SPAE 010, 011 High Impedance Protection Relay

Similar documents
Stabilized Differential Relay SPAD 346. Product Guide

SPAD 346 C Stabilized differential relay

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

Instantaneous Overcurrent Relay

SPAD 346 C. Stabilized Differential Relay. User s manual and Technical description SPAD 346 C V ~ V. f n SPCD 3D53 SPCJ 4D28

SPAF 340 C Frequency Relay

SPAJ 144 C. Combined overcurrent and earth-fault relay SPAJ 144 C. User s manual and Technical description A CBFP V ~ V.

Phase and neutral overcurrent protection

SPAS 348 C. Feeder Protection Relay. User s manual and Technical description SPAS 348 C V ~ V. t 2 > [ s ] f n = 50Hz 60Hz

Transformer differential protection

SPAJ 110 C. Earth-fault relay SPAJ 110 C. User s manual and Technical description. U aux V ~ V f n. n ( I o>> SPCJ 1C8

Harmonic restraint earth fault or single-phase overcurrent protection

IRI1-ER - Stabilized Earth Fault Current Relay

Time over/underfrequency relay with protection assemblies

SPAJ 111 C. Sensitive earth-fault relay SPAJ 111 C. User s manual and Technical description. U aux V ~ V. f n. n ( I o>> SPCJ 1C7

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd.

SPAJ 135 C. Combined overcurrent and earth-fault relay SPAJ 135 C. User s manual and Technical description. U aux V ~ V.

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

presentation contents application advantages

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

Type MCAG 14, 34 T&D. High Stability Circulating Current Relay

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

IRI1-ER - Stabilized Earth Fault Current Relay. Manual IRI1-ER (Revision A)

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

XUA1 - AC Voltage and phase balance relay

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work

)HDWXUHV Voltage restraint overcurrent stage with five different inverse or definite time characteristics

SPAC 335 C and SPAC 336 C Feeder terminals

Type CP-S, CP-C & CP-A Switch mode

N. TEST TEST DESCRIPTION

Overcurrent Protection / 7SJ45

SFIBER Fibre-optic Option Card for Lon Star Coupler RER 111. Technical Reference Manual

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

3 Pole high impedance differential relay 7VH83

N. TEST TEST DESCRIPTION

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK

Three-phase monitoring relay

satech SynchroStar GPS 200 Series

Earth fault protection for isolated neutral systems with frequency converters

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Three-phase monitoring relays CM-PFE and CM-PFE.2

02/11/2015

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New)

Electronic timer CT-SDS.22

SPAS 120 C Directional earth-fault relay

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

XP2-R Power and Reverse Power Relay

Introduction DIN rail mounted electricity meters

02/11/2015

Energy Management Three-phase energy meter with output modules Type EM4-DIN

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

Protection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New)

XU2-AC AC voltage relay. (Februar 1997) Manual XU2-AC (Revision New)

SPAA 120 C and SPAA 121 C Feeder protection relay

Modular multifunction generator protection

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd

Fixed Series Compensation

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions

Pressure Transmitter Type AKS 32 and AKS 33 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

Energy Management Energy Meter with plug-in Output Modules Type EM4-DIN

XD1-T Transformer differential protection relay. Manual XD1-T (Revision A)

C series Product brief

Time relay RXKA 1. (xx jpg) RXKA 1

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

XD1-T - Transformer differential protection relay

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

AUXILIARY RELAYS FOR TRIPPING APPLICATIONS

02/11/2015

Current and voltage measuring relays RXIK 1, RXEEB 1 and RXIB 24

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy

XF2 Frequency Relay. Manual XF2 (Revision A)

PROXIMITY SENSOR TERMINOLOGY

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Three-phase monitoring relay CM-PFS

High Performance Current Transducer IT 200-S ULTRASTAB = A. ε L

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

SPECIFICATION FOR OVERCURRENT RELAYS

Transcription:

SPAE 010, 011 High Impedance Protection Relay User s manual and Technical description f n = 50/60 Hz U n = 50 / 100 / 200 V 2 5 U REF > SPAE 010 0.8 U aux 0.6 1.0 RESET OK x 80... 265 V ~ _ 0.4 U > U n 1.2 U > 0087A RS 493 Ser.No.

