Siemens Transformer Technology Seminar Insulation & Thermal Design

Similar documents
Transformer Technology Seminar Winding Selection

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Power Transformers Basics

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015

HOT SPOT STUDIES FOR SHEET WOUND TRANSFORMER WINDINGS

Transformer Technology Seminar What to consider at Design Reviews

Electrical Design Process

Basic Principles and Operation of Transformer

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2

Siemens Transformer Technology Seminar Low Partial Discharge Transformers

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

TRANSFORMER TECHNOLOGY GPT

Optimization of power transformers based on operative service conditions for improved performance

Western Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc.

nical catalogue Tech

Power transformers for Network, Rectifiers, Furnace

Transformer Factory Testing

PCS Working Group on General Requirements C

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

Transformer Design: Economics & Reliability

Design Improvement by Diagnostics of Transformers still in Operation and of Apparatuses taken out of Service

Temperature Rise Tests

Liquid-Filled Transformers

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED

New prospects for power transformer winding thermal design optimisation using THNM and CFD simulations

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

Regional Technical Seminar

ABB Power Products Service

CFD STUDY OF NON-GUIDED LAMINAR MIXED CONVECTION OF A HIGH PRANDTL NUMBER FLUID IN A TRANSFORMER WINDING-LIKE GEOMETRY

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX

TECHNICAL SPECIFICATION

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

Tougher than any challenge. Transformers for highcurrent. industrial applications. siemens.com/transformers

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Effective maintenance test techniques for power transformers

SUMMARY. PALAVRAS CHAVE Power Transformer, CFD, Hot spot, Winding, Temperature

Technical recommendation for the purchase of Real Time Thermal Rating for transformers

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

K Factor Power Transformers

Efacec work every day to anticipate solutions for a sustainable world in the new energy era.

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

Effects of Harmonic Distortion I

Regional Technical Seminar SHORT CIRCUIT FORCES

Wood. Wood construction

NUMERICAL STUDY ON MIXED CONVECTION AND THERMAL STREAKING IN POWER TRANSFORMER WINDINGS

CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS

Walchand Institute of Technology. Basic Electrical and Electronics Engineering. Transformer

VIRGINIA TRANSFORMER CORP. Drive & Rectifier. Transformersrs

Transformers. 6.1 Principles of operation. Professor D.J. Allan Merlindesign. Chapter 6

TATUNG POWER TRANSFORMERS

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

Hands-On Transformer Testing and Maintenance

(

TMC Transformers TMC

CAST RESIN DRY TRANSFORMER

(2) New Standard IEEE P (3) Core : (4) Windings :

The Effect of PV on Transformer Ageing: University of Queensland s Experience

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

Winding Temperature Measurement in a 154 kv Transformer Filled with Natural Ester Fluid

Transformer Technology Seminar GIC Capability of Power Transformers

Electric Field Analysis of High Voltage Condenser Bushing

APPENDIX 4 TYPICAL LAYOUT, VALUES AND CONSTANTS

Direct Measurement of Transformer Winding Hot Spot Temperature and its Significance

Underground System Design TADP 547

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

Regional Technical Seminar SHORT CIRCUIT FORCES

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

Basic principles and operation of a transformer

COIL WINDING ISSUES P. Fabbricatore INFN Genova LCD - Magnet 13Oct09. Coil winding issues

Outcomes from this session

Mathematical Modeling of Disc Type Winding Of Transformer

This document is a preview generated by EVS

2.3 PF System. WU Weiyue PF5 PF PF1

TRAFO ELECTRIC P. LTD.

Identification of Overheating in Transformer Solid Insulation by Polarization Depolarization Current Analysis

LECTURE 10. Dr. Teresa D. Golden University of North Texas Department of Chemistry

Basics of electrical transformer

Phase Shifter Application Workshop. Siemens Energy, Inc.

Ritz Instrument Transformers GmbH. Welcome

Introduction. Centrado leading-edge transformer. Introduction

Cholla T809 Condition Assessment Report Provided by students of Northern Arizona University with the support of Arizona Public Service

Reactor and inductor are names used interchangeably for this circuit device.

