PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

Similar documents
DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

SHARDA Make Harmonics Filter

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

STANDARD SPECIFICATION FOR COLD JUNCTION COMPENSATION BOXES (CJCB)

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

2.5. Contents Description Motor Drive Isolation Transformers... Mini Power Centers... Totally Enclosed Non-Ventilated Transformers

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

K Factor Power Transformers

Reference Number PPS 05 - (RIC Standard: EP SP)

PROBLEMS on Transformers

Compact Substation or Prefabricated Substation Inside Totally Enclosed Weatherproof Enclosure COPYRIGHT REGISTERED

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s

TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

2.4. Transformers. Contents Description General-Purpose Encapsulated Transformers Catalog Number Selection... Product Selection... Product Description

T S 15KVA 1PH 240/480 Transformer

DISTRIBUTION TRANSFORMER 11 / kv

Technical Specifications

Technical Specifications SECTION C

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

General Electricity Company of Libya

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

TECHNICAL SPECIFICATION OF 630 KVA, 11/ KV DRY TYPE OUTDOOR TRANSFORMERS.

PANELMDP Main Distribution Panel. Descriptions Energy Efficient Transformer

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

Cast resin transformers HARMONY TM

Ritz Instrument Transformers GmbH. Welcome

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

50-SDMS-01 SPECIFICATIONS FOR

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

VI 3 - i TABLE OF CONTENTS

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

86 chapter 2 Transformers

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

380V/415V/440V 50HZ/60HZ 3 PH PRIMARY AND 230V 50HZ/60HZ 3PH 4 WIRE SECONDARY CENTRE TAPPED NEUTRAL EARTHED TRANSFORMER

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

CAST RESIN DRY TRANSFORMER

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

METER - INSTALLATION Pad Mount Transformer

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Electrical Description

Status Date Prepared Reviewed Endorsed Approved

HOW TO SAFE GUARD THE TRANSFORMER..???

500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor

INTERNATIONAL TRANSFORMERS. Acme Electric s broad selection of CSA energy efficient transformers

2.14 Main Cable Type HO7RN-F4G10-15 Metres each Chiller Tank Capacity- 75 Litres Compressor- 3.5 Tons Refrigeration type

2.4. Transformers. Contents Description General-Purpose Encapsulated Transformers Catalog Number Selection... Product Selection... Product Description

SPECIFICATION FOR AC-DC POWER SUPPLY FOR DEFENCE APPLICATION

2.4. Transformers. Contents Description General-Purpose Encapsulated Transformers Catalog Number Selection... Product Selection... Product Description

General Specifications for Unit Substations

Hours / 100 Marks Seat No.

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

Overtravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0

Arc Suppression Coils

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

POTENTIAL TRANSFORMER

User s Manual For CT Model IMB

Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers

VOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS)

SECTION PANELBOARDS

ELECTRIC ACTUATOR. Quarter turn(rotary type) - ZGQ Series

Module 7. Transformer. Version 2 EE IIT, Kharagpur

Maharashtra State Electricity Distribution Co. Ltd.

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

TECHNICAL INFORMATION

TMC Transformers TMC

Test Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy

(

Transcription:

PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY CHECKED BY APPROVED BY SAROJ SAH SANJAY AHIRWAR RAJESH AGRAWAL DESIGN ENGR (CEE) MANAGER( CEE) SR MGR-(CEE) ISSUED BY CONTROL EQUIPMENT ENGINEERING DIVISION BHARAT HEAVY ELECTRICALS LIMITED, BHOPAL - 1 -

