Conext CL-60 Inverter Active and Reactive Power Control and LVRT

Similar documents
Conext CL125 Inverter - Active and Reactive Power Control and LVRT/HVRT

Application Note on Power Point Tracking for Conext Core XC and XC-NA Series Inverters

Application Note: String sizing Conext CL Series

Application Note: Grid Settings by Utility Region for the Conext Core XC Series

Conext Core XC Series Inverter, 0G-XC-BB: Thermal Derating Application Note

Technical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US

Technical information SUNNY TRIPOWER CORE1-US

Technical information SUNNY BOY 3.0-US / 3.8-US / 5.0-US / 6.0-US / 7.0-US / 7.7-US

Conext Core XC ES and XC-NA ES Series Energy Storage Inverters

AccuSine SWP A. Operation. Active Harmonic Filter 02/

Conext Core XC and XC-NA Series Grid Tie Photovoltaic Inverter

Conext Core XC-NA ES Series Energy Storage Inverter

WARNING. Disconnect the inverter from all the external power sources before service!

Declaration of Conformity

WARNING. Disconnect the inverter from all the external power sources before service!

Conext Core XC-NA Series Grid Tie Photovoltaic Inverter and DC Recombiner

JBus/Modbus Communication Card

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

How do I Implement Hybrid Solutions for LV Dynamic Power Factor Correction

Conext CL Three Phase Grid Tie Inverters Conext CL NA Conext CL NA

Solectria Renewables Modbus Level 5 For models PVI KW

Target Mchunu and Themba Khoza Eskom Transmission Division, System Operator Grid Code Management

RenConnectLite. Version 3.0. Software User Guide.

IEEE sion/1547revision_index.html

Conext Automatic Generator Start

5 Summary test results and additional findings

Ameren Illinois Company d/b/a Ameren Illinois Smart Inverter Specifications

Option D1 Voltage/var/cos phi control Description of option Functional description

Revised IEEE 1547 Standard for Interconnecting Distributed Energy Resources with Electric Power Systems- National Grid Solar Program

PFC Lite. How it works OMNIVERTER. OMNIVERTER November 14, 2015 Slide 1

VOLTAGE REGULATOR R 449. Installation and maintenance. This manual must be sent to the end user R 449 X2 Z1 X1 Z2 E+ E- (12V - 10A)

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

BC145 SIGNAL ISOLATOR BOARD

Inverter Source Requirement Document of ISO New England (ISO-NE)

Indication of Dynamic Model Validation Process

Mounting Instructions / Manual MV1171

Installation and Operating Instructions. Power IT Power Factor Controller RVC

5 Summary LOW VOLTAGE RIDE THROUGH WITH HIGH CURRENT INJECTION. Motivation. Future Requirements. Test results for symmetrical failures

12-stage shift-and-store register LED driver

Technical Information SMA SOLID-Q 50 / PRO 60 Modbus Interface

SPECIFICATION, CONTROLS AND ACCESSORIES

Installation and Operating Instructions

Technical Information Short-Circuit Currents Information on short-circuit currents of SMA PV inverters

CHAPTER KEYPAD OPERATION AND QUICKSTART. In This Chapter... The GS2 Digital Keypad GS2 Quickstart...3 6

Conext CL-60 PV Inverter

Electrical Multimeter

Film Capacitors Power Factor Correction

AN Extended Range Proximity with SMSC RightTouch Capacitive Sensors

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Solectria Renewables Modbus Level 6 For models SGI 500XT

Optocoupler, Phototriac Output, High dv/dt, Low Input Current

SPECIFICATION, CONTROLS AND ACCESSORIES

ALPTEC POWER FACTOR CONTROLLER

1 Form A Solid State Relay

FFSP1665A/D. Silicon Carbide Schottky Diode 650 V, 16 A Features. FFSP1665A Silicon Carbide Schottky Diode. Description.

FFSP1065A/D. Silicon Carbide Schottky Diode 650 V, 10 A Features. FFSP1065A Silicon Carbide Schottky Diode. Description.

