Modeling and Simulation of 6-Pulse and 12-Pulse Rectifiers under Balanced and Unbalanced Conditions with Impacts to Input Current Harmonics

Similar documents
Modeling and Simulation of Paralleled Series-Loaded-Resonant Converter

Various Modeling Methods For The Analysis Of A Three Phase Diode Bridge Rectifier And A Three Phase Inverter

Design and Analysis of Two-Phase Boost DC-DC Converter

Comparative Study of Sinusoidal Pulse Width and Hysteresis Modulations in Current Source Inverter

Single Switch Forward Converter

Harmonic Analysis of Output Voltage of Single phase AC Voltage Controllers

CHAPTER 1 INTRODUCTION

A Single Phase Single Stage AC/DC Converter with High Input Power Factor and Tight Output Voltage Regulation

Comparative Study of Pulse Width Modulated and Phase Controlled Rectifiers

Effective Harmonic Mitigation with Active Filters

ANALYSIS OF POWER QUALITY IMPROVEMENT OF BLDC MOTOR DRIVE USING CUK CONVERTER OPERATING IN DISCONTINUOUS CONDUCTION MODE

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

New Converter for SRM Drive With Power Factor Correction

CHAPTER 3 H BRIDGE BASED DVR SYSTEM

CHAPTER 4 PI CONTROLLER BASED LCL RESONANT CONVERTER

ISSN Vol.03,Issue.07, August-2015, Pages:

A BRUSHLESS DC MOTOR DRIVE WITH POWER FACTOR CORRECTION USING ISOLATED ZETA CONVERTER

CHAPTER-III MODELING AND IMPLEMENTATION OF PMBLDC MOTOR DRIVE

ELEC 387 Power electronics Study of flyback stepdown converter and comparison with buck converter

Power Factor Pre-regulator Using Constant Tolerance Band Control Scheme

Understanding Input Harmonics and Techniques to Mitigate Them

Power Quality Notes 2-1 (MT)

Unipolar and Bipolar PWM Inverter

Modeling and Simulation of Synchronizing System for Grid-Connected PV/Wind Hybrid Generation

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

International Journal of Modern Engineering and Research Technology

Harmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with Matrix AP Harmonic Filter vs. AFE Drive

Converters with Power Factor Correction

Harmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with MTE Matrix AP Harmonic Filter vs. 18-Pulse Drive

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL

CHOICE OF HIGH FREQUENCY INVERTERS AND SEMICONDUCTOR SWITCHES

Use of Advanced Unipolar SPWM Technique for Higher Efficiency High Power Applications

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

Simulation & Implementation Of Three Phase Induction Motor On Single Phase By Using PWM Techniques

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, VARIATION OF HARMONICS AND RIPPLE WITH PULSE NUMBER Pulse Number

Three Phase Five Level Inverter with SPWM fed from Hybrid Renewable Energy Based Induction Motor Drive

2020 P a g e. Figure.2: Line diagram of series active power filter.

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM

Lecture Note. DC-AC PWM Inverters. Prepared by Dr. Oday A Ahmed Website:

Harmonics Elimination Using Shunt Active Filter

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

14. DC to AC Converters

( ) ON s inductance of 10 mh. The motor draws an average current of 20A at a constant back emf of 80 V, under steady state.

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

Comparative Analysis of Control Strategies for Modular Multilevel Converters

THE third-harmonic current injection is a method to reduce

Australian Journal of Basic and Applied Sciences. Simulation and Analysis of Closed loop Control of Multilevel Inverter fed AC Drives

Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks

[Ahmed, 3(1): January, 2014] ISSN: Impact Factor: 1.852

A New Active Interphase Reactor for 12-Pulse Rectifiers Provides Clean Power Utility Interface

MULTICARRIER TRAPEZOIDAL PWM STRATEGIES FOR A SINGLE PHASE FIVE LEVEL CASCADED INVERTER

POWER QUALITY ENHANCEMENT USING BRIDGELESS CONVERTER BASED ON MULTIPLE OUTPUT SMPS

POWER FACTOR CORRECTION OF ELECTRONIC BALLAST FOR FLUORESCENT LAMPS BY BOOST TOPOLOGY

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

Dr.Arkan A.Hussein Power Electronics Fourth Class. Operation and Analysis of the Three Phase Fully Controlled Bridge Converter

SPICE for Power Electronics and Electric Power

Hardware Implementation of SPWM Based Diode Clamped Multilevel Invertr

Design of a Cell Charger for an ipad Using Full Bridge Rectifier and Flyback Converter

Third Harmonics Injection Applied To Three Phase/Three Level/Three Switch Unidirectional PWM Rectifier

Hybrid PWM switching scheme for a three level neutral point clamped inverter

Design of Three Phase PWM Voltage Source Inverter for Induction Heater

Bridgeless Cuk Power Factor Corrector with Regulated Output Voltage

Three Phase Induction Motor Drive Using Single Phase Inverter and Constant V/F method

