ELECTRONIC SINGLE PHASE AND THREE PHASE L.V. METER SPECIFICATIONS

Similar documents
TECHNICAL DESCRIPTION THREE-PHASE SUBSTATION ELECTRONIC METERS

SULTANATE OF OMAN METERING AND DATA EXCHANGE CODE

Introduction DIN rail mounted electricity meters

DRAFT TANZANIA STANDARD (Draft for comments only) Part 8: Electricity metering minimum accuracy and environmental requirements

MT372 Three-phase electronic meter with built-in modem or RS485 communication interface

12/2 Product overview. 12/3 7KT1 14, 7KT1 53 E-counters. 12/9 7KT1 11, 7KT1 12 digital measuring devices. 12/11 7KT1 0 analog measuring devices

SINGLE PHASE STS PREPAID METER

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

DIRECT CONNECTED STATIC POLY PHASE ENERGY METER OF ACCURACY CLASS 1

E650 Series 3. Electricity Meters IEC/MID Industrial and Commercial ZMD402AT/CT, ZFD402AT/CT. Technical Data

Three phase CT Connection Smart Meter s Technical Specification

E550 Series 2. Electricity Meters IEC/MID Industrial and Commercial ZMG400AR/CR. Technical Data

E550 Series 2. Electricity Meters IEC/MID Industrial and Commercial ZMG310AR/CR. Technical Data

Power quality Harmonics up to 40th harmonic Unbalance, rotary field indication Distortion factor THD-U / THD-I

MID. Energy Management Energy Meter Type EM33 DIN. Product Description. How to order EM33 DIN AV3 3 X XS PF. Type Selection EM33 DIN

MID. Energy Management Energy Analyzer Type EM11 DIN. Product Description. How to order EM11 DIN AV8 1 X O1 PF. Type Selection EM11 DIN

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES)

Energy Management Three-phase energy meter with output modules Type EM4-DIN

PRODUCT LEAFLET AUGIER-BOX. Remote Monitoring Unit for Street Lighting /07/2011

071-3: 2009 CEB SPECIFICATION

ICARUS ELECTRONIC GAS VOLUME CONVERTER

Energy Management Energy Analyzer Type EM210 MID

Energy Management Energy Meter with plug-in Output Modules Type EM4-DIN

02/11/2015

INDUSTRIAL+COMMERCIAL ZMD310AT/CT TECHNICAL DATA. Measurement Accuracy. Measurement Behaviour. MID-specific data. Current (for Class B) General

Data Sheet. RISH Master Record %THD

02/11/2015

AMIK 200 / 201 Technical Data Sheet

FTU233. Ripple Control Receiver. Technical Data. Load Management Ripple Control

Installation and Operating Instructions

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

INDUSTRIAL+COMMERCIAL ZMD400AR/CR, ZFD400AR/CR TECHNICAL DATA. Frequency. IEC-specific data. Current. Measurement Accuracy.

MID. Energy Management Energy Meter Type EM23 DIN. Product Description. Type Selection. How to order EM23 DIN AV9 3 X O1 PF A EM23 DIN

Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302

THE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT

ME162 Single-Phase Electronic Meter

AM 160 AM 360. The meter is MID certified as well as WELMEC 7.2 compliant and has been designed to serve billing purposes.

SINGLE AND POLY-PHASE STATIC METERS

Environmental Influences. Display. Inputs and Outputs. Electromagnetic Compatibility. Communication Interfaces. Insulation Strenght.