Power logic 12-bit shift register; open-drain outputs

R448 & R448 V50 A.V.R.

Wind Power Facility Technical Requirements CHANGE HISTORY

/ Maximum flexibility for the applications of tomorrow. / Open data communication. / Smart Grid Ready

NCP800. Lithium Battery Protection Circuit for One Cell Battery Packs

Low-power configurable multiple function gate

Operating Guide October 2006

HPVFP High Performance Full Function Vector Frequency Inverter

GX 340 SERIES (AUTOMATIC VOLTAGE REGULATOR)

AN NHS3xxx Temperature sensor calibration. Document information

/2008. Altistart 22. Soft start - soft stop unit. User manual 09/2009 BBV

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

PSBDAF20~200V1 Schottky Barrier diode

HEF4894B-Q stage shift-and-store register LED driver

Two elements in series configuration in a small SMD plastic package Low diode capacitance Low diode forward resistance AEC-Q101 qualified

/ The allrounder with maximum yield. / Smart Grid Ready. / WLAN interface

Is Now Part of To learn more about ON Semiconductor, please visit our website at

NUP2105LT3G. Dual Line CAN Bus Protector SOT 23 DUAL BIDIRECTIONAL VOLTAGE SUPPRESSOR 350 W PEAK POWER

Planar PIN diode in a SOD523 ultra small plastic SMD package.

1 Form A Solid-State Relay

SM05T1G Series, SZSM05T1G. Transient Voltage Suppressor Diode Array. SOT 23 Dual Common Anode Diodes for ESD Protection

Dual Photovoltaic MOSFET Driver Solid-State Relay

UM OM29263ADK Quick start guide antenna kit COMPANY PUBLIC. Document information

BC857XQA series. 45 V, 100 ma PNP general-purpose transistors

Data Sheet. RISH Master Record %THD

BAT-Series Grid Inverter. Battery Charger.

PAM2861. Description. Pin Assignments. Features. Applications. A Product Line of. Diodes Incorporated 1A LED DRIVER WITH INTERNAL SWITCH PAM2861

Digital Multifunction Instrument - Rish Master 3440

Power One Aurora String Inverter: energy absorption

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Aluminum Electrolytic Capacitors Power Ultra High Ripple Current Snap-In for Solar

Dual Photovoltaic MOSFET Driver Solid-State Relay

Optocoupler, Phototransistor Output

EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1. Three phase multifunction din rail energy meter

Optocoupler, Phototransistor Output, with Base Connection

Description. Symbol Parameter FCH041N65EF-F155 Unit V DSS Drain to Source Voltage 650 V

BAP Product profile. 2. Pinning information. 3. Ordering information. Silicon PIN diode. 1.1 General description. 1.2 Features and benefits

Dual Photovoltaic MOSFET Driver Solid-State Relay

Operation and Installation manual

RISH Master 3440i/3440iDL 0.2S

MBRD835LT4G. SWITCHMODE Power Rectifier. DPAK Surface Mount Package SCHOTTKY BARRIER RECTIFIER 8.0 AMPERES, 35 VOLTS

Possible Future Modifications to IEEE 1547

LP 600 Orion Electronic Dimmer for Magnetic Adapters in Poultry Houses User Manual

/ PC board replacement. / Smart Grid Ready TECHNICAL DATA FRONIUS SYMO (3.0-3-S, S, S, M, M, M)

Transcription:

