Value Valves US Electric ctuator DOUBLE CTING SPRING RETURN www.bvcusa.com
01~02 VLUE VLVE U.S.. ELECTRIC CTUTORS
QURTER-TURN ELECTRIC CTUTOR FETURES FETURES Enclosure: IP 67 (Nema 4, Nema 4X) waterproof and dust-proof enclosures. MaterialDry powder coated aluminum alloy. Conduit entrance (1/2 NPT). Motor: Standard duty cycle 30%. Extended duty cycle available. H insulation class for EOM-1 and EOM-F class for EOM-2 to EOM-12. Built-in thermal protection (275 F) prevents motor burnout. Position Indicator: ll models have a position indicator beacon on the actuator cover. Manual Override: Non-clutch design, the manual operator can be operated without any lever, clutch or brake upon power outage. When electric motor is operating, manual hand-wheel does not rotate. Gear Train: High alloy steel gear trains provide self-locking function. Gear trains lubricated with high temperature lubricant at the factory. Working conditions: mbient temperature23 F~140 F. Standard Features (noted) and Options: Space heater/thermostat (Standard). dditional limit switches (Standard on EOM 2-13). Potentiometer unit (1K Ohm). Local control unit (local/remote, on/off). Torque switches. Current position transmitter (output 4-20m). Modulating controller. Various voltages. Nylon coated enclosure. Certificates: ISO 9001. CE. CS. ISO 5211.
Torque (In.Lbs) 1062 443 310 797 1329 3543 4429 5757 8857 13286 17714 22143 26571 31000 39825 Power (Watts) 40W 10W 10W 40W 40W 120W 120W 120W 180W 220W 180W 220W 250W 300W 300W Model No. EBM-2 EOM- EOM-1 EOM-2 EOM-3 EOM-4 EOM-5 EOM-6 EOM-7 EOM-8 EOM-9 EOM-10 EOM-11 EOM-12 EOM-13 Speed (Sec/ 90 ) 8 20 12 15 22 16 22 28 46 46 58 58 58 58 80 Weight (Lbs) 9.9 6.6 4.4 24.23 24.23 48.46 48.46 48.46 79.30 79.30 123.35 123.35 123.35 123.35 178.2 Manual Override N/ N/ Lever Mounting Flange (ISO 5211) F07 F07 F03/F05/F07* F07 F07 F10 F10 F10 F12 / F14 F12 / F14 F16 F16 F16 F16 F25 *(Two holes only) 03~04
Dimensions B C F D G H E I J Plastic cover. No manual overide. No mechanical stops. No certificates. 4 - K Dimension Model No. EBM-2 B C D E 2 - H I G F J K L M N With modulating card E = 9.00 No mechanical stops. 4 - P 4 - Q Dimension Model No. EOM- EOM--M
B C D F E G H 2 - I J K L 4 - N 4 - P With modulating card F = 7.20 No mechanical stops. Dimension Model No. M EOM1 B C D E F I J 2 - K L G H M 4 - N With DC motor E= 11.37 (apply to DC model or 75% duty cycle) Note: with torque switch = 14.20 Dimension Model No. EOM2-EOM3 05~06
Dimensions B C D E F G I J 2 - K L H M 4 - N Note : with torque switch = 18.10 Dimension Model No. EOM4-EOM6 B C D E F G I J 2 - K H L M 4 - N Note : with torque switch = 17.12 Dimension Model No. EOM7 EOM8
B C D E F 2 - K I J H 2 - M N L 2 - M N L 4 - P 4 - P Dimension Model No. EOM9-EOM10 EOM11-EOM12 B C D 2 - K E F G I J L P H 2 - M N 8 - Q Dimension Model No. EOM-13 07~08
OPTION ITEMS TORQUE SWITCHES djustable cam activated torque switches to provide over-load protection. It can only apply to EOM-2 ~ 13. EOM-1, EOM- & EOM--M (1KΩor 5KΩ) POTENTIOMETER UNIT EOM-2 ~ 13 (1KΩor 5KΩ) It is synchronous turn with transmission shaft, and it can provide feedback signal for position indicator. (with lock) LOCL CONTROL UNIT Local / Remote selection switches. Open / Close selection switches. It can only apply to EOM-2 ~ 13. (without lock) MODULTING CONTROLLER FOR EOM-2~13 Modulating actuator: 30% or 75% duty cycle for EOM-2 ~ 8, 50% duty cycle for EOM-9 ~ 13. It is a board inside actuator and supplied for EOM-2 ~ 13. Input signal: 4-20m, 1-5V, 2-10V. Output signal: 4-20m, 2-10V. EOM-2 ~ 13 CURRENT POSITION TRNSMITTER It works with potentiometer unit and provides 4-20m output signal for position indicator. MODULTING CONTROLLER FOR EOM-1, EOM- & EOM--M It is a board inside actuator and supplied for EOM-1 & EOM-. Input signal: 4-20m, 1-5V, 2-10V. Output signal: 4-20m, 2-10V.