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

Energy Management Energy Meter Type EM111

Energy Management Energy Meter Type EM112

ULTRA RAPID POWER QUALITY ANALYZER

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

ENCORE 300 SERIES INSTALLATION AND OPERATING INSTRUCTIONS

Power Meter Series PM3200 Functions and characteristics

Digital Multifunction Instrument - Rish Master 3440

ENGLISH 3 Phase Multi-function Power Meter 1/5A MID MID

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

Brunata Optuna H Ultrasonic energy meter Type 775 Installation Guide Edition 1.2

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID

Energy Management Energy Meter GM3T E GM3T-RS485 E

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

Centrale de mesure Power Meter PM500 Merlin Gerin

Custom "Compact" range with display CD20 Custom Part number

QUINT-PS AC/24DC/40

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

Energy Management Energy Meter Type EM21 72R Retro-Fit

Power quality Harmonics up to 40th harmonic Rotary field components Distortion factor THD-U / THD-I

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

PREMIER INSTALLATION AND OPERATING INSTRUCTIONS

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

ZHUHAI PILOT TECHNOLOGY CO., LTD.

"Modular" versions designed for application-specific functions LCD with 4 lines of 18 characters and configurable backlighting

AC/DC Current Oscilloscope Probe Model SL261

UMG 103. UMG 103 Universal measurement device for DIN rails. GridVis Analysis software. Harmonics. Measurement accuracy 0.5.

Checklist for electromechanical and electronic active energy meters in accordance with the MID Directive (2004/22/EC)

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

Integra 1560 and 1580 Digital Transducer Systems

EPM Single-point submetering system. imagination at work. Engineered for retrofit and new construction with power line communication capability

Side view View from below Rear view

Energy Management Energy Meter Type EM110

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

Measuring centers MC7x0 series Multifunction Meter MC740

Three-phase monitoring relay CM-PFS

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

The RSM shall be extensively used in field & laboratory for verification of the accuracy of all types of single-phase energy meters.

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features:

MT 560/UMT TRANSDUCER & ANALYZER

Specification for a Fully Automatic Meter Test Equipment for testing Three-phase/Single/Transformer operated/ reference Standard energy meters.

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

User Manual Single Phase Electronic Meter For Active Energy HXE12R

Test Specification for Type Approval

MHz FUNCTION GENERATOR INSTRUCTION MANUAL

CROSS Chassis from 160 A to 450 A

HAWK5000 Operators Manual

MINI-PS AC/24DC/1.3

DIGITAL SYNCHRONIZING UNIT KS3.2 SERVICE MANUAL. 144 x 144 x 77 mm C E R T I F I E D

POWER TRANSDUCERS FOR SINGLE-PHASE AND THREE-PHASE NETWORK ISO P11P, P13P and P13B mm SERVICE MANUAL

GIMA Multi-Function Electricity Meter OPERATOR S MANUAL

AMI-AS230 Single Phase Meter

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

INSTRUCTION MANUAL (ATEX / IECEx)

CAMTO. Arc detecting relay. system. January Revised August D D1200

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

MDW-45 Converter RS RS-422/485

Transcription:

HELLENIC ELECTRICITY DISTRIBUTION NETWORK OPERATOR S.A. NOTICE OF CALL FOR TENDERS No ND-207 PROJECT: Pilot Telemetering and Management System for the Electric Power Supply Demand by Residential and Small Commercial Consumers and Implementation of ELECTRONIC SINGLE PHASE AND THREE PHASE L.V. METER SPECIFICATIONS

CONTENTS SCOPE... 4 OPERATING CONDITIONS... 4 Operating Temperature... 4 Humidity... 4 TABLE OF CLIMATIC AND ENVIRONMENTAL CONDITIONS... 4 REGULATIONS - SPECIFICATIONS... 5 EQUIPMENT DESCRIPTION... 6 MECHANICAL REQUIREMENTS... 6 Terminals and Terminal Cover... 7 Nameplate... 8 Communication via the optical head (IR- Port)... 8 Physical requirements... 8 ELECTRICAL REQUIREMENTS... 9 Type of Connection to the Network... 9 METERING SYSTEM... 9 General... 9 Accuracy Class... 9 Operating Voltage Range... 9 Measured Current Range... 9 Load Capacity... 9 Network Frequency... 10 OPERATION REQUIREMENTS... 10 Starting current... 10 Accuracy... 10 Meter Power Supply... 10 Meter self-consumption... 10 Auxiliary Supply (Clock autonomy)... 11 REGISTERS... 11 2