Conext CL-60 Inverter Active and Reactive Power Control and LVRT http://solar.schneider-electric.com 976-0381-01-01/B March 2017 Application Note EXCLUSION FOR DOCUMENTATION UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER (A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION; (B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK; AND (C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION. Objective The goal of this application note is to describe the CL-60 Inverter s active/reactive power control and Low Voltage Ride Through (LVRT) methods, input parameters, and range. DANGER RISK OF FIRE, ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH This Application Note is in addition to, and incorporates by reference, the relevant product manuals for each product in the Conext CL-60 Inverter. Before reviewing this Application Note you must read the relevant product manuals. Unless specified, information on safety, specifications, installation, and operation is as shown in the primary documentation received with the product. Ensure you are familiar with that information before proceeding. Failure to follow these instructions will result in death or serious injury. CL-60 Active and Reactive Power Controls and LVRT Settings Standards: BDEW, VDE-AR-N-4105 Relay 1 & 2 Figure 1 Block diagram of CL-60 PV Inverter The control of inverter power can be implemented manually through the LCD display or remotely using the Conext CL Easy Config Tool. Copyright 2017 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Author: Keyur Javiya. For local customer technical support go to: http://solar.schneider-electric.com/tech-support.

Application Note Active Power Control The actual active power that the inverter delivers is a function of the available power in the PV array, but users can set the active power limit using these methods. Method 1 is useful when a set limit of active power is required for a specific application. See Method 1: Nominal power limit (P-W): [scale in %] on page 2. Method 2 is useful for applications such as zero export or to improve the overall system stability. See Method 2: Maximum Nominal Active power limit function of the frequency P(f): Derating on page 4. The active power output limit could be set using the Modbus communication signals from an external controller, the Conext CL Easy Config Tool, or through the LCD display interface on the inverter. The inverter responds to the command within 1-2 seconds, but because the communication method also includes some time delay, the overall response time for the event depends on the method used to deliver the command. Method 1: Nominal power limit (P-W): [scale in %] Figure 2 P-Q parameter settings menu tree Table 1 CL-60: Active Power parameter settings P-W Limit % 0% 110% (66000) 110% (66000) 1% The nominal power can be limited in % Rate Limit - - OFF - OFF/ON Set the active power change rate. When it is ON, the user can set the rate to rise or decline. Power rise, Gradient Power Decline, Gradient %/min 8%/min 100%/min 100%/min 1% When Rate limit is ON, this parameter can be set. %/min 8%/min 6000%/min 6000%/min 0.1% When Rate limit is ON, this parameter can be set. 2 of 13 976-0381-01-01 rev B

Active and Reactive Power Control and LVRT CL-60: Active power ramping When the inverter returns to the online state after a grid event, the active power may be ramped up gradually from 0% to 110% over a specified period using the Fault slow up parameter. For example, if the user sets the Fault slow up to ON with a slow-up rate of 10%/ min, then the power will rise at 10% per minute. When 100%/min slow-up rate is selected, the inverter will supply full active power from the available PV power into the grid. Table 2 CL-60: Active power ramping parameter settings Fault slow up - - ON - ON/OFF Set the state of the power rise rate change when a fault is cleared. When this is ON, the active power rise rate can be set by the user. Slow up rate %/min 8%/min 100%/min 100%/min 1% Set the active power rise rate after clearance of a fault event Save P-W settings - - OFF - OFF/ON Selection of the above settings to be saved or not CL-60: Time parameter change Table 3 CL-60: Time parameter settings Figure 3 Time parameter settings menu tree Standby Time Sec 20 Sec 20 Sec 255 Sec 1 Sec Time from inverter standby to start up Recover Time Sec 0 Sec 300 Sec 900 Sec 1 Sec Time from inverter fault clearing to standby 976-0381-01-01 rev B 3 of 13

Application Note Method 2: Maximum Nominal Active power limit function of the frequency P(f): Derating Figure 4 Derating parameter settings menu tree Frequency-based active power de-rating allows users to control the inverter s active power output with respect to change in frequency. This control method follows a defined slope based on three power and frequency values. The inverter LCD screen will display these values and allow users to change them for defining the curve. When defining the values, ensure that P1>P2>P3. Table 4 CL-60 Active Power P(f) Derating parameter settings Fre-Derating - - OFF - ON/OFF Set the Derating parameter to OFF/ON. When ON is selected, the inverter will operate in active power derating mode when the grid frequency exceeds the set value. F1 F2 F3 P1 P2 P3 Hz % - 0% - - 100% 100% 0.1 Hz 1% These three values of frequency and power define the curve for frequency derating. Users will decide the slope of the derating and enter the calculated values P1>P2>P3 4 of 13 976-0381-01-01 rev B