Value Valve Electric ctuator Ordering Matrix MODEL NUMBER MTRIX - EXMPLE PRT NUMBER - EOM- 4 - - 0-2 9 EOM- 4 0-2 - 9 MODEL VOLTGE OPTIONS 3543 in lbs 120 ON-OFF / SINGLE PHSE / 2 EXTR LIMIT SWITCHES EBM-2 = 120 VC 0 = ON-OFF (EOM1-EOM12) EOM-1 B = 220 VC 1 = MODULTING (EOM1-EOM12) EOM- C = 380 VC 2 = 1 PHSE (EOM1-EOM12) EOM-2 D = 460 VC 3 = 3 PHSE (EOM2-EOM12) EOM-3 E = 12 VC ( EOM1 - EOM6) 4 = 3 PHSE WITH LOCL-REMOTE CONTROL (EOM2-EOM12) EOM-4 F = 12 VDC ( EOM1 - EOM6) 5 = 3 PHSE / MODULTING / LOCL-REMOTE CONTROL (EOM2-EOM12) EOM-5 G = 24 VC (EOM1 - EOM12) 6 = 1K OHM POTENTIOMETER (EOM2-EOM12) EOM-6 H = 24 VDC (EOM1 - EOM12) 7 = TORQUE SWITCHES (EOM2-EOM12) EOM-7 I = 240 VC 8 = SINGLE INPUT EOM-8 J = 340 VC 9 = 2 EXTR LIMIT SWITCHES (EOM1-EOM12) EOM-9 10 = EXTENDED DUTY CYCLE (EOM2-EOM13) EOM-10 11 = CURRENT POSITION TRNSMITTER (EOM2-EOM12) EOM-11 12 = Not Used EOM-12 13 = 1 PH., LOCL-REMOTE CONTROL, W/LOCL-REMOTE STTUS FEEDBCK EOM-13 13ED = 1 PH., LOCL-REMOTE CONTROL, WITH LOCL-REMOTE STTUS FEEDBCK RELY ND EXTENDED DUTY MOTOR 14 = HRD NODIZING ND NYLON COTED HOUSING (EOM1-EOM12) 15 = 1 PHSE, 50 HERTZ (EOM2-EOM12) 16 = 3 PHSE, 50 HERTZ (EOM2-EOM12) SEE ELECTRIC OPERTOR BROCHURE FOR COMPLETE OPTIONS REV. 3/2010 09~10
Simplfied Operation Manual EOM-1 ~ EOM-13, EOM-, EOM--M, BM-2 110/220/24V ctuator (ON/OFF, 3 Point Control) Wiring Diagram 110/220V a.c. 110/220V a.c. 24V a.c./d.c. uxilary Switches (SPDT Relay) 30% duty cycle 75% duty cycle G N L N G N L G + L 24V a.c. 24V d.c. B C E F EOM-1, EOM- B C D E F EOM-2~13, BM-2 PE 1 3 4 5 6 Terminals L to ctuator 3 Open 4 Close 7 Heater 7 PE 1 3 4 5 6 7 Terminals Power to 1, 7 L to ctuator 3 Open 4 Close PE 1 3 4 5 6 7 Terminals Power to 1, 7 L to ctuator 3 Open 4 Close ctuator Position EOM-1 EOM- EOM-2~13 BM-2 Fully open - B - C Fully Close - E D - F Details refer to Travel switches adjustment. The quarter-turn actuator is provided with a limiting of manual rotation device to avoid over-travel with the hand-wheel. Before setting the limit switches, please adjust the mechanical stops. Mechanical Stops adjustment "LS4" Synchronous turn with LS2(Option) 1. To loosen the screws 2. To adjust limit switches & travel cams. 3. To adjust the screws 4. To reverse one cycle LS4 LS3 LS2 "LS3" Synchronous turn with LS1(Option) LS2 "CLOSE" Clockwise :Decrease closed degree. Counter-clockwise:Increase closed degree to fully close. LS1 LS1 Clockwise:Increase opening degree to fully open. OPEN CLOSE "OPEN" Counter-clockwise:Decrease opening degree. Travel switches adjustment for EOM-1 & EOM-, "LS4" Synchronous turn with LS2(Option) LS4 LS3 LS2 LS1 "LS3" Synchronous turn with LS1(Option) LS2 "CLOSE" LS1 "OPEN" Clockwise :Decrease closed degree. Counter-clockwise:Increase closed degree to fully close. Clockwise:Increase opening degree to fully open. Counter-clockwise:Deccrease opening degree.