Power Safety Quality

Energy Efficient Distribution Transformers

Industrial Applications

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

DOCUMENTATION OF INSULATION MEASUREMENTS FOR ELECTRICAL MACHINES

SECTION 16322B SUBSTATION TRANSFORMERS DRY-TYPE

Climatic, Environmental and Fire Behaviour (C2 E2 F1) Test of Cast Resin Transformer

Transcription:

Customer Technical Meeting Pomona, CA May 24 25, 2016 Siemens Transformer Technology Seminar Insulation & Thermal Design Siemens AG Transformers siemens.com/answers

Winding Selection Windings: Page 2

Winding Selection Conductors: Paper Insulated Flat Conductors If higher mechanical stability is required: Multiple conductors with Epoxy bonding. In this case, the individual strips are insulated from one another with enamel. Page 3

Winding Selection Conductors: Continuously Transposed Conductors (CTC) CTC Axial twin CTC If higher mechanical stability is required: Strands with Epoxy bonding CTC with intermediate paper layer Page 4

Winding Selection Conductors: Conductor Insulation High electrical breakdown withstand Thermal stability Kraft Paper made of long wood fibers, purified from resin material and lignin through a chemical process. The Degree of Polymerization (DP) measures the length of the fibers and is a measure for aging Density Thermal Class Cellulose Paper 0.7-0.85 g/cm³ 105 Cellulose Paper, Thermally upgraded 0.7-0.85 g/cm³ 120 Calendered paper 0.95-1.1 g/cm³ 105 Calendered Paper, Thermally upgraded 0.95-1.1 g/cm³ 120 Meta Aramid (Nomex 410) 1 g/cm³ 220 Page 5

Winding Selection Example: Net Covered CTC for lower winding gradients Page 6

Insulation Materials Solid Insulation Materials Based on natural cellulose fibers all materials can be impregnated with oil Paper very thin material (50... 200 mm) electrical +++, mechanical Pressboard thickness 0,5... 8mm Sheet material, angle rings snout segments electrical ++, mechanical + Page 7

Insulation Materials Solid Insulation Materials Laminated Pressboard Glued pressboard with Casein or Polyester thickness 9... 120mm electrical +, mechanical ++ Laminated Wood glued veneer from beech (or birch) with Phenolharz different direction of layers thickness 10... 120mm electrical -, mechanical +++ Page 8

Insulation Materials Solid Insulation Materials Synthetic materials cannot be oil impregnated Insulating varnish Nomex Glass fiber Page 9

Typical Insulation Structure Example Page 10

Typical Insulation Structure Field plot of a 123 kv transformer Test: one phase induced The green lines are equipotentials they connect points of equal voltage. The electric field gradient cuts these at 90 degrees. Page 11

PD and breakdown considerations General cause of partial discharge and/or a breakdown is high electrical stress according the following situations: Causes can be Cavity not filled with oil Contamination (metal) Design (selection of material, failure in design) Mechanical damage Manufacturing outside of tolerance Sharp edges Page 12

PD and breakdown considerations Cavity not filled with oil (inside glue, glass fiber, ) Er ~1 air, vacuum Material with Er > 1 Electrical field strength higher than inside the material E cavity ~ 2 5x E material Breakdown voltage of cavity < Breakdown voltage of material Start of partial discharge inside the cavity Breakdown Page 13

PD and breakdown considerations Contamination (metal) inside material (pressboard, laminated pressboard, KP-wood, paper) Metal High field strength at the edges of the metal part, local overload Partial discharge Breakdown possible (dependent on the size of the metal part) Page 14

PD considerations Causes of Partial Discharge and Breakdown Example Manufacturing outside of tolerance Cylinder HV-disc winding 2 mm High electrical field strength partial discharge breakdown Page 15

PD considerations Causes of Partial Discharge and Breakdown - Examples Soft paper insulation Deformed angle ring Page 16

Insulation & Thermal Design PD considerations Causes of Partial Discharge and Breakdown - Examples Contamination with metal parts Page 17 Glue in the insulation arrangement

Thermal Design Considerations Source of conductor and core heating Loss contribution: Contribution Load current Ohmic resistance of winding conductor: I² R 60-90 % eddy current losses in all metallic parts due to the magnetic stray flux of the windings < 20 % No-load voltage Magnetic flux Φ in core 10-30 % core steel 1 W/kg exciting current < 1 % of rated current Page 18