Energy registers... 11 Historical data registers... 11 Instantaneous information... 11 Diagnostic functions... 11 Display readings... 12 Definition of Tariff Zones... 12 Time Switch / Calendars... 12 Real Time Clock (RTC)... 12 Display... 13 Load switch and push-button... 13 OUTPUTS... 14 Integrated Relay Output... 14 COMMUNICATION PROTOCOL... 15 COMMUNICATION WITH IN HOME DISPLAYS (IHD)... 15 CONNECTION WITH IN HOME DISPLAYS (IHD)... 16 ELECTROMAGNETIC COMPATIBILITY (EMC)... 16 HARMONIC DISTORTION 2-150 KHZ:... 17 COMMUNICATION INTERFACE... 17 ENERGY PROFILES RECORDING... 17 TAMPERING EVENT LOGGING... 17 DEFINITION OF TESTS... 19 Sample tests (acceptance tests)... 19 SPARE PARTS... 19 OPERATING INSTRUCTIONS... 20 METERS PARAMETERISATION... 20 GUARANTEE... 20 3

TECHNICAL SPECIFICATION ELECTRONIC SINGLE-PHASE AND THREE-PHASE L.V. METERS SCOPE This specification determines the construction, testing, acceptance check and packing for transportation and delivery to HEDNO warehouses of electronic single-phase and three-phase Low Voltage (L.V.) meters for direct connection to the network for energy measurement. OPERATING CONDITIONS Operating Temperature The temperature zone in which the meter functions properly must be between -20 C and +55 C. The storage and transport temperature zone shall be between -20 C and +70 C. Humidity The electronic meter shall operate under an average annual relative humidity of less than 75%. For 30 days in total interspersed within the year, it shall operate under relative humidity of 75% to 95 %. Additionally, at random moments within the day, it shall operate under relative humidity 85 % (IEC 62052). TABLE OF CLIMATIC AND ENVIRONMENTAL CONDITIONS Maximum altitude 2,000 m Minimum ambient temperature Average ambient temperature Maximum ambient temperature Maximum temperature at external surfaces due to solar radiation - 20 ο C 20 ο C 55 C 70 ο C Minimum relative humidity 5 % Maximum relative humidity 95 % 4

REGULATIONS - SPECIFICATIONS REGULATIONS EN / IEC62052/11 & EN/IEC62053/21-22-23 EN/IEC 62058-11 EN/IEC 62058-31 EN 50470-1 TITLE Alternating current static watt-hour meters for active energy (classes 0.5 & 1) Electricity metering equipment (A.C.) - Acceptance inspection Part 11: General acceptance inspection methods Electricity metering equipment (AC) - Acceptance inspection - Part 31: Particular requirements for static meters for active energy (classes 0,2 S, 0,5 S, 1 and 2) Electricity Metering equipment (a.c.) Part 1: General requirements, tests and test conditions - EN 50470-3 Metering equipment (class indexes A, B and C) Electricity Metering equipment (a.c.) Part 3: Particular requirements - EN / IEC 60529 EN/IEC 60068-2-6 EN/IEC 60068-2-30 EN/IEC 60695-2-1 EN/IEC 60695-2-2 CENELEC / TC13 Static meters for active energy (class indexes A, B and C) Degrees of protection provided by enclosures. Basic environmental testing Procedures Part 2: Tests. Test EA : shock Basic environmental testing Procedures Part 2: Tests. Test Db and guidance: Damp, neat cyclic (12 + 12 - hour cycle). Fire hazard testing part 2: test methods. Glow wire test and guidance. Fire hazard testing part 2: Test methods Needle flame test. CENELEC technical body responsible for equipment for electrical energy measurement and load control. 1. The electronic meters shall be industrial products manufactured according to the International-European EN/IEC regulations / standards and to the Technical Specifications of HEDNO as mentioned above, which are valid on the day of the submission of the bids as well as on the day of installation and delivery. 5