SPECIFICATION FOR 500 KVA DRY TYPE TRANSFOFMER 01. GENERAL: This specification covers the requirement of 500KVA transformer for use in electrical system for drilling oil rigs. The transformer shall be suitable for semi outdoor conditions and shall have self supporting structure with top lifting arrangement. The transformer shall have delta connected 600VAC, 50Hz primary and star connected 415VAC, 50Hz secondary with neutral brought out. The transformer shall be used to feed a common MCC bus which shall be used to feed various AC motors, Lighting loads, A/Cs and other AC auxiliary loads of the rig. 02. TECHNICAL SPECIFICATION: RATING : 500KVA DUTY : Continuous PRIMARY : 600VAC, 3 Phase, 50Hz, delta connected Taps at (+)2.5% & (-) 2.5% and (+)5% & (-)5% (Tap links should be accessible) SEOCNDARY : 415VAC, 3 phase, 50Hz, star connected and neutral brought out VECTOR GROUP : DYN 11 TYPE : Cast resin core dry type transformer with encapsulated winding ENCLOSURE : IP23 (Semi outdoor application) COOLING : Natural Air Cooled (AN) INSULATION : Class F (Epoxy Encapsulated) INSULATION LEVEL : Rated short duration withstand voltage 3KV RMS as per IS -11171 DIMENSION : Length : 1570 mm max. Breadth Height : 1050 mm max. : 1900 mm max. - 2 -

AMBIENT TEMP. : 50 DEG. C. IMPEDANCE : 4.5% VOLTAGE TERMINALS : Terminal box shall be provided with tin plated flat copper terminations for 3 Nos primary (3 phase) & 5 Nos secondary terminals (3 Phase + 2 Neutral) suitable for 32mm wide copper terminal with 2 Nos 11mm dia hole at 25mm centre distance as per drg no-34406104003. Cable glands of suitable size with neoprene gasket for 300sqmm cable (36mm OD) shall be provided (Total 8 nos). Transformer shall have top cable entry as per enclosed Drg-37211010564, R00. Both primary & secondary terminals shall be brought on one side of the of the transformer. Acceptable make of glands are Commet, Jainson & Brako. CABLE GLANDS : Total 8 Nos : 3 Nos for primary (3 Ph) and 5 Nos for secondary ( 3 Ph + 2 N) suitable for 36mm OD cable. Single compression type cable glands to be provided on non-magnetic plate (SS or Aluminum) at the top of the transformer. WINDING MATERIAL : INSPECTION COVER: Electrolytic grade copper Should be removable from front APPLICATION : Two such transformers shall be connected in parallel to feed AC loads like 3 phase motors, Compressors, Lighting loads etc. STANDARDS : Generally as per IS 11171-1985 & IS 2026-1977 following latest amendments. 03. IMPORTATNT NOTES: Following points to be taken care by the supplier during design and manufacturing of transformer. a) The transformer shall be placed in semi outdoor confined compartment with flap /hinge type doors, where only two sides will be accessible and open to free air for ventilation. The other two sides shall be very close to compartment walls and free air ventilation will be obstructed. This aspect should be taken care during design of transformer. b) The power supply to transformer may contain significant spikes and harmonics generated by thyristor converters, hence the design of transformer should be suitable for spikes & harmonics. - 3 -

c) The transformer shall operate in oil rig drilling sites which are normally very humid with relative humidity reaching more than 95%. The design of transformer should be suitable for working in such humid environment. d) Temperature rise & terminal marking of the transformer shall be as per IS 11171:1985. SC withstand ability of transformer shall be as per IS 2026:1977. e) 2 Nos earthing point shall be provided at the bottom of the transformer for earthing of transformer enclosure. f) Transformer shall be provided bi-directional roller with locking arrangement for easy movement. g) All hardware used for transformer assembly shall be zinc plated & passivated. h) Transformer core shall be earthed to main frame of the enclosure at two independent points. i) The construction of transformer shall be rugged enough to withstand frequent transit & vibration during transportation from one site to another and during operation. j) Transformer shall be provided with suitable rating plate, diagram plate & lifting lugs. Supplier to ensure that lifting lugs have sufficient safety factor and high tensile strength suitable to take transformer load. k) Transformer to be painted as per standard industrial painting process however painting should be resistant to various chemicals used in drilling oil rigs. l) Cable terminal identification label (1U, 1V, 1W, 2U, 2V, 2W & 2N1, 2N2) of approximate 60 x 60mm size to be provided near glands for identification. m) Only tinned copper or phosphor bronze washer / spacer to be used. Also phosphor bronze screws shall be used, wherever required. n) Tubular insulators are not acceptable. Only epoxy insulators to be used, wherever required. o) Enclosure sheet of transformer shall not be less than 2mm thick sheet steel with louvers at all sides. p) Sketch No-CEE/ORE/4/4831, showing location of the transformer with available space, door location and opening is enclosed. After installation at site the transformer shall be accessible from two sides only i.e face C & D below flap type doors whereas remaining two sides i.e. A & B shall be non-accessible due presence of wall. Hence all the parts which require access during maintenance and inspection shall be face C or D only. Preferably, access cover for tapping shall be provided at the face D and rating plate & vector diagram to be provided on the face C. No projection of terminal box is permissible. - 4 -