EOM-1~ EOM-13, EOM-, EOM--M 110/220/24V ctuator (Modulating, 30% & 75% duty cycle) Wiring Diagram 24V d.c. 24V a.c., 110/220V a.c. G PE 1 2 3 4 5 6 7 8 9 10 11 12 Note: Terminals We suggest that you use the shielding wire and please don t exceed 30m. Modulating Board Set Up EOM-1 & EOM-,EOM--M _ Signal Feedback + Input Output N L _ + _ + uxilary Switches (SPDT Relays) B C E F B C D E F EOM-1, EOM- EOM-2~13 ctuator EOM-1 Position EOM- EOM-2~13 Fully Open - B - C Fully Close - E D - F Details refer to Travel switches adjustment. EOM-2 ~ EOM-13 Output Signal _+ Input Signal_ + Power + _ M P1 P2 12 11 7 6 5 4 2 1 VR1 ON 1 2 3 Green Lamp (Open indicator) S1S8 4 5 6 7 8 VR2 Dip Switch please refer to page 9 for setting VR52 VR51 Red Lamp (Closed indicator) SW1 SW0 Yellow Lamp (Power light) Sensitivity Switch setting is position # 3 for factory Disconnect power supply before changing the following settings. Dip Switch setting * S1S8 8 7 6 5 4 3 2 1 ON * S3, S4 &S5 for out put signal Output Signal S3 S4 S5 2-10V ON OFF ON 4-20m OFF ON OFF * S1, S2 for input signal Input Signal S1 S2 2-10V OFF ON 4-20m ON OFF 1-5V OFF OFF sensitive switch: (Factory setting is position 3 ) 0 9 1 8 2 3 6 4 5 * S7 & S8-ctuator response to the loss of control signal. When signal fails S7 S8 Full closed OFF ON Full open ON OFF Stops ON ON Position 0 : Lowest Sensitive, 0-90 divided into 17 steps. Position 1 : Highest Sensitive, 0-90 divided into 70 steps. * S6 - Direction of travel in response to the control. ( Factory setting is OFF. ) Turn Off Seting for OPEN and CLOSE LED2 Fully Open LED7 Input Signal Short 1. Keep pressing SET for 3 seconds, then LED9 comes on, it will enter the Circuit manual mode. LED3 Power LED8 Motor Current Overload 2. Keep pressing UP until LED2 comes on (fully-open), then supplies the input signal (5V or 10V or 20m) and presses MODE once. LED4 bnormal Voltage LED9 Manual Control 3. Keep pressing Down until LED1 comes on (fully-close), then supplies the input signal (1V or 2V or 4m) and presses MODE once. LED5 Wrong Input Signal 4. fter finishing the above settings, press SET once. To reset and return to the original status Please power off and get troubleshooting, then power on. 7 S6 OFF ON 90 90 Symbol Signal Signal LED1 Fully - Closed LED6 Motor Thermostat 11~12