2. In cases where the requirements of this Specification contradict with the above editions of International Regulations / Standards or any other relevant Standards, the corresponding HEDNO specification shall prevail. 3. The meters shall have markings pursuant to the European Standards, and they are also required to have the "CE" conformity mark. 4. The offered meters for residential and light/small commercial applications shall be of class B, in compliance with the EU Directive 2004/22/EC (Measuring Instruments) and according to the Ministry Decision (Government Gazette 521 / issue B / 12.04.2007, No. F2-1393). 5. All necessary certificates for the above compliance, that have been issued for the offered meters by a competent Notified Body, should be submitted. 6. Moreover, the supplier of the meters shall submit a certificate certifying that the meters are calibrated in facilities which are compliant with ISO 9001 as well as ISO/IEC 17025. EQUIPMENT DESCRIPTION MECHANICAL REQUIREMENTS Cover 7. The electronic meter shall be designed and manufactured according to the protection class IP51 as specified in EN/IEC 60529 for indoor installation (but with the meter covers closed). 8. The cover window shall be made of a high purity transparent material, enabling the meter's readings to be easily read even after 15 years exposure to the sun. 9. The support dimensions of the meter shall be according to DIN 43857. 10. The meter cover shall be according to DIN 43857 for standardized connection of the phase and neutral conductors and for the connection of the signal outputs, communication units etc. The meter cover shall be according to the IEC specifications for direct connection of the phase and neutral conductors as well as the pulses output, signal-output, communication device by terminal blocks. The meter width shall be according to DIN 43857. 11. The electronic meter cover shall contain a communication port which is accessible through an optical head, which shall be waterproof. 12. The electronic meter shall be properly connected to the communication medium each time used (PLC, GSM/GPRS, etc.). It must be possible to secure the said 6

communication device inside the meter s housing or inside the meter s cover. 13. The communication with the optical head port must be performed in accordance with EN 62056-21:2002. 14. The electronic meter must be delivered with its cover sealed or completely closed (glued). 15. In case that the meter is delivered with sealed (glued) cover, every attempt to open it shall result in a broken box in a visible manner. 16. In case that the meter is delivered with sealed (glued) cover, if opened, an internal tamper alarm shall be triggered. 17. It shall be possible to perform the following tasks without unsealing the meter cover: Reading through the display and activation of its functions by button (push buttons). Reading of the meter's characteristics (name table). Programming and reading of the electronic meter by a laptop computer or portable handheld unit, using the optical communication port. Manual reconnection of supply via a waterproof button (push button) mounted on the front cover. Note that it is intended that only authorized HEDNO personnel would utilize this method, as the button is not generally accessible by the consumer. Check of measuring accuracy of active energy by a pulse signal from a LED installed on the front cover of the meter. Terminals and Terminal Cover 18. The size and position of the terminals shall be according to DIN 43857 EN/IEC standards. For single-phase meters, the terminals shall be able to connect stranded cable of minimum cross-section 4 mm 2 and maximum cross-section 35 mm 2. For three-phase meters, the terminals shall be able to connect stranded cable of cross-section at least 25 mm 2. The minimum cross-section for connection of stranded cable at the signal or pulse terminals shall be at least: 1 mm 2 The terminals for output pulses, signal outputs, communication device shall be of spring type without tightening screws. 19. The terminals shall be of front connection type and shall have lifted insulation 7

