Arc Flash Mitigation An Overview. Gus Nasrallah, P.E. Electroswitch May 30, 2013

Similar documents
Electrical Arc Hazards

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

First Draft Language

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

Cause, Effect & Mitigation Strategies

ARC FLASH & PPE UPDATE. Michael Olivo, P.E. Aaron Ramirez, E.I.T.

STANDARDIZING ARC FLASH PPE LABELS

Steve Kovach District Sales Engineer

Arc Flash and NFPA 70E

Arc Flash Analysis and Documentation SOP

Arc Flash Hazard Standards:

NFPA-70E. Electrical Safety in the Workplace. Standard for Edition

Webinar: An Effective Arc Flash Safety Program

{40C54206-A3BA D8-8D8CF }

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

THREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA

Arc Flash Analysis Training

Arc Flash Hazard and Mitigation 2 nd Workshop on Power Converters for Particle Accelerators June 14 16, 2010

DC ARC FLASH. THE IMPLICATIONS OF NFPA 70E 2012 ON BATTERY MAINTENANCE

Arc Flash Study Principles & Procedures for below 15 kv AC Systems. Xuan Wu, Dennis Hoffman, Ronald Wellman, and Manish Thakur

2015 NFPA 70E. SESHA 2015 ARIZONA MINI CONFERENCE December 10, 2015 Intel Corporation

REDUCING ARC FLASH HAZARD BY REMOTE SWITCHING

Paul Dobrowsky Innovative Technology Services

A Guide to Establish an Arc Flash Safety Program for Electric Utilities

Arc Hazard Assessment for DC Applications in the Transit Industry

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

Arc Flash Calculation Methods

Education & Training

APPLYING LOW-VOLTAGE CIRCUIT BREAKERS TO LIMIT ARC FLASH ENERGY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

Key factors to maintaining arc flash safety

NATIONAL ELECTRIC SAFETY CODE 2012 EDITION

CHANGEABILITY OF ARC FLASH PARAMETERS AND ITS IMPACT ON HAZARD MITIGATION IN LOW VOLTAGE POWER SYSTEMS

Electrical Severity Measurement Tool Revision 4

Electrical Measurement Safety. Sponsored By:

Ft Worth IEEE-PES. Presented by: Doug Harris Specifications Engineer Dallas, TX. Arc-Flash Hazard Mitigation & Selectivity

Selection of PPE Practical experience of different arc assessment methods and their comparison

2017 ELECTRICAL SAFETY SERVICES. Arc Flash Electrical Maintenance Lockout/Tagout And More

ARC FLASH HAZARD ANALYSIS AND MITIGATION

DESIGN STANDARD DS 29

Electrical testing safety Part 1: Preparing for absence of voltage testing

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

SWITCHING SAFETY & RELIABILITY CONFERENCE

COMMON SOURCES OF ARC FLASH HAZARD IN INDUSTRIAL POWER SYSTEMS

OSHA & Arc Flash. Scott Ray Distribution Project Engineer POWER Engineers, Inc.

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

VACUUM INTERRUPTER APPLICATION NOTES Filename: VIAN X-Rays and Vacuum Interrupters Revision: 0 PAGE 1

Electrical Safety Policy Health and Safety FCX-HS03 Release 07/2018 Version 1

Copper Core & Coil Transformer

NOTICE ER Roland Flood Pumping Station Arc Flash Study

A controlled arc-flash, produced in a flashtube. Even though the energy level used is fairly low (85 joules), the low-impedance, low-inductance

2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis

Effective System Grounding

high RESISTANCE GROUNDING SYSTEM the power to protect www. ElectricalPartManuals. com Instruction Manual C-102

PRODUCTIVELY SAFER LOCK-OUT TAG-OUT PROCEDURE

New Age Technologies in Construction Safety and Associated Concerns

Upgrading Your Electrical Distribution System To Resistance Grounding

SECTION POWER SYSTEMS STUDIES

Best Practice Reducing The Risk of Arc Flash Cross Over

Industrial and Commercial Power Systems Topic 7 EARTHING

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

CREATING A COMPARATIVE MAP OF RELATIVE POWER FOR DC ARC FLASH METHODOLOGIES. A Thesis. presented to

How does an Arc occur?