DC-DC Resonant converters with APWM control

ANALYSIS AND DESIGN OF CONTINUOUS INPUT CURRENT MULTIPHASE INTERLEAVED BUCK CONVERTER

CHAPTER 4 FULL WAVE RECTIFIER. AC DC Conversion

Highly Efficient Ultra-Compact Isolated DC-DC Converter with Fully Integrated Active Clamping H-Bridge and Synchronous Rectifier

Modeling of Single Stage Grid-Connected Buck-Boost Inverter for Domestic Applications Maruthi Banakar 1 Mrs. Ramya N 2

Bidirectional Ac/Dc Converter with Reduced Switching Losses using Feed Forward Control

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

A VARIABLE SPEED PFC CONVERTER FOR BRUSHLESS SRM DRIVE

SPICE FOR POWER ELECTRONICS AND ELECTRIC POWER

FOURIER ANALYSIS OF A SINGLE-PHASE FULL BRIDGE RECTIFIER USING MATLAB

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Multiphase Interleaving Buck Converter With Input-Output Bypass Capacitor

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Fig.1. A Block Diagram of dc-dc Converter System

Three phase six-switch PWM buck rectifier with power factor improvement

Harmonics White Paper

AC : AN ACTIVE POWER FACTOR CORRECTION LABORA- TORY EXPERIMENT FOR POWER ELECTRONICS COURSE

PERFORMANCE ANALYSIS OF A NEW CONVERTER FOR SWITCHED RELUCTANCE MOTOR DRIVE WITH COMPONENT SHARING

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Single Phase Bridgeless SEPIC Converter with High Power Factor

ITEE Journal Information Technology & Electrical Engineering

Direct AC/AC power converter for wind power application

Hybrid Power Quality Compensator for Traction Power System with Photovoltaic Array

A Comparison on Power Electronic Inverter Topologies

Switching Angles and DC Link Voltages Optimization for. Multilevel Cascade Inverters

An Adjustable-Speed PFC Bridgeless Single Switch SEPIC Converter-Fed BLDC Motor

A Novel Power Factor Correction Rectifier for Enhancing Power Quality

Technical Paper. Harmonic Distortion in Data Centers

CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER

COMPARISON OF POWER QUALITY SOLUTIONS USING ACTIVE AND PASSIVE RECTIFICATION FOR MORE ELECTRIC AIRCRAFT

Brushless DC Motor Drive using Modified Converter with Minimum Current Algorithm

An Active Interphase Transformer for 12-Pulse Rectifier System to Get the Performance Like 24- Pulse Rectifier System

Small-Signal Model and Dynamic Analysis of Three-Phase AC/DC Full-Bridge Current Injection Series Resonant Converter (FBCISRC)

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

AC VOLTAGE CONTROLLER (RMS VOLTAGE CONTROLLERS)

A New Single Switch Bridgeless SEPIC PFC Converter with Low Cost, Low THD and High PF

Transcription:

Second Asia International Conference on Modelling & Simulation Modeling and Simulation of 6-Pulse and 12-Pulse Rectifiers under Balanced and Unbalanced Conditions with Impacts to Input Current Harmonics Arief Hernadi (1), Taufik (2), and Makbul Anwari (3) (1)(2) Electrical Engineering Department Cal Poly State University San Luis Obispo, CA 9347 USA ahernadi@calpoly.edu taufik@calpoly.edu Abstract This paper discusses the impact of using 6-pulse and 12-pulse rectifier circuit commonly found in Adjustable Speed Drives. The 12-pulse topology is known to be more expensive, but produce the least input current harmonics. However, the latter statement is completely true under balanced line conditions. In practice, the lines are inherently unbalanced. Hence, the question of whether the 12-pulse rectifier will indeed perform better in terms of the harmonics injected to the line is still under on-going discussions. This paper presents the modeling and simulation of both rectifier topologies to compare their input current harmonics. The rectifiers are modeled using OrCAD Pspice and several common cases of line conditions will be simulated to compare their harmonic levels. Results of the simulations pertaining to their Total Harmonic Distortions for each case will be explored. 1. Introduction As technology grows everyday, the study of power systems has shifted its direction to power electronics to produce the most efficient energy conversion. Power electronics is the study of processing and controlling the flow of electric energy by supplying voltages and currents in a form that is suited for user loads [1]. The goals of using power electronics are to obtain the benefit of lower cost, small power loss and high energy efficiency. Because of high energy efficiency, the removal of heat generated due to dissipated energy is lower. Other advantages of power electronics are reduction in size, weight, and overall cost. Like other technologies, power electronics has certain disadvantages. One major shortcoming is the generation of harmonic voltages and currents. To filter (3) Department of Energy Conversion Universiti of Teknologi Malaysia Skudai, Malaysia makbul@ieee.org out harmonics, more components and money would be needed for a given project. Having harmonics produced by power electronics will result in upstream losses in windings and in transformers in the system. A rectifier is a power electronic circuit that is used to convert ac signals into dc signals. A rectifier is a power processor that should give a dc output voltage with a minimum amount of harmonic contents [2]. When a polyphase ac is rectified, the phase-shifted pulses overlap each other which produce a smoother dc output than that made by a single-phase ac rectifier. This is considered as an advantage in high-power rectifier circuits, where the actual size of filtering components would be prohibitive in spite of their necessity to obtain low-noise dc power [3]. When a three-phase input is available, rectifiers can come in a variety of pulses such as the 6-pulse and 12-pulse. As the number of pulses increases, the input characteristic improves. This results from a greater number of pulses in a given period which is due to the larger number of diodes used. This, in turn, makes the 12-pulse rectifier more costly. However, the analysis commonly done to exhibit the advantage of lower input harmonics for the 12-pulse is done under steady-state balanced line condition. In practice, line condition is inherently unbalanced due to the fact that the threephase lines are loaded differently in each of its three lines. Therefore, the study of how input current harmonics are impacted under unbalanced line conditions should be conducted to help determine cost vs. benefit considerations when implemented in commonly used controllers such as the Adjustable Speed Drives. Such study using hardware implementation has been done and was reported in [4]. However, the study was performed under certain operating conditions and the results are not representative of any other conditions in general. Besides, the actual system implemented for the study 978--7695-3136-6/8 $25. 28 IEEE DOI 1.119/AMS.28.88 134