1MRS 750063-MUM EN Issued 1995-05-08 Modified 2002-04-24 Version B (replaces 34 SPAE 1 EN1) Checked MK Approved OL SPAE 010, 011 High Impedance Protection Relay Data subject to change without notice Contents General features... 2 Area of application... 2 Operation... 3 Requirements on current transformers... 4 Connection and block diagram... 5 Connections... 5 Settings and markings on the relay front plate... 6 Technical data (modified 2002-04)... 6 Operating time characteristics... 8 Relay applications... 8 Maintenance and repairs... 10 Dimensions and instructions for mounting... 11 Information required with order... 11 General features High impedance differential type earth-fault protection. Applied for earth fault protection of transformers, motors and generators. The relay includes the stabilising resistor. Short total operating time together with high degree of stability. High degree of immunity against all types of mechanical and electrical interference and tested according to the latest relevant IECstandards. High accuracy and long time stability features due to a digital and software based design. Area of application The protective relays type SPAE 010 and SPAE 011 form in their applications a differential protection of the high impedance type. The differential protection of the high impedance type is used as earth-fault protection for transformers, generators and motors. The difference between the two relays is the auxiliary supply voltage required. For SPAE 010 the auxiliary supply voltage is within the range 80...265 V ac or dc and for SPAE 01 1 the range is 18...80 V dc. 2

Operation The high impedance type differential protection is stable for all types of faults outside the zone of protection. The stabilisation is obtained by a resistor in the differential circuit. In SPAE 010 and SPAE 011 the stabilizing resistor is included in the relay and is in series with the measuring transformer. This gives the name of the protection system, i.e. a high impedance type protection. The stability of the protection is based on the circumstance that the impedance of a current transformer quickly decreases as the current transformer saturates. The reactance of the excitation circuit of a fully saturated current transformer goes to zero and the impedance is formed only of the resistance of the winding. By means of the resistor in the differential current circuit these condary current fed by a non-saturated current transformer is forced to flow through the secondary circuit of a saturated current transformer. The operating level of the high impedance relay is to be set to a level not permitting a relay operation for any currents in the differential current circuit, caused by any fault currents arisen by faults outside the zone of protection of the high impedance protection. When a fault arises within the zone of protection, both current transformers strive to feed current through the differential current circuit and the protection will operate. Iu Ir Ru Iu Ru SPAE Ir SPAE Fig. 1. The principle of the high impedance type differential protection 3

Requirements on current transformers The sensitivity and reliability of the protection is much depending on the characteristics of the current transformers. The number of turns of the current transformers forming part of one and the same protection should be as equal as possible. In high impedance protections class x current transformers are to be used, the technical features of which are defined by the kneepoint voltage UK, excitation current Ie at the knee point and the secondary winding resistance Rin. The knee-point voltage is the excitation voltage value measured on the secondary side of the current transformer, which when increasing with 10 % causes an 50 % increase of the excitation current. For the current transformers to be able to force a current enough to operate the relay through the differential circuit during a fault condition inside the zone of protection, the knee-point voltage Uk should be 2 times higher than the stabilising voltage Us required in through fault conditions: Uk = 2 x Us = 2 x Ikmax /n (Rin + Rm) (1) where Uk = the knee point voltage Us = he stabilizing voltage Ikmax = the maximum through fault current n = turns ratio of the current transformer Rin = he internal resistance of the current transformer secondary winding Rm = he total resistance of the longest measuring circuit loop The factor two is used when no delay in the operating time of the protection in any situation is acceptable. In order to prevent the knee-point voltage from growing too high, it is advisable to use current transformers, the secondary winding resistance of which is of the same size as the resistance of the measuring loop. The sensitivity requirements set up for the protection are endangered, if the excitation current of the current transformers, corresponding to the knee-point voltage is permitted to grow too high. The magnitude of the excitation current Ie can be calculated from the expression: Ie = (Iprim/n-(Ir+Iu))/m (2) where Ie = the excitation current Iprim = the primary current level, for which the protection is to operate Ir = the current corresponding to the relay setting Iu = the current flowing through the protective resistor n = turns ratio of the current transformer m = number of current transformers per phase belonging to the protection To prevent the voltage of the secondary circuit from growing too high during faults within the zone of protection, a resistor is connected in parallel with the differential current circuit. The resistance of the resistor is dependent of the voltage; the higher the voltage is, the lower the resistance value becomes. 10 000 5 000 3 000 2 000 1 000 500 300 200 100 50 Û (V) a b c 30 20 Î (A) 10 0.01 0.03 0.1 0.3 0.005 0.02 0.05 0.2 0.5 1 2 3 5 10 30 20 50 100 Fig. 2. Characteristics of the voltage dependent resistor a = resistor 5248 831-D, b = resistor 5248 831-C, c = resistor 5248 831-B 4