diaphragms in order to provide protection against accidental short-circuits between phases and neutral during the connection or disconnection of the meter. 20. Each terminal shall have at least two terminal screws for tighening in order to ensure proper electric contact and no risk of temperature rise or conductor loosening under normal operating conditions. 21. The terminal s cover shall feature a tampering alarm and be sealed, so that any internal intervention in the terminals requires breaking the cover seals with simultaneous activation of the alarm signal, while the terminals position shall be according to VDE-0418. Nameplate 22. The nameplate of the meter shall be in compliance with the EU Directive 2004/22/EC (Measuring Instruments), according to the Ministry Decision no. F2-1393 (Government Gazette 521 / issue B / 12.04.2007 No F2-1393). 23. The nameplate shall be designed and installed so that the following capacities or information are provided: The PPC S.A. logo. The meter constant. The symbol for double insulation protection and the CE mark for compatibility with EU regulations/standards. Meter information (including but not limited to meter type, serial number, nominal values / ratings, year of manufacture). The nominal values shall include nominal voltage, nominal current and maximum voltage. Communication via the optical head (IR- Port) 24. The electronic meter shall be equipped with a communication port through an optical head. The communication port shall be infrared type (IR - Port). 25. The communication protocol of the IR Port shall be in accordance with EN 62056-21:2002. 26. The optical head shall be read through a portable handheld device or PC/laptop. The optical head shall be self-supported in a manner that does not affect the proper operation of the meter (e.g. magnetic). Physical requirements 27. The electronic meter shall be manufactured according to the requirements of DIN 43857-1 and DIN 43857-2. This facilitates the installation of the meter 8

inside meter cabinets standardized by HEDNO. ELECTRICAL REQUIREMENTS Type of Connection to the Network 28. The electronic meter must be designed for connection to a low voltage network. METERING SYSTEM General 29. The metering system must be digital for direct connection to the network. 30. The meter must calculate at least the following: Incoming Outgoing active energy Incoming Outgoing reactive energy (for three-phase meters) Voltage and current Phase sequence (for three-phase meters) Direction of energy flow Accuracy Class 31. For residential and small commercial meters, the electronic meter shall be of accuracy class B. Operating Voltage Range 32. The meter shall be suitable for operation with rated voltage 230 Volts, and shall operate within a voltage range of 0,8 to 1,15xUn (where Un is the nominal voltage). Measured Current Range 33. The meter maximum current shall be Imax = 60 A for single phase meters. 34. The meter maximum current shall be Imax = 100 A for three phase meters. 35. The meter shall have basic current value Ib = 10 A. Load Capacity 36. The meter must withstand overload according to EN/IEC 62052-11, 62053-21,- 22 and -23 and EN 50470. 9

Network Frequency 37. The electronic meter shall operate at a network frequency of 50 Hz and a variation zone of ±2%. OPERATION REQUIREMENTS Starting current 38. The direct connected electronic meter shall begin the energy measuring when the current reaches at least 0.5% of the nominal current In, according to EN 50470-3. 39. The electronic meter shall use the starting power instead of the starting current in order to define the starting limit. Accuracy 40. The electronic meter shall achieve the required accuracy for power measuring (W) according to EN/IEC 62053 and EN 50470. Meter Power Supply 41. The meter shall be suitable for low voltage measuring, with nominal network voltage 230/400V (± 10%, in accordance with EN/IEC 62053-22 and EN/IEC 62053-11). 42. The electronic meter shall be able to operate in each of the following cases of power failure, with the accuracy that characterizes the corresponding voltage asymmetry: Neutral loss Phase(s) loss in three-phase meter Neutral inversion 43. Upon voltage restoration, the meter must return to normal operation in 5 seconds at maximum. 44. The electronic meter must be consistent with EN/IEC 62053, EN 50470 with regard to the overload and over-current requirements. 45. In case of continuous voltage loss, the meter non-volatile memory shall permit information retrieval after a period of 10 years without any auxiliary supply. Meter self-consumption 10

46. The energy consumption shall be according to EN / IEC 62052-11, EN/IEC 62053/21-22-23 for multifunctional meters. 47. Without the communications unit and the display backlight the energy selfconsumption shall not exceed the values specified in EN/IEC 62052-11 & EN/IEC 62053/21-22-23. Auxiliary Supply (Clock autonomy) 48.The auxiliary supply shall provide power only to the real time clock (R.T.C). 49.The meter shall be equipped with: Lithium battery capable of providing sufficient energy for the operation of the internal clock (R.T.C) for three years at least (without the meter being connected to the network). The battery s life-time with the meter connected to the network shall be at least 10 years, with a maximum loss of 10% due to self-discharge. OR / AND Super-capacitor. 50.In any case the billing values of the meter must be reserved in its memory for at least ten (10) years. REGISTERS Energy registers 51.The meter shall be provided with at least six (6) tariff zones with the relevant (12) incoming and outgoing energy registers. Historical data registers 52. The control of the integration period shall be performed by the internal calendar clock of the meter. 53. Integration period shall be programmable from 5 to 60 minutes (5, 10, 15, 20, 30 and 60). Instantaneous information 54. The registers of the measured quantities shall be updated at least every second. 55. This information shall be available to be shown on the display or to be registered as events. Diagnostic functions 11