Active and Reactive Power Control and LVRT Reactive Power Control CL-60 Inverters are designed with spare capacity to generate on-demand reactive power while keeping the 60kW active power rating intact. The CL-60E and CL-60A inverters can generate 28.7 kvar and 27.6 kvar respectively without any nameplate (60 kw) de-rating. If the PV plant is designed to operate on unity PF only, these inverters can generate an additional 10% (CL-60E) and 6% (CL-60A) active power. So, if the PV system is to be designed for unity power factor, 66kW (IEC) or 63.4 kw (UL) rating should be used for total nameplate rating capacity of your PV plant. The Power Factor limit is -0.8 (Ind) to +0.8 (Cap). The Highest Reactive kvars from the inverter is +/-39.6 (CL-60E) and +/-38.0 (CL-60A). The inverter has a Q-Var switch that enables the option to generate Reactive Vars to the Off or On position. There are four methods to control Reactive VARs generated by CL-60 Inverters: Configurable fixed PF - cos-. See Method 1: Pf-Configurable Constant Power Factor, cos = cos on page 6 Configurable Constant Q - % Var Limit. See Method 2: Qt-Configurable Constant Reactive Power Q on page 8. Configurable PF (cos- ) as a function of Active power P. See Method 3: Q(P) - Configurable Power Factor Function of the Active Power, cos (P) on page 8. Configurable Reactive Power Q as a function of Grid voltage U. See Method 4: Q(U) - Configurable Reactive Power Function of the Grid Voltage, Q(U grid ) on page 9. NOTE: When one method is selected, the other methods are disabled. Figure 5 P-Q parameter settings menu tree Table 5 CL-60 Reactive Power parameter settings Save Q-Var Settings - - ON - Options: Pf/ Qt/Off/Q(P)/ Q(U) Select ON or OFF to apply the selected Q-Var control method and settings 976-0381-01-01 rev B 5 of 13

Application Note Table 5 CL-60 Reactive Power parameter settings Q-Var switch - - OFF - OFF/ON This option is to turn the selected reactive power regulation function ON or OFF. PF - -0.8 (ind) 1.0 +0.8 (cap) 0.1 Power Factor of Inverter output AC power Q-Var limits % -100% 0.0% +100% 1% Limits of Inverter output reactive power Method 1: Pf-Configurable Constant Power Factor, cos = cos The following graph for CL-60E and CL-60A represents the default structure implementation. It limits the selectable value for Q as a function of active power P. cos = ---------------------- P Q = S 2 + P 2 P 2 + Q 2 6 of 13 976-0381-01-01 rev B

Active and Reactive Power Control and LVRT P 66 kw 60 kw Q t S p t 52.8 kw Qind () t 2 2 cap () n () Qcap.max/Sn Qmax.limit CL-60E Pf=0.8 Pf=0.9 -Qind.max/Sn -39.6kVar -28.76kVAR 0 28.76kVar 39.6kVar P 63.4 kw 60 kw Q t S p t 2 2 cap () n () 50.7 kw Q t S p t 2 2 ind () n () Qmax.limit CL-60A Qcap.max/Sn Pf=0.8 Pf=0.9-27.6kVar -38kVar 0 27.6kVar 38.0kVar -Qind.max/Sn Q Figure 6 P-Q Curves for CL-60 976-0381-01-01 rev B 7 of 13