Connection and block diagram R31 R33 = stabilizing resistors Ru = voltage dependent resistor Ru + (~) Uaux - (~) 50 V 100 V 200 V 63 40 41 42 43 61 62 70 71 72 67 68 69 74 75 65 66 R31 R32 R33 R31 = 2.2 kω R32 = 2.2 kω R33 = 4.4 kω OK A D µp U> SPAE U>/Un RESET Fig. 3. Connection and block diagram of the high impedance relay type SPAE 010 or SPAE 011 Connections The terminals of the relay have the following function: Terminal Function 40-41 Measured voltage when the setting range is 0.4...1.2 x 50 V 40-42 Measured voltage when the setting range is 0.4...1.2 x 100 V 40-43 Measured voltage when the setting range is 0.4...1.2 x 200 V 61-62 Auxiliary power supply. The positive pole of dc supply is connected to terminal 61 63 Protective ground 65-66 Trip contact 1 74-75 Trip contact 2 67-68-69 Alarm contact 70-71-72 Internal relay failure alarm contact. When the auxiliary power is connected and there is no internal failure contact 70-72 is closed 5

Settings and markings on the relay front plate The front plate contains one setting knob, two LEDs, one green and one red and one pushbutton. The operation voltage of the protection is set by means of the U/Un setting knob on the relay front panel and the setting range is 0.4...1.2 x Un. The two LEDs on the front plate are used to indicate the relay status and the trip of the relay: The green LED (OK) is alight whenever the auxiliary voltage is connected, the relay is operating and there is no internal relay failure. The red LED (U>) lights up whenever the relay trips. The red LED remains glowing when the breaker is tripped and the relay drops off. RESET push-button is used to reset the red tripindicator. Protection symbol 2 U REF > Relay ratings and test voltages Relay type designation Setting knob for voltage Normal state indicator (no internal failure) Range of auxiliary voltage f n = 50/60 Hz U n = 50 / 100 / 200 V SPAE 010 U aux OK U > x _ 80... 265 V ~ 5 0.4 0.8 0.6 1.0 U > U n 1.2 RESET Trip indicator Type number and serial number' 0087A RS 493 Ser.No. Fig. 4. Front panel of the relay SPAE 010 with setting elements TechnicaI data (modified 2002-04) Energizing inputs Terminal numbers 40-41 40-42 40-43 Rated voltage, Un 50 V 100 V 200 V Thermal withstand capability - continuous 1.3 x Un - for 1 s 10 x Un Rated frequency, fn 50/60 Hz Protection characteristics Voltage setting range, U>/Un 0.4...1.2 x Un Operating current 9...27 ma Operating time see fig. 5 Drop-off time 120 ms Drop-off/pick-up ratio 0.8 6

Output contact ratings Trip contacts, terminal numbers 65-66, 74 75 Rated voltage, make or break 250 Vac or dc Make and carry for 0.5 s 30 A Make and carry tor 3 s 15 A Continuous carry 5 A Breaking capacity for dc, when the control circuit time constant L/R 40 ms, at 48/110/220 V dc 5 A / 3A / 1 A Contact material gold plated AgNi Signalling contacts, terminal numbers 67-68-69, 70-71-72 Rated voltage, make or break 250 Vac or dc Make and carry for O.5 s 10 A Make and carry for 3 s 8 A Continuous carry 5 A Breaking capacity for dc, when the control circuit time constant L/R 40 ms, at 48/110/220 V dc 1A / 0.25A / 0.15A Contact material gold plated AgNi Auxiliary power supply Supply voltage, SPAE 010 Supply voltage, SPAE 011 Power consumption 80...265 V ac or dc 18...80 Vdc about 5 W Insulation Tests Dielectric test IEC 60255-5 2kV, 50Hz, 1min Impulse voltage test IEC 60255-5 5kV, 1.2/50µs, 0.5J Insulation resistance measurement IEC 60255-5 >100MΩ, 500Vdc Electromagnetic Compatibility Tests High-frequency (1MHz) burst disturbance test IEC 60255-22-1 - common mode 2.5 kv - differential mode 1.0 kv Electrostatic discharge test IEC 60255-22-2 and IEC 61000-4-2 - contact discharge 6 kv - air discharge 8 kv Fast transient disturbance test IEC 60255-22-4 and IEC 61000-4-4 - All ports 2 kv Spark interference test voltage, inputs and outputs as per SS 436 15 03, PL 4 4...8 kv Environmental Conditions Specified service temperature range -10...+55 C Transport and storage temperature range -40...+70 C Temperature influence on the operating values of the relay over the specified service temperature range <0.2%/ C Damp heat test, cyclic IEC 60068-2-30 +25...55 C, r.h. > 93%, 6 cycles Degree of protection by enclosure of the relay case when panel mounted IP 54 Weight of fully equipped relay 2 kg 7

