3.9 08.1 3..7 9.1 18. 7. 3..7 7.8 109 183 AMPS..3 10. 0.8 31. 1.7.7 83..9 09. 1.9.8.7 9. 1. 19.0 8. 38.1 7.0 9.0 AMPS.1 3.1.1 10. 1. 0.8 31.3 1.7.3 103.9 1 1.0 1 1. 71.0 81 3.0 91.0 10 9 10 10 9 10
9- Buck-Boost Transformers Three-phase capacity of encapsulated Buck-Boost autotransformers connected in Wye Maximum load capabilities requiring three Buck-Boost Transformers Low (LV) High (HV) Catalog Number Load Required 01.100.10 1.0 Enclosure Figures Use Figure Use Figure 3 1 08 1-XX 173 08 1-XX 183 08 1-XX 189 08 1-XX 08 9 1-XX 08 3 1-XX 08 9 1-XX 08 3 1-XX 3 1 1-1XX 37 1 1-XX 378 1 1-XX 390 1 1-XX 397 1 1-XX 398 38 1-1XX 398 78 1-1XX 1 37 1-XX 1 3 1-XX 1 7 1-XX 1 71 1-XX 1 98 1-1XX 31.00 1.70 1.1 1.7.8. 8.. 1.8.0 3.0.0 AMPS 3.89.89 9.79 18.9 9. 38.9 8.9 78.9 7 197 1.. 3.7 7.. 1.0. 30.0. 7.0 AMPS.0 7...0 37.0 0.0 7.0 100 10 0. 3.3.. 1.8. 33.7.0 7.0 1 AMPS 7.07 10. 17. 3.9.8 70.7 10 3 3.0. 7. 1.0. 30.0.0 0.0 90.0 10 AMPS 9.17 13.7.9.8 8.8 91.7 137 183 7 8 3.3.9 8. 1..7 33.0 9..0 99.0 1 AMPS 9.17 13.7.9.8 8.8 91.7 137 183 7 8. 3.8.3.7 19.1. 38. 1.0 7. 7 AMPS 7.08 10. 17. 3.0. 70.8 10 30 1.8.7. 9.0 13. 18.0 7.0 3.0.0 90.0 AMPS.0 7...0 37. 0.0 7.0 100 10 0 1..1 3. 7.1 10. 1. 1. 8.0.0 71.0 AMPS 3.91.91 9.83 19.1 9.1 39.1 9.1 79.1 8 191 1.. 3.7 7.. 1.0. 30.0.0 7.0 AMPS. 3.7.. 18..0 37. 0.0 7.0. 3.3.. 1.8. 33.7.0 7.0 1 AMPS 3.3.8 8.8 17.. 3.3.8 70.7 10 17 3.0. 7. 1.0. 30.0.0 0.0 90.0 10 AMPS.8.88..9 3..8 8.8 91.7 137 9..7.. 33.7.0 7. 90.0 13 AMPS. 10.0 1. 33.3 9.7. 100 133 00 333.0 9.0 1.0 30.0.0 0.0 90.0 0 180 300 AMPS 8.73 13.1 1.8 3.. 87.3 131 17 3 3.1.7 7.8 1.7 3. 31. 7. 3.0 9.0 17 AMPS..8.3. 33.9. 8. 91.3 13 9 1.7..3 8..9 17..9 3.0 1.0 8.0 AMPS.0 3.7.. 18.7.0 37. 0.0 7.0.3 9. 1.7 31. 7. 3.0 9. 189 31 AMPS 8.7 13.1 1.8 3.7. 87. 131 17 37.8 7..0.0 3.0 8.0 7.0 9.0 1 0 AMPS. 10.0 1. 33.3 0.0. 100 133 00 333 3.3.9 8. 1..7 33.0 9..0 99.0 1 AMPS.8.87..9 3.1.8 8.7 91. 137 9. 3.8.3.7 19.1. 38. 1.0 7. 7 AMPS 3..9 8.83 17.. 3..9 70.8 10 17 1.8.7. 9.0 13. 18.0 7.0 3.0.0 90.0 AMPS. 3.7.. 18.7.0 37. 0.0 7.0 1 1.0 1 1. 71.0 81 3.0 91.0 8 8 7 7 7 7 8 8 7 8 Jefferson Electric Dry-Type Transformers jeffersonelectric.com 800-89-37
Buck-Boost Transformers 9-7 Single-Phase 00V Class Isolation Transformers.00 1 : 130 C Insulation Class 1. 10 : 180 C Insulation Class 0 x 0V /V 0 Hz Catalog Number Temp Rise Enclosure Figure Height (A) Width (B) Depth (C) (D) (E) (F) Est Ship Wgt 0.0 1-00-000 9 8.03 3.31 3.08.81.19. 0.1 1-01-000 9 8.03 3.31 3.08.81.19. 0.1 1--000 9 8.03 3.31 3.08.81.19. 8 0. 1--000 9 8.03 3.31 3.08.81.19. 0. 1-31-000 9 10.19.0.9 9.0 8.38. 0.7 1-1-000 9 10.19.0.9 9.0 8.38. 17 1 1-1-000 9 10.19.0.9 9.0 8.38. 17.8 1. 1-1-000 13 3..9.3 10..0..8 1-71-000 13 3..9.3 10..0. 33. 3 1-81-000 13 3 1. 7. 7.1.8 1. 3. 1-91-000 13 3 1. 