04. RATING PLATE: Stainless steel / Anodised aluminum rating plate shall have information as per IS 11171-1985. Following minimum information to be provided necessarily on the rating plate. a) Transformer type b) IS followed c) Manufacturers name d) Manufacturers Sl No for the transformer e) Year of manufacturing f) Class of insulation g) Max possible temperature rise h) No of Phases i) Rated Frequency j) Rated Voltage including tapping k) Rated current for each winding l) Connection symbol m) Vector group n) Type of cooling o) Total weight Details of rating plate to be submitted by the supplier for approval after placement of PO. 05. ROUTINE & TYPE TESTS: The transformer shall be subjected to following tests as per IS 11171-1985 / IS 2026-1977 witnessed by BHEL and/or ultimate customer's representative for acceptance. a) Measurement of winding resistance 1. HV side in all taps 2. LV side b) Measurement of voltage ratio and checking of voltage vector relationship. c) Measurement of impedance voltage, short circuit impedance & load losses. d) Measurement of no load loss & current. e) Separate source voltage with stand test f) Induced voltage with stand test g) Temperature rise test h) Measurement of IR i) Core and Bolt test Inspection by BHEL or ultimate customer shall not relieve supplier form their warranty/after sales commitment in any manner. - 5 -

06. DOCUMENTS/INFORMATION TO BE SUBMITTED ALONG WITH OFFER: Following information or documents to be furnished by the supplier along with offer. SL Documents/Information 01 Type of transformer 02 Rating of transformer 3 Primary Winding Details 04 Secondary Winding Details 05 Reference standard/s 06 No of Phases 07 Rated Frequency 08 Vector Group 09 Type of Cooling 10 Impedance Voltage 11 Tapping on HV 12 Enclosure type 13 No Load losses at rated voltage 14 No load current at rated voltage 15 Total losses (Cu+ Iron) at rated load 16 Insulation class 17 Insulation level 18 Average temp rise of windings over ambient temp (50 Degree) 19 Dimension (L X B X H) 20 Winding material 21 Efficiency at unity PF at full load 22 Efficiency at unity PF at half load 23 Percentage Regulation at unity PF 24 Percentage Regulation at 0.8 PF (Lag) 25 Approx. weight of transformer in Kg Supplier to furnish details with their offer 07. DOCUMENTS TO BE SUBMITTED AFTER PLACEMENT OF PO FOR APPROVAL: Supplier shall furnish following drawings, documents or information within one week from the date of placement of PO for approval of BHEL. a) OGA drawing b) Exterior finish of transformer c) Details of rating & diagram plate d) Total Weight of transformer in Kg 08. WARRANTY: Supplier shall provide the guarantee / warrantee for the offered transformer for 12 months from the date of commissioning or 18 months from the date of supply, whichever is earlier. - 6 -

- 7 - Specification No-OR12423

- 8 - Specification No-OR12423

- 9 - Specification No-OR12423