Spring Return ctuator www.bvcusa.com 2010 pril
Spring Return ctuator In additional to the normal function, these actuators are designed to provide fail-safe positioning of valves and dampers upon loss of supply voltage. mechanical spring set is utilized to position the controlled device to either the fully OPEN or fully CLOSED position without any external power source. mechanical BUFFER employed at the end of the spring stroke reduces the dynamic effects of the spring return system. Clutchless, leverless manual override design provides full-time manual positioning of the controlled device. The design has already won the new Patent in Taiwan, U.S., Japan and China. Specification Model Max Torque (In.Lbs) Weight (Lbs) Flange Size (ISO 5211) ES 500 443 60 F07 ES 1300 1150 126 F10 ES 2000 1770 209 F12 ES 2600 2299 209 F12 Model Selection Table MODEL HOUSING DIRECTION VOLTGE 13~14 ES 500 ES 1300 ES 2000 ES 2600 N: Non-explosionproof CW: fails clockwise CCW: fails counterclockwise Example MODEL HOUSING DIRECTION VOLTGE ES 500 N CW 110VC/1PH OPTIONS: 2 additional limit switches, heater 110VC / 1PH 120VC / 1PH 220VC / 1PH 240VC / 1PH 380VC / 3PH 440VC / 3PH 24VC 24VDC
MJOR Components Spring Return actuators are suitable for ball valves, butterfly valves, damper systems, or any quarter-turn application requiring mechanical fail-safe positioning. Position Indicator Buffer Structure Manual Override Main Housing Windows Protection Cover Spring & Rack Gear Structure
General Information and Options Standard Capability Duty Cycle Rating : 50% (compliance to IEC standard) Two - Position Control mbient Temperature Range Temperature : -22 OF ~ +149 O F Humidity : 30% ~ 95% Enclosure Material : aluminum alloy, powder coated Lubrication The gear train has been factory lubricated for life under normal operating conditions. Position Indicator ll models are equipped with a direct - drive position indicator on the top of actuator cover. Various Options Manual Override Modulating Controller Input Signal : 4-20m, 1-5V, 2-10V Output Signal : 4-20m, 2-10V Modulating Type is Without "Buffer" Floating Control Space Heater Heater Thermostat dditional Limit Switches (2 Units) Potentiometer Unit (1K Ohm or 5K Ohm) Current Position Transmitter Operating Direction Standard : Fails Clockwise Optional : Fails Counter - Clockwise Conduit Entrance Standard : 1/ 2"NPT Optional : 3/4"NPT, M20 Various Voltage 110 / 220V C, 24V C / DC, 380VC, 440VC Nylon Coated Enclosure Material 15~16