56. The electronic meter shall perform a diagnostic check of its circuits each time it is placed under voltage, after every voltage outage and at regular time intervals. 57. In case an error is detected, a corresponding fault message, identifiable by the optical head and via telemetering, shall be displayed on the meter display. Display readings 58. Beyond measuring information (energy registers, instantaneous values of current-voltage-power, network quality data), the meter shall store in its memory and shall be programmable which of the following additional information shall be shown on the display: Meter serial number (up to 12 digits) Current date and time Tariff zone / calendar information Status of the load switch Error indication Definition of Tariff Zones 59.The definition of the meter's tariff zones shall be performed with the following methods: through the internal time switch through appropriate meter programming 60.The meter shall have a minimum of 6 zones. Time Switch / Calendars 61. The meter must be equipped with a calendar time switch for changing tariff zones and determine the end of the billing period. 62. The clock mechanism shall be high precision Quartz (<5 ppm deviation +/- 20%). Real Time Clock (RTC) 63. The clock shall provide all required timings for the proper operation of the meters. 64. The calendar shall support leap years and programming of daylight time adjustment. 65. The clock shall support automatic change to/from daylight time according to the 12

European standard. 66. When synchronization is performed by internal crystal, the achieved accuracy shall be greater than 5 ppm (deviation +/- 20%). 67. Moreover, synchronization accuracy of one second shall be achieved through the communication unit. Display 68. The display shall be able to show information from the energy registers and information from the historical registers, which have been defined through programming. 69. The information shall be read based on CENELEC methods and standards. The decimal digits, the units, the multipliers, the content and the display sequence shall be defined through programming. 70. Similarly, the list content and the display sequence shall be defined through programming. 71. It is required to include at least the following readings: Units: W, kw, Kvar, Kvarh, Wh, kwh, V, A Units: Kvar, Kvarh for three-phase meters Error code State of selected Outputs including the load switch Active tariff zone 72.The meter display must be visible from a distance of 1m below and 0.75m horizontally from the front side of the meter (observation angle 30 o ). All screens shall be visible under low lighting conditions. 73.The date display type shall be user-definable as follows: yy/mm/dd 74.The meter shall support the following operation modes of the display: Normal (automatic scrolling of displayed information) Technical Check (Programming - Set mode) Load switch and push-button 75. The load switch shall not require maintenance throughout the meter s lifecycle. 76. The push-button of the load switch must have a lifecycle of at least 10,000 switching operations under full nominal load with power factor 1. 13

77. The load switch shall be adjustable relative to the power of the customer s supply. 78. The load switching capability shall be according to IEC 62055-31 UC2. 79. The push button of the load switch shall change state (connection/ disconnection) only following a relevant order in one of the following functions: 1. Local operation: authorized utility personnel can use the local button to manually connect or disconnect. In this operating mode, remote disconnection is possible, but remote connection is not. 2. Remote operation: This operating mode does not allow local operation (manual disconnection and connection). To safely execute remote reconnection of a disconnected customer, local operation mode is provided and, then, the operator may reconnect his supply. 3. Alternating operation: the operating mode of the push-button s disconnection switch must enable remote alternation between remote operation" and local operation and vice-versa. 80. The default operating mode of the disconnection switch when delivered must be local operation. 81. For reconnection, when the load is disconnected, consumer action is required as follows: a. The central system transmits a command enabling the meter to reconnect. b. Consumer opens (OFF state) the general switch of the internal electrical installation, which is detected by the meter. Subsequently, the consumer closes his general switch (ON state). 82. During a power outage, the load switch must be kept in the same position as before the power outage. 83. After power restoration, the load switch must be kept in the same position as before the power outage. 84. The state of the disconnection switch shall be remotely readable and any change must be registered in a special file. 85. Load Limitation: The meter shall permit remote setting of load limits. OUTPUTS Integrated Relay Output 86. At least 1 integrated relay output shall be included in all meters to provide 14