Earth Fault Indicator EFI-BLZ-50 User Manual

Application Note (Revision NEW) Original Instructions. EMI Control in Electronic Governing Systems

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

2014 NEC Changes Part 1

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Industrial Electrician Level 3

Grounding for Power Quality

Short Circuit Current Calculations

3Ø Short-Circuit Calculations

Enclosed circuit breaker (ECB) with Arcflash Reduction Maintenance System

INSTRUCTION MANUAL. March 11, 2003, Revision 3

How OSHA s New Transient Overvoltage Requirements Affect Work Practices. B.A. YEUNG, H. BRANCO Leidos Engineering, LLC USA

FR-ABR-(H)0.4K to 22K

2 Grounding of power supply system neutral

High Voltage Testing. Team 5: Justin Bauer, Matt Clary, Zongheng Pu, DeAndre Dawson, Adam McHale

REVIEWED HES MANAGER

Grounding Recommendations for On Site Power Systems

Variable Refrigerant Flow (VRF) System Simple Touch Remote Control SAFETY WARNING

How does an Arc occur?

Model 4210-MMPC-L. Multi-measurement Prober Cable Kit. Overview. Quick start guide topics. Related documents

EFCOG BEST PRACTICE # 211. Best Practice Title: Managing Hazards of Multiwire Branch Circuits Installed Before the 2008 NEC

NOsparc! MHXAC1F120! MHXAC1F240! MHXAC1F480 PATENTS AND PATENTS PENDING. Contact Arc Suppressor

1. Executive Summary. 2. Introduction. Selection of a DC Solar PV Arc Fault Detector

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

SE-502 MANUAL GROUND-FAULT GROUND-CONTINUITY DETECTOR

EPG. by Chris C. Kleronomos

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

MITIGATING ELECTRIC SHOCK AND ARC FLASH ENERGY A TOTAL SYSTEM APPROACH FOR PERSONNEL AND EQUIPMENT PROTECTION

Standards for MV switchgear rated for arc flash protection

TABLE OF CONTENTS. References

Risk Management Department. Control of Hazardous Energy

Thomas Wilkins Wilkins Consulting Henderson Nevada U.S.A.

Why? Why? "Fatal Four Bureau of Labor Statistics. Monitoring and Metering for Electrical Safety. Shock Fire Explosion Production

Transcription:

Arc Flash Mitigation An Overview Gus Nasrallah, P.E. Electroswitch May 30, 2013

Agenda Origin of Modern Arc Flash studies Why Now more than before NFPA 70E Standards Protection Zone IEEE 1584 2002 IEEE 1584 Vs NFPA 70E Arc Flash Assessment & Mitigation Minimizing Energy Unit Presence of Personnel Near Arc Flash Options Available Arc Flash Resistant switchgear, Chicken switch, Time delay switches and Relays Questions

What is Arc Flash? An Arc Flash is an electric current that passes through air when insulation or isolation between electrical conductors is no longer sufficient to withstand the applied voltage. [NFPA 70E] Arc flash results from an arcing fault, where the electric arcs and resulting radiation and shrapnel cause severe skin burns, hearing damage, and eye injuries. (OSHA Training Grant SH-16614-07) Arc flash causes damage from energy flux, not electric current and is distinct from electrocution.