Notes Direction of rotation is based on viewing actuator from top. Drawing shows actuator output shaft in power fail clockwise position. Standard unit fails clockwise. Optional unit fails counter-clockwise. Standard Model B C D E F G H I J K L M N Flange Type ES500 10.16 14.17 15.75 1.18 0.16 2.17 3.54 7.01 1/2" 6.73 3.43 0.67 2.76 M8 x 1.25 F07 ES1300 14.37 18.19 18.82 1.54 0.20 2.76 4.92 10.31 1/2" 9.72 4.65 0.87 4.02 M10 x 1.5 F10 ES2000 17.24 23.62 21.57 1.77 0.20 3.35 5.91 11.97 1/2" 12.01 5.24 1.06 4.92 M12 x 1.75 F12 ES2600 17.24 23.62 21.57 1.77 0.20 3.35 5.91 11.97 1/2" 12.01 5.24 1.06 4.92 M12 x 1.75 F12 With Manual Override Model B C D E F G H I I J K LL M N P Q Flange Type ES500 15.24 14.17 21.06 1.06 7.01 1/2" 7.64 1.18 0.16 2.17 3.54 6.73 8.50 0.67 2.76 M8 x 1.25 F07 ES1300 19.02 18.19 25.31 2.28 10.31 1/2" 11.65 1.54 0.20 2.76 4.92 9.72 9.29 0.87 4.02 M10 x 1.5 F10 ES2000 23.19 23.62 29.06 3.94 11.97 1/2" 15.75 1.77 0.20 3.35 5.91 12.01 11.18 1.06 4.92 M12 x 1.75 F12 ES2600 23.19 23.62 29.06 3.94 11.97 1/2" 15.75 1.77 0.20 3.35 5.91 12.01 11.18 1.06 4.92 M12 x 1.75 F12
110/120V C, 1 PHSE Run - Full Load mpere Lock - Locked Rotor mpere Model Operating Time ( Sec / 90 O ) ( 60Hz / 50Hz ) 110V C / 1PHSE Current ( 60Hz / 50Hz ) 120V C / 1PHSE Motor Spring Run Lock Run Lock ES500 7 / 9 3 1.0 / 1.3 2.0 / 2.2 1.5 / 2.5 2.8 / 3.0 ES1300 7 / 9 8 2.6 / 4.5 10 / 10.5 3.8 / 6.9 11 / 11.5 ES2000 11 / 13 12 2.6 / 4.5 10 / 10.5 3.8 / 6.9 11 / 11.5 ES2600 14 / 17 12 2.6 / 4.5 10 / 10.5 3.8 / 6.9 11 / 11.5 220/240V C, 1 PHSE Model Operating Time ( Sec / 90 O ) ( 60Hz / 50Hz ) 220V C / 1 PHSE Current ( 60Hz / 50Hz ) 240V C / 1 PHSE Motor Spring Run Lock Run Lock ES500 7 / 9 3 0.6 / 0.7 1.0 / 1.2 0.7 / 0.8 1.3 / 1.5 ES1300 7 / 9 8 1.5 / 2.2 5.0 / 5.1 2.1 / 3.8 5.6 / 5.7 ES2000 11 / 13 12 1.5 / 2.2 5.0 / 5.1 2.1 / 3.8 5.6 / 5.7 ES2600 14 / 17 12 1.5 / 2.2 5.0 / 5.1 2.1 / 3.8 5.6 / 5.7 380/440V C, 3 PHSE Model Operating Time ( Sec / 90 O ) ( 60Hz / 50Hz ) 380V C / 3 PHSE Current ( 60Hz / 50Hz ) 440V C / 3 PHSE Motor Spring Run Lock Run Lock ES500 7 / 8.5 3 0.4 / 0.4 0.5 / 0.6 0.3 / 0.4 0.5 / 0.6 ES1300 7 / 8.5 8 1.0 / 1.5 2.8 / 3.0 0.7 / 1.0 2.1 / 2.2 ES2000 11 / 13 12 1.0 / 1.5 2.8 / 3.0 0.7 / 1.0 2.1 / 2.2 ES2600 14 / 17 12 1.0 / 1.5 2.8 / 3.0 0.7 / 1.0 2.1 / 2.2 24V C / DC, 1 PHSE Model Operating Time ( Sec / 90 O ) ( 60Hz / 50Hz ) Current ( 60Hz / 50Hz ) 24V C / DC Motor Spring Run Lock ES500 7 3 3.0 4.0 ES1300 8 3 9.0 19.0 ES2000 11 3 9.0 19.0 ES2600 17 3 9.0 19.0 17~18
SSEMBLIES
VLUE Value US Butterfly Valves & Controls Inc. 671 Industrial Blvd, Grapevine, Texas 76051 Phone817-421-5343 Facs817-416-6270 www.bvcusa.com