information or/and remote switching capability (on/off) of individual customer circuits. 87. The relay output will be capable of operating a relay. 88. The technical specifications of the relay output are the following: Solid state relay, Voltage 12-240 V ac/dc, Minimum current 100mA 89. The above relay output should be programmable remotely by the parameterization software of the meters. COMMUNICATION PROTOCOL 90. Meters must be compatible with standards approved by CENELEC or/and emerging standards that are currently under final evaluation by CENELEC/TC13 committee (Meters & More, Prime, G3-PLC, CX-1, OSGP). 91. At the physical layer, any technology is accepted. A minimum communication speed of 4.8 Kbits/sec is required. All communication technologies (GPRS, Multicarrier, S-FSK, B-PSK, etc) are accepted. 92. At the data link layer any kind of technology is accepted (included among others, TCP/UDP IP and 1334-LLC). 93. At the application layer, full compatibility with COSEM-OBIS/DLMS standard is required. 94. All above must be documented by compliance certification according to DLMS User Association procedure. http://www.dlms.com/conformance/certificationprocess/index.html 95. Required speed of at least 4.8 kbits/s must be certified by a certificate issued by a laboratory certified according to ISO / IEC 17025 standard. COMMUNICATION WITH IN HOME DISPLAYS (IHD) 96. The electronic meter must ensure communication with the in home display (IHD) used. In any case, the meter must transmit readings to the in home display at a range of at least thirty (30) meters inside a building constructed by reinforced concrete. 97. The electronic meter shall communicate with in-home displays via radiofrequency methods (Bluetooth, Zigbee, etc.) or via PLC. 98. The Contractor shall specify the commications method between electronic meter 15

and the IHD as well as the protocols used, in his Tender offer. 99. The electronic meter shall transmit, to the in home displays, the real-time consumption in KW at least once per 30 seconds. 100. The electronic meter shall transmit at least meter details such as supply number, serial number, MAC address or equivalent unique identifier, and the number of domestic network to which it is connected. 101. The electronic meter shall also transmit the local time to the in home displays. 102. The electronic meter shall transmit simple messages to in home displays including: Greetings Special Information A warning for scheduled power interruptions. CONNECTION WITH IN HOME DISPLAYS (IHD) 103. The electronic meter shall be capable of being paired remotely with in home displays. 104. The electronic meter shall be capable of being connected locally with in home displays. The electronic meter shall only be paired with an in-home display based on the MAC address or other equivalent unique identifier. 105. Communication between the electronic meter and the in home display shall be secure and encrypted. 106. The pairing state of the electronic meter with the in home display shall be possible to be remotely monitored. 107. Upon loss of power and subsequent restoration, the electronic meter shall automatically be paired with the previously authorized in home display. ELECTROMAGNETIC COMPATIBILITY (EMC) 108. The meter shall comply with the following standards: Electrostatic discharge according to IEC 61000-42 High frequency electromagnetic field according to IEC 61000-4-4 Line transients according to IEC 61000-4-4 Radio interference attenuation according to IEC/CISPR22 class B 16