Thermal Design Considerations Cooling types Oil Loop Symbol Cooler Type Symbol Oil Natural Oil Forced (pump) Oil Directed (pump, directed flow into main windings) ON OF OD Air Natural (radiator) Air Forced (radiator with fans, or cooler) Water Forced (cooling by water) AN AF WF e.g. ONAN or one transformer with several conditions, e.g.: ONAN, ONAF, OFAF former ANSI code: OA, FA, FOA since 2006: ANSI = IEC Page 19

Thermal Design Considerations Oil flow in core type transformers: top pump pump Core Radiator LV HV bottom ON: Oil Natural oil flow by heated parts (buoyant force) OF: Oil Forced oil pumps: flow into tank OD: Oil Directed oil pumps: flow directed into windings Page 20

Thermal Design Considerations Examples Page 21 ONAN / ONAF radiators with fans ODAF 5 Coolers

Thermal Design Considerations Conventional Limits as per IEEE Limits as per IEEE C57.12.00-2010 Top Oil rise above ambient 65 K Winding rise above ambient 65 K Hotspot rise above ambient 80 K Ambient Limit IEEE C57.12.00-2010 Range +40 C oil: -20 C Daily average 30 C Thermally upgraded paper shall be used for insulation components that determine the minimum life expectancy, such as: winding insulation, layer to layer insulation, lead insulation. The allowed Hotspot Temperature of thermally upgraded paper insulation is 30+80=110 C. IEEE C57.91-2012 suggests that the expected lifetime at 110 C could be 15-20 years. The lifetime depends strongly on the moisture and oxygen content of the oil and insulation, therefore an oil preservation system is recommended. Page 22

Thermal Design Considerations Standard Model Winding Page 23 A is the top-oil temperature derived as the average of the tank outlet oil temperature and the tank oil pocket temperature B is the mixed oil temperature in the tank at the top of the winding (often assumed to be the same temperature as A) C is the temperature of the average oil in the tank D is the oil temperature at the bottom of the winding E represents the bottom of the tank g r is the average winding to average oil (in tank) temperature gradient at rated current H is the hot-spot factor P is the hot-spot temperature Q is the average winding temperature determined by resistance measurement X axis indicates temperature rise Y axis indicates relative vertical positions measured point; calculated point

Thermal Design Considerations Detailed simulation Loss Distribution in individual parts of the windings can be calculated with very high precision On this basis calculation of the Hotspot-Temperature is done, based on the calculated winding gradients, oil gradients and outer cooling system simulation. Page 24

Thermal Design Considerations Hotspot distribution Mineral oil Synthetic Ester Natural Ester Test Hot-spot rise 69.8 K Hot-spot rise 77.4 K Hot-spot rise 80.2 K Page 25

Thermal Design Considerations Winding to oil gradient of a CTC Temp Loss W/m² Enamel 0,8 K Oilfilm 1,5 K Paper Insulation3,0 K 14,2 K Interface paper-oil 8,9 K Distance Page 26

Thermal Design Considerations Oil Flow Concepts for the Windings suitable for natural or directed oil flow Test Layer Windings with Strips Disc Windings without radial cooling ducts but with axial cooling ducts Disc Windings with radial and axial cooling ducts Increased cooling surface Disc Windings with radial cooling ducts The oil is guided by oil guide washers Very efficient for ON and OD cooling Disc Windings with radial and axial cooling ducts The oil is guided by oil guide washers Page 27

Thermal Design Considerations Examples of temperature rises in oil and windings (same windings, losses and radiators) 55 39 39 78 55 39 55! 78 37 59 41 37 5739 6345! 5238 23 23 35 35 35 35 ON High longitudinal rise Page 28 OF Cooler top oil: low, but hotspot unchanged Not recommendable OD Recommendable for larger transformers Limit: oil velocity to avoid electrostatical charging

Siemens AG MPT Transformers Contact Kurt Kaineder Head of Engineering Head of Electrical Design Global Technology Center MPT Siemens AG Oesterreich Transformers Linz Kraussstraße 7 4020 Linz Phone: +43 (5) 1707-71098 Fax: +43 (5) 1707-55391 Mobile: +43 (664) 615 4946 Mobile: +43 (664) 80117 71098 E-mail: kurt.kaineder@siemens.com Siemens.com/transformers

Siemens US Transformers Contact James McIver Principal Application Engineer E T TR US 6860 Bermuda Road, STE 100 Las Vegas NV 89119 USA Mobile: (702) 241-0157 E-mail: james.mciver@siemens.com Siemens.com/transformers Page 30