Origin of Modern Arc Flash Study The Other Electrical Hazard: Electric Arc Blast Burns (Ralph Lee, 1985) Wakeup call Start of Modern Arc Flash Safety Studies, based on industrial experience Put arc flash hazards on a par with those of electrocution

Origin of Modern Arc Flash Study Key Results from Lee 1985: Arcs are extremely hot: 4 x Temperature of the Sun Importance of incident energy and threshold for very serious burns of 1.2 cal/cm 2 - still in use. Calculation of effects of arc current, distance from arc, voltage, and other variables. More on this later. All that is necessary to incur serious or fatal injuries is to be within five feet or so from a severe power arc with bare skin or flammable clothing.

Other Key Early Work Pressures Developed by Arcs, Ralph Lee 1987. Up to 2,000 psf Testing Update on Protective Clothing and Equipment for Electric Arc Exposure, Bingham, Doughty, and Neal 1997 Besides data on personnel protective equipment and clothing (PPE) also discussed the amplifying effect of enclosures. Predicting Incident Energy to Better Manage the Electric Arc Hazard on 600-V Power Distribution Systems, Doughty, Floyd, and Neal 2000

Why now? More attention to worker safety More medium and high voltage feeds in industrial applications Better data (and more is on the way) Large increase in electricity usage Higher Efficiency Equipment (Lower Impedance)

NFPA 70E Provides guidelines to limit injuries to second degree burns. Defines zones depending on risks of electrocution and arc flash burns.

NFPA 70E Shock/electrocution boundaries depend on voltage. Limited Approach Area: no untrained personnel may approach live conductors within this distance. Restricted Approach Area: trained personnel with PPE and a written plan Prohibited Approach Area: trained personnel, PPE, written plan and risk assessment. Assumption is that work within this zone is the same as touching the live conductor. Training, tools and documentation must be appropriate.

Flash protection Boundary and Limits of Approach

NFPA 70E NFPA 70E, Section 130.3 (B) states: The incident energy exposure level shall be based on the working distance of the worker s face and chest areas from a prospective arc source for the specific task to be performed

NFPA 70E Flash Protection Boundary Depends on available energy: arc voltage * fault current * duration Can easily be a larger or smaller area than the limits from system voltage NFPA calculations are easy to do and are often conservative. More on this later. There are three methods in NFPA 70E, with different applicability and computational effort required. Online calculators and other tools are available.

Typical NEC Warning Label

Protection Zones From an excellent training presentation prepared by West Virginia University for OSHA under grant SH-16614-07. Available on the web in English and Spanish.

NFPA 70E Boundries Good safety practices minimize risk: Switch remotely if possible. Standing aside and away as much as possible during switching. Avoid leaning on or touching switchgear and metallic surfaces. Use proper tools and PPE.

IEEE 1584-2002 Guide for Performing Arc Flash Hazard Calculations Based on statistical analysis of lab data Well defined, but somewhat lengthy procedure for calculating energy, flash boundary and required PPE. 49 case studies of incidents

IEEE 1584 In the process of being revised, hopefully for this year. Extensive, well funded effort to get new data Should cover a variety of situations (new voltages) with new experimental data More accurate equations

Using IEEE 1584 to Calculate Incident Energy and Flash Boundary Step 1: Calculate the Arcing Current Inputs: Bolted Fault Current, System Voltage, Gap, Enclosed/Not Enclosed Output: Arcing Current Log(I a ) = K + 0.662*log(I bf )+0.0966*V + 0.000526*G + 0.5588*V*log(I bf ) - 0.00304*G*log(I bf ) I a = 10 log(ia)

Using IEEE 1584 to Calculate Incident Energy and Flash Boundary Step 2: Determine Incident Energy Inputs Open/Boxed, High/Low Impedance Ground, Gap, Voltage, Time and Distance from Arc Incident Energy is proportional to Time and inversely proportional to 1/D 2 or 1/D 1.437 or in between. log(e n ) = K 1 +K 2 +1.081*log(I a ) + 0.0011*G E = C f * E n * (t/0.2) * (610 x /D x )

Using IEEE 1584 to Calculate Incident Energy and Flash Boundary Step 3: Calculate Flash Boundary Distance where incident energy falls to 1.2 cal/cm 2 D B = 610 * [C f * * (t/0.2) * (E n /E B )] 1/x