HARMONIC DISTORTION 2-150 KHZ: The offered meter should satisfy tests regarding its tolerance to the influence of symmetric high frequency currents (range 2kHz - 150kHz), such as those produced by photovoltaic inverters. Successful test results of the offered meter should be proved by the respective test certificate or test protocol issued by a certified by EN ISO / IEC 17025: 2005 test laboratory. Meters must comply with the Test Procedure as defined in the technical report of CENELEC CLC / TR 50579. COMMUNICATION INTERFACE 109. The electronic meter shall be capable of communicating via modem GSM/GPRS, PLC, etc. for telemetering parameterization. 110. The communication modem may be provided inside the meter (On Board), plugin/modular, or external. 111. When the communication device is not modular and must be installed as external, meter must feature an RS485 communication port. 112. The communication port (if such port exists), shall be in a protected, confined point of the meter, not accessible by non-authorized personnel. 113. Access to the communication port must be protected with a tampering event logging. ENERGY PROFILES RECORDING 114. Meters must be capable of load profiles recording for the following quantities: Incoming Outgoing active energy Incoming Outgoing reactive energy 115. For integration period of 15 min, load profile data shall be stored for at least the last sixty (60) days. 116. Internal memory shall be non-volatile for a minimum preservation time of 10 years. TAMPERING EVENT LOGGING 117. The meter shall have the capability, via appropriate arrangements and parameterization, of detecting and logging at least the following events, of potential attempt for tampering the meter while in normal operation under voltage (each event individually), by logging the time (date and hour) of 17

appearance and disappearance of each event: strong DC magnetic field influence; terminals cover removal; tampering/ any form of removal of the modem cover or connections; 118. The electronic meter shall use passwords to restrict the access to the meter for data reading, parameterization, etc. POWER QUALITY MONITORING 119. The meter shall have the capability, via appropriate parameterization for the definition of the measured quantities thresholds, of monitoring at least the following events (each event individually), by logging the time (date and time) of appearance and disappearance of each event: under-voltage (phase to neutral) over-voltage (phase to neutral) over-current power-down power-up METER HEALTH MONITORING 120. The meter shall have the capability to detect and log the following events: Battery low Meter error malfunction code Meter reprogrammed status/feedback Meter communication complete Meter communication failed Load control switch state REMOTE CONFIGURATION AND FIRMWARE UPGRADE 121. The electronic meter shall be capable of local and remote configuration. 122. Firmware for the electronic meter shall be capable of being deployed remotely via the engaged communication method. 123. Changes in firmware or configuration shall be acknowledged by the meter via 18

communication with the central system. 124. Firmware upgrades for the electronic meter shall be validated upon sending (local or remote) and shall be able to be held inactive until activation at a certain future time. TESTS DEFINITION OF TESTS Type Tests All tests intended for identifying the type characteristics of the meter in order to prove the compliance with the requirements of the relevant standards/regulations that these characteristics are required to comply with. Series tests Tests performed on new meters to ensure that they comply with the results of the above tests or to prove that the batch meets the specialized general and specific requirements of the relevant specification. Acceptance tests Sampling tests performed on a batch of meters prior to delivery for the purpose of making a decision regarding the acceptance or rejection of the batch. All tests shall be performed as described in each relevant and most recent issue of the IEC standards. Sample tests (acceptance tests) 125. Sampling tests for acceptance during the acceptance check are all the tests specified in IEC EN 62058-31. 126. The sampling procedure for the tests shall be according to IEC 60410 using the following criteria: Test level II table I, IEC 60410. Simple or double sampling (tables II and III, IEC 60410). Acceptable quality level A.Q.L. = 1 for each separate test. SPARE PARTS 127. The suppliers shall guarantee the availability of spare parts for a period of 5 years after the end of the warranty period. 128. The suppliers are required to submit, together with their bid, a price list for the 19

necessary spare parts. OPERATING INSTRUCTIONS 129. Bidders shall submit in their offers, the operating instructions manual of the meters. METERS PARAMETERISATION 130. The meters shall be delivered programmed with the parameterization that will be advised and agreed by HEDNO, during the sample approval procedure, before the starting of the series production of the meters. 131. The meters shall be delivered with the real-time clock (RTC) programmed at the local time in Greece. GUARANTEE 132. The meters shall be accompanied by five (5) years warranty from their delivery date. 20