ECM HIGH EFFICIENCY CIRCULATORS WILO STRATOS
Stratos Commercial high efficiency pumpp Main features & benefits 0-285 Gal/min flow 3 40 ft head 8 models (1.25, 1.5, 2 & 3 ) EC motor (permanent magnet rotor) Automatically ti adjusts to system demands d No external sensors required Easy setup via red button Water temperature from 14⁰F to 230⁰F Constant t pressure control mode Variable pressure control mode Temperature control mode BMS options: LON & Bacnet, 0-10V Infrared device for remote control & setup Excellent warranty 24/18 months UNIQUE FEATURES & UP TO 80% Q ENERGY SAVINGS!
Stratos-D (dual-power head pump) p) 2 & 3 size models Flow up to 450 gpm IF modules required Duty/Standby mode Lead/Lag mode Space saving Accessories saving
Sratos-Z for Domestic Hot Water Cast S. Steel volute EC Motor Built-in VFD T⁰ control with 0-10V IF 0-160 GPM @ 40-3 NSF/ANSI 61-G certified pump
ECM Technology Commutation (reverse currents) Coil 1 Coil 4 Coil 2 Coil 3
Speed Control Electronic continuous speed control (Constant Pressure) > Automatic differential e pressure e control o n max 1. The brain determined the actual pumping head. (actual value) Pumping Head H [F Ft] H 2 H 1 3 2 Constant speed pump 1 2. The drive sees the difference between the set value (point 1) and the actual value. (point 2) 3. Via ECM smart technology the controller reduces the speed and reduced the pumping head to match the system curve. (point 3) Q 1 Q 2 Flow Q [USGPM]
Built In Control Modes P C C (Constant Pressure Differential) Control Mode On site setting via red button Can be adjusted from 3ft to max pump head Pump will vary the flow but keep a constant diff. pressure Built-in control mode, does not require external sensors Recommended in low resistance systems or in-floor heating loops zoning In the example above, the pump is set to maintain 20 ft constant differential pressure. The flow will modulate from 0 to 230 gpm.
Built In Control Modes Constant Speed Control Mode Max Set speed 2210 rpm Min On site setting via red button Can be adjusted from Min to Max speed with 10 rpm increments Built-in control mode, does not require external sensors Recommended in fixed flow/head application In the example above, the pump is set to 2210 rpm. Minimum and Maximum speeds vary depending on pumps models.
Built In Control Modes P V (Variable Pressure Differential) Control Mode On site setting via red button Can be adjusted from 3ft to max pump head Pump will automatically vary the flow and the head on system demand. Min head at 0 flow is half the max head set Built-in model, does not require external sensors Recommended in high resistance systems In the example above, the pump is set to maintain 24 ft differential pressure at maximum flow. As the flow decreases, the head decreases proportionally.
Built In Control Modes P T T (Temperature Pressure Differential) Control Mode Change in temperature at the pump changes the pressure setpoint IR tool required to activate and set perameters Stratos t installed on return T Max T Min = > or = 50 deg. F T Max: 150 F H @ Max T: 10 T Max: 190 F H @ Max T: 7 T Min: 100 F H @ Max T: 30 T Min: 140 F H @ Max T: 25 Head Head 30 25 10 7 100 F 150 F Temp 190 F 140 F Temp Condensing Boiler Application Non-Condensing Boiler Application (Decreases delta P on temp rise) (Increases delta P on temp rise)
Power Supply 1ph 230V G FC 2 x 1ph 115V Check local electrical code 3ph 208/230V Acceptable input voltage: 195V min / 263V max
Interface modules for BMS communication
External Control Modes BUILDING MANAGEMENT SYSTEM Interface modules for: 0-10V DC Signal LON BACNET Dual pump operation
Inter-Face 0-10V/DP / Ext. Off 0 to 1 V: Pump Off 1 to 3V: Pump On / Minimum speed 3 to 10V: Speed modulation, 3V=Min and 10V-Max Ext. Off Contact: if closed losed = Pump On / if open = Pump Off
Inter-Face 0-10V/DP/Ext. Min 0 to 1 V: Pump On / Minimum speed 1 to 10V: Speed modulation, 1V=Min and 10V=Max Ext. Min Contact: if closed = Modulation / if open = Speed Min
Inter-Face 0-10V/DP/SBM 0 to 1 V: Pump Off 1 to 3V: Pump On / Minimum speed 3 to 10V: Speed modulation, 3V=Min and 10V-Max SBM Status Contact: if closed = Pump is On / if open = Pump is Off
Dual Pump Operation Dual pump operation Auto changeover Lead/Lag mode Duty/Standby mode Power Management
BACnet InterFace Module MS/TP SLAVE IF RS485 High Baud Rates Analog input/output Binary input/output Multistate input/output p Dual pump operation
LON InterFace Module FTT 10A transceiver High Baud Rates Analog input/output Binary input/output Multistate input/output XIF files available Dual pump operation
Interface (IF) modules for Stratos IF modules summary board Description Article # 0 10V Ext. Off Ext. Min Run (SBM) LON BacNet DP IF 0 10V/DP/Ext.Off 2030475 x x x IF 0 10V/DP/Ext.Min 2030485 x x x IF 0 10V/DP/SBM 2030495 x x x IF SBM/Ext.Off/DP 2084867 x x x IF LON 2030455 x x IF BacNet 2097810 x x Key: x = Available 0 10V = External 0 10V DC input signal Ext. Off = pump p start/stop contact Ext. Min = Default minimum speed contact SBM = Run status contact LON = BMS LON interface BacNet = BMS BacNet interface DP = Dual pump management
IR Remote Control Infra-Red remote control: O it i ti i On site communication via laptop Control setting Pump monitoring Data logging & saving