7. 7.1.8 1. 3. 90 7. 1-101-000 13 1. 13. 8. 10. 8.. 1 10 1-1-000 13 1. 13. 8. 10. 8.. 178 0 x 0V 1/3V 0 Hz Catalog Number Temp Rise Enclosure Figure Height (A) Width (B) Depth (C) (D) (E) (F) 0.1 1-01-000 13 8.03 3.31 3.08.81.19. 0.1 1--000 9 8.03 3.31 3.08.81.19. 0. 1-1-000 9 8.03 3.31 3.08.81.19. 0. 1-31-000 9 10.19.0.9 9.0 8.38. 1 0.7 1-1-000 9 10.19.0.9 9.0 8.38. 17 1 1-1-000 9 10.19.0.9 9.0 8.38. 18 1. 1-1-000 13 3..9.3 10..0..8 1-71-000 13 3..9.3 10..0. 33. 3 1-81-000 13 3 1. 7. 7.1.8 1. 3. 8 1-91-000 13 3 1. 7. 7.1.8 1. 3. 9 7. 1-01-000 13 1. 13. 8. 10. 8.. 1 10 1--000 13 1. 13. 8. 10. 8.. 178 0 x 80V /8V 0 Hz Catalog Number Temp Rise Enclosure Figure Height (A) Width (B) Depth (C) (D) (E) (F) 0.1 1-101-000 9 8.03 3.31 3.08.81.19. 0.1 1-1-000 9 8.03 3.31 3.08.81.19. 0. 1-11-000 9 8.03 3.31 3.08.81.19. 0. 1-131-000 9 10.19.0.9 9.0 8.38. 1 0.7 1--000 9 10.19.0.9 9.0 8.38. 17 Est Ship Wgt Est Ship Wgt 1 1-11-000 9 10.19.0.9 9.0 8.38. 17.8 1. 1-11-000 13 3..9.3 10..0..8 1-171-000 13 3..9.3 10..0. 33. 3 1-181-000 13 3 1. 7. 7.1.8 1. 3. 8 1-191-000 13 3 1. 7. 7.1.8 1. 3. 88 7. 1-01-000 13 1. 13. 8. 10. 8.. 1 10 1--000 13 1. 13. 8. 10. 8.. 178 S0B S0C S80E See website for additional, copper windings and temperature options. Housing dimensions subject to change without notice. Consult website or factory where dimensions are critical. Use the Find a Product tool for detailed specification sheets. For further information, contact an Application Engineer at 800-89-37, technical_services@jeffersonelectric.com
9-8 Buck-Boost Transformers Buck-Boost Isolation Transformer s S0B & Connections Primary: 0 x 0 Volts Delta Secondary: / Volts PRIMARY S0C & Connections Primary: 0 x 0 Volts Delta Secondary: 1/3 PRIMARY S0E & Connections Primary: 0 x 80 Volts Delta Secondary: /8 Volts PRIMARY SECONDARY Connections Primary Volts Interconnect Primary Lines 0 H to H3 H1, H 0 H1 to H3 H to H H1, H Secondary Volts Interconnect Secondary Lines X to X3 X1, X X1 to X3 X to X X1, X SECONDARY Connections Primary Volts Interconnect Primary Lines 0 H to H3 H1, H 0 H1 to H3 H to H H1. H Secondary Volts Interconnect Secondary Lines 3 X to X3 X1, X 1 X1 to X3 X to X X1, X SECONDARY Connections Primary Volts Interconnect Primary Lines 80 H to H3 H1, H 0 H1 to H3 H to H H1, H Secondary Volts Interconnect Secondary Lines 8 X to X3 X1, X X1 to X3 X to X X1, X More wiring diagrams can be found in catalog s appendix, section 1. Use the Find a Product tool on our website for detailed specification sheets. For further information, contact an Application Engineer at 800-89-37, technical_services@jeffersonelectric.com Enclosure Figures. Figure Figure 3 Figure LIT901-0817b Jefferson Electric Dry-Type Transformers jeffersonelectric.com 800-89-37