IEEE 1584 v. NFPA 70E 70E is often very conservative. From A Survey of Arc Flash Computation Methods and Mitigation Strategies, Carl Spezia 2010

Arc Flash Assessment Determination of degree of risk and precautions required. Arc flash incidents are high cost/low probability events (Spezia 2010) Injury, litigation, regulatory requirements NIOSH DVD Arc Flash Awareness gives accounts from electrical workers Assessing risk and benefits can be difficult See, for example: http://www.nsc.org/safetyhealth/pages/411resourcesimpo rtanceofarcflashsalisbury.aspx

Arc Flash Mitigation [Incident Energy] = K * time * F(fault current)/ D 1.497 NFPA 70E for enclosures Problem is caused by the intersection of factors Energy in the arc Fault current Clearing Time (Time is more important than fault current) Presence of personnel near the arc Proximity to the arc, ie. Working at close quarters Incident Energy α 1/D 2 (Open area) or 1/D 1.5 (Enclosure) Susceptibility of personnel to incident energy (PPE) All of these factors can be addressed!

Minimizing Energy Decrease fault current Series reactance can lower fault current but Lower current can slow clearing devices Often not practical or cost effective

Minimizing Energy Current Limiting Fuses Must clear a short circuit fault in less than a half cycle Because of fast melting and increased fuse impedance in the first quarter cycle both time and peak current are greatly reduced. Can greatly reduce incident energy (by more than a factor of ten) Only work within limited ranges. Great when you have one that fits the application. IEEE 1584 and vendor web sites have detailed ratings

Minimizing Energy Fiber Optic Flash Sensors Provide very fast arc detection - ~2 msec Work in closed spaces such as switchgear Readily available Some newer digital relays have inputs for up to four optical arc sensors See Inshaw, C., & Wilson, R. A., Western Protective Relay Conference, 2004.

Minimizing Energy Change Relay Settings During Maintenance or Other Operations Uses existing equipment Requires coordination study May increase system vulnerability during maintenance Depends greatly on particular circumstances.

Limit Presence of Personnel Near Arcs If you aren t there you won t get hurt. Only work on energized equipment when absolutely necessary Look hard for any alternative. Observe OSHA and NFPA guidelines and rules Lockout/tagout! Check that voltage is really not present. Remote racking of breakers, Mimic panels, etc. Arc resistant switchgear (any potential arc is shunted away from personnel)

Limit Presence of Personnel Near Arcs Use Time Delay Trip and Close Control Switches in Metalclad Switchgear Provide 10 to 30 second delay from instigation of operation to actual switching. Discrete switch solution from Electroswitch Also available in some newer digital protective relays

Limit Presence of Personnel Near Arcs Electroswitch Time Delay Control Switch Simple, intuitive operation Trip and close operations started and cancelled via pushbuttons Remote operation also built in.

Increase Distance of Personnel to Arc For metalclad this often means operating a control switch remotely. Homegrown solutions Hot sticks Rope Other

Increase Distance of Personnel to Arc The Chicken Switch Clamps on to existing switch handle. Disadvantages: Has to be found each time you need to operate the switch Needs careful installation to avoid breaking the switch handle

Protect Personnel Subject to Arc Flash This is the last line of defense! It is there to protect against life threatening injury. It is important to specify the PPE reasonably accurately. Too little protection can result in disaster Overprotection reduces worker mobility and vision, causing other problems.

Protect Personnel Subject to Arc Flash Ranges from: class 0 (Untreated cotton) Class 4 (Cotton underwear plus FR shirt, pants, coveralls and multilayer flash suit) for up to 40 cal/cm 2 Beyond 40 cal/cm 2 equipment must be deenergized.

Arc Flash Mitigation Solvable problem Better standards and information (IEEE 1584 revision are on the way. Information is readily available. Questions?