Operating time characteristics t (ms) 100 80 Operating time 60 40 20 0 0 1 2 3 4 5Applied 6voltage 7 8 9 10 U/U> Fig. 5. Operating time characteristics of SPAE 010 and SPAE 011. Relay applications R31 R33 = stabilizing resistors Ru = voltage dependent resistor Ru + (~) Uaux - (~) 50 V 100 V 200 V 63 40 41 42 43 61 62 70 71 72 67 68 69 74 75 65 66 R31 R32 R33 R31 = 2.2 kω R32 = 2.2 kω R33 = 4.4 kω OK A D µp U> SPAE U>/Un RESET Fig. 6. Earth-fault protection of transformer using high impedance relay SPAE 010 8

In solidly earthed networks the Earth-fault currents reach very high magnitude. Therefore the earth-fault protection should be fast operating. In the application above the earth-fault protection of the high voltage side of the power transformer has been carried out with the high impedance relay SPAE 010 using the differential connection principle, i.e. so called restricted earth-fault protection. The turns ratios of the current transformers are selected equal. The protection is to be stable both for earth-faults and short-circuits arising outside the zone of protection. In order to keep the secondary circuits as short as possible, the summation connections are performed at the terminals of the current transformers. The setting value of the relay, U> can be calculated from the expressions: U> Us (3) Us = Ikmax x (Rin + Rm)/n (4) where U> = setting value of the relay U = stabilizingvoltage Ikmax = the maximum through fault current, for which the protection is to be stable Rin = the internal resistance of the current transformer secondary winding Rm = the total resistance of the longest measuring circuit loop, i.e. the range from the relay terminals to the current transformer n = turns ratio of the current transformer The ratio of the stabilising voltage and the kneepoint voltage has to be checked using the expression (1). The knee-point voltage has to be high enough to secure the operation of the protection in through fault situations. The sensitivity of the protection can be calculated using the expression: Iprim = n (Us /Rs +m x Ie+Iu) (5) where Iprim = the primary current level, for which the protection will operate n = turns ratio of the current transformer Us = the stabilising voltage Rs = the value of the internal stabilising resistor m = the number of current transformers per phase in the protection Ie = the excitation current of the current transformer at the excitation voltage Us, when regarding the excitation curve of the C.T. as being linear Iu = the current flowing through the protective resistor at the voltage level Us, see figure 2 on page 4. 9

Maintenance and repairs When the protective relay is operating under the conditions specified in the section "Technical data", the relay is practically maintenance free. The relay modules include no parts or components subject to an abnormal physical or electrical wear under normal operating conditions. If the environmental conditions at the relay operating site differ from those specified, as to temperature, humidity, or if the atmosphere around the relay contains chemically active gases or dust, the relay ought to be visually inspected in association with the relay secondary test being performed. At the visual inspection the following things should be noted: Check for signs of mechanical damage on relay case and terminals Accumulation of dust inside the relay cover or case; remove by blowing air carefully Rust spots or signs of eruginous metal on terminals, case or inside the relay On request, the relay can be given a special treatment for protection of the printed circuit boards against stress on materials, caused by abnormal environmental conditions. If the relay fails in operation or if the operating values remarkably differ from those of the relay specifications, the relay should be given a proper overhaul. Minor measures can be taken by personnel from the customer s company instrument workshop but all major measures involving overhaul of the electronics are to be taken by the manufacturer. Please contact the manufacturer or his nearest representative for further information about checking, overhaul and recalibration of the relay. Note! Static protective relays are measuring instruments and should be handled with care and protected against moisture and mechanical stress, especially during transport. 10

Dimensions for mounting The relay is housed in a normally flush-mounted case. If needed, Fe can also be surface mounted. The relay case is made of a black anodized, extruded aluminium profile. A cast aluminium Al by mounting frame with a rubber gasket provides a degree of protection by enclosure to IP 54 when the relay is panel mounted. The relay case is complete with a hinged gasket, clear, UV- stabilized polycarbonate cover with a sealable fastening screw. The degree of protection by enclosure of the cover is also IP 54. A terminal block is mounted on the back of the relay case to facilitate all input and output connections. A connection diagram is shown adjacent to the terminal block. To each terminal one or two 2.5 mm 2 wires can be connected. No terminal lugs are needed. Flush mounting Panel cut-out Surface mounting Information required with order 1. Number of and type of relay 2 off, SPAE 010 2. Auxiliary power supply voltage, U aux 110 Vdc 3. Accessories none 4. Special requirements none 11

ABB Oy Substation Automation P.O.Box 699 FIN-65101 VAASA Finland Tel. +358 (0)10 22 11 Fax.+358 (0)10 22 41094 www.abb.com/substationautomation 1MRS 750063-MUM EN