can be quite costly, thus it will be impractical to perform similar study for other operating conditions. Therefore, the most economical and practical method to perform this study is through the use of computer simulation. This paper describes the modeling of 6-pulse and 12-pulse rectifiers operating under unbalanced conditions. Examples of case studies were performed using the model and results will be presented. The model uses Orcad Pspice and could be easily adapted to learn the impact of any unbalanced conditions to rectifier s input current harmonics. 2. 6-Pulse and 12-Pulse Rectifier Models Figure 1 shows schematic of the 6-pulse bridge rectifier using Orcad Capture. The input represents three-phase voltages whose amplitude may easily be adjusted to any desired values which reflects the percentage of unbalance in the system. The phases of the three phase voltages follow the positive sequence convention. The series resistances on both the primary and secondary sides are needed to prevent convergence and inductance loop errors. The output resistance was chosen to enable users to adjust to the desired rms of input currents. The transformers represent a Y-Y connected three-phase transformer formed by three single-phase transformers where each is modeled using a part called the K_linear. The turns ratio (N S /N P ) of each transformer can be conveniently adjusted by the value of their primary (L P ) and secondary (L S ) inductances following equation: N N P S = L S L P For the model presented in this paper, as shown in Figure 1, a turns ratio of 1:1 was selected. Since all three single-phase transformers use the same turns ratio, the part called PARAMETERS is being used. The part allows users to define some global parameters whose values may be used repetitively in any of the components on the schematic. The diodes in the schematic are closed to an ideal diode model called the diode. With this diode model, users may conveniently adjust diode parameters most suited for their applications. R7 PARAMETERS: Lin = H Lout = H R36 TX14 D45 D46 VOFF = VAMPL =.5m FREQ = 6 V4 D47 D48 VOFF = VAMPL =.5m FREQ = 6 V5 R2 R3 TX4 TX5 R8 R9 D49 D5 R6. V6 VOFF = VAMPL =.5m FREQ = 6 R4 R5 Figure 1. 6-Pulse bridge rectifier schematic 135.

VOFF = VAMPL = 17 FREQ = 6 PHASE = V1 R19 TX1 R22 D1 D3 D2 D4 PARAM ET ERS: L1_Y = H L2_Y = H L1_D = H L2_D =.57735uH Rload = 1 VOFF = VAMPL = 17 FREQ = 6 PHASE = 12 V2 R2 TX2 R23 D5 D6 R21 TX3 R24 VOFF = VAMPL = 17 FREQ = 6 PHASE = 24 V3 R1 {Rload} R26 R25 R14 TX8 R16 D9 D1 R15 TX9 R17 D11 D12 R39 TX1 R18 D13 D14 R27 Figure 2. 12-pulse bridge rectifier schematic Figure 2 depicts the 12-pulse bridge rectifier. The model is constructed using two 6-pulse bridge rectifiers in series. The same three phase voltages are connected at the input of both rectifiers. However, as shown in Figure 2, the first rectifier is fed from a Y- Y connected transformer, while the other rectifier is fed from a -Y connected transformer to introduce the necessary phase shift to produce the 12 pulses affect on its dc output. Since the voltage gain in -Y differs from that of Y-Y by a factor of 3, hence the turns ratio for the -Y has to be adjusted accordingly, as shown under the PARAMETERS part of Figure 2. 1. Balanced 3-Phase System as the baseline case 2. Case 1: Unbalanced with V A = 12V + 3%, while the other two voltages are at 12V 3. Case 2: Unbalanced with both V A and V B = 12V + 3%, while V C = 12V 4. Case 3: Unbalanced with both V A = 12V + 3%, V B = 12V, and V C = 12V 3% 3. Simulation Results Both rectifier models were simulated. To demonstrate the validity of the models, an example of input line current for the 12-pulse is shown in Figure 3 at 2% (dotted line) and 1% load (solid line). The model indeed draws multiple-step current waveform as one would expect from a 12-pulse rectifier. In this paper, the results of the following case examples will be presented: Figure 3. Line current in 12-pulse bridge rectifier Note that the above cases and voltage values are selected arbitrarily with the 3% variation comes from 136

common practical tolerance limit typically imposed by utility companies. Based on the above case examples, results in terms of the total harmonic distortions (THD) of input line currents are presented in Figures 4, 5, and 6. Interestingly, the results in general showcase the advantage of the 12-pulse rectifier over their 6-pulse counterpart. But first, Figure 4 depicts the level of THD for all four case studies done on the 6-pulse rectifier. Although the percentage difference is not significant; however it clearly shows that in certain percentages of load, the balanced system produces THD of input line current worse than that of the unbalanced cases. As evidenced in Figure 4, this occurs when the load is less than 3% or higher than 8%. Moreover, it is interesting to observe that case 1 always produces the least amount of THD. and case 2 overall gives out the highest THDs. It is also interesting to note that under balanced system, the THD line current is significantly better at load higher than 8%. Figure 6 combines results from both the 6-pulse and the 12-pulse rectifiers to compare performance of both rectifiers. As can be seen from Figure 6, the 12- pulse rectifier clearly outperforms the 6-pulse in all four case examples. This surely justifies the higher cost of the 12-pulse as compared to the 6-pulse. The difference in the THD of line current can be as much as 17%. In practice, this translates to higher filtering requirement for the 6-pulse which add up to the installation cost. One very interesting finding is that the THDs for both 6-pulse and 12-pulse rectifiers in all four cases are quite flat or stable over load variation. This provides convenience when it comes to sizing the harmonic filters at the input. 29.9 6-pulse Balanced 35 29.8 6-pulse Case 1 29.7 6-pulse Case 2 6-pulse Case 3 3 29.6 29.5 29.4 29.3 25 2 15 6-pulse Balanced 6-pulse Case 1 6-pulse Case 2 6-pulse Case 3 12-pulse Balanced 12-pulse Case 1 12-pulse Case 2 12-pulse Case 3 29.2 2% 3% 4% 5% 6% 7% 8% 9% 1% 14.2 14 13.8 13.6 13.4 Figure 4. THD line current of 6-pulse rectifiers 12-pulse Balanced 13.2 12-pulse Case 1 13 12-pulse Case 2 12-pulse Case 3 12.8 2% 3% 4% 5% 6% 7% 8% 9% 1% Figure 5. THD line current of 12-pulse rectifier Figure 5 shows simulation results of the 12-pulse rectifier. It clearly shows that case 3 always yields the least amount of THD, while both the balanced 1 2% 3% 4% 5% 6% 7% 8% 9% 1% Figure 6. THD line current of both 6-pulse and 12-pulse bridge rectifiers 4. Conclusion Modeling and simulations of two commonly used bridge rectifiers were presented and discussed in this paper. The models make use of Orcad schematics whose lite version is available for free and downloadable from their company s (Cadence) website. The simulation was realized to be very flexible and economical to study performance of these rectifiers under numerous practical conditions which will otherwise be very expensive to put together. With simulations, engineers will be able to predict before hand the level of harmonics of input current that they will be dealing with under threephase system that they are accustomed to. To demonstrate the validity of the models, four case examples were simulated on the models to show 137

the impact of unbalanced system to their THD input line current. Results were presented and discussed in this paper. However, one crucial point is that although the models are based on mostly ideal components, users may easily modify the models to a more realistic one by simply adding parameters such as resistive losses or more comprehensive diode models. 5. References [1] Mohan, N., Undeland, T., and Robbins, W., Power Electronics: Converters, Application and Design, John Wiley and Sons Inc., 22. [2] Rashid, Muhammad H., Power Electronics Circuits, Devices, and Applications, New Jersey: Pearson Prentice Hall, 24. [3] Ask the Experts, The EC&M Magazine, December 1, 22. [4] Hink, Karl M., Harmonic Mitigation of 12-Pulse Drives with Unbalanced Input Line Voltages, MTE Corporation. 138