Application Note Table 6 PF parameters settings PF - -0.8 (ind) 1.0 +0.8 (cap) 0.1 Power Factor of inverter output AC power When p >= 80% P n 2 Q cap t S n p 2 2 = t Q ind t = S n p 2 t Method 2: Qt-Configurable Constant Reactive Power Q Table 7 Q-Var limits parameter settings The inverter delivers configured value (%) of constant reactive power Q when this method is selected. The corresponding value of Q of the selected % value would be based on Figure 6 on page 7. Q-Var limits % -100% 0.0% +100% 1% Limits of inverter output reactive power Method 3: Q(P) - Configurable Power Factor Function of the Active Power, cos (P) The following graph represents the default structure implementation. There is no requirement for Q 10%S n implement Q=0 for Q<5%S n. cos General Q(P) Curve cos Default Q(P) Curve Upper PF Cap P1 Capacitive 1 Lower Power Power Upper Power p (P/Sn) Upper PF Cap =1 Lower Power =50% P1 Power Upper Power =100% p (P/Sn) L2 Inductive L2 Inductive Lower PF Ind P2 Lower PF Ind P2 Figure 7 General and Default Q(P) curve for CL-60 8 of 13 976-0381-01-01 rev B

Active and Reactive Power Control and LVRT Table 8 Q(P) method parameter settings Upper PF Cap - 0.9 1 1 0.01 Power Factor of point P1 in the Q(P) mode curve Lower Power % 0 50% 50 1% Output power of point P1 in the Q(P) mode curve Lower PF Ind - 0.9 0.9 1 0.01 Power Factor of point P2 in the Q(P) mode curve Upper Power % 50 100% 100% 1% Output power of point P2 in the Q(P) mode curve Method 4: Q(U) - Configurable Reactive Power Function of the Grid Voltage, Q(U grid ) Table 9 Q(U) method parameter settings This method offers the change in ratio Q/Sn with respect to grid voltage. Lower Q/Sn Ind. % 0% 25% 50% 1% Inductive Q/Sn value of point P4 in the Q(U) mode curve Upper Q/Sn Cap. % 0% 25% 50% 1% Capacitive Q/Sn value of point P1 in the Q(U) mode curve Lower U limit % 80% 80% 90% 1% Grid voltage limit of point P1 in Q(u) mode curve (in %) Upper U limit % 110% 115% 115% 1% Grid voltage limit of point P4 in Q*u) mode curve (in %) U1 limit a % 95% 95% 100% 1% Grid voltage limit of point P2 in Q(u) mode curve (in %) U2 limit a % 100% 105% 105% 1% Grid voltage limit of point P3 in Q(u) mode curve (in %) Hysteresis % 0% 3% 5% 1% Hysteresis voltage width (in %) a.u1 limit + Hysteresis < U2 limit - Hysteresis 976-0381-01-01 rev B 9 of 13

Application Note Q/Sn Upper Q/Sn Cap P1 Hysteresis Lower Limit of U Overexcited Inverter operation P2 U1 Limit Hysteresis U2 Limit P3 Upper limit of U Underexcited Inverter operation Grid Voltage U Lower Q/Sn Ind P4 -Q/Sn Figure 8 Q(U) settings curve for CL-60 Convention: 1. Reactive Capacitive Power injected to grid: positive value set 2. Reactive Inductive Power injected to grid: negative value set 10 of 13 976-0381-01-01 rev B

Active and Reactive Power Control and LVRT Low Voltage Ride Through (LVRT) Figure 9 LVRT parameter settings menu tree During the Fault Ride Through, the inverter continues to operate under a defined duration of low grid voltage. Voltage ride through (VRT) is the capability of the inverter to maintain output current and remain online when the voltage in the grid is temporarily outside the nominal dead band. When the grid voltage drops below the preset low voltage (LV) threshold, the event is called low voltage ride through (LVRT). Figure 10 LVRT After the voltage dip, the reactive current reference would be changed according to the country specific requirements as shown in Figure 11. 976-0381-01-01 rev B 11 of 13

Application Note U U n 110% 100% 90% A(3000mS, 20% Un) Inverter Online Inverter Disconnected 30% 20% B(1000mS, 20% Un) t0 (1000ms) (1.5s)(1700ms) (150ms) (625ms) (3000mS) time BDEW Default Figure 11 Low voltage ride through curve for CL-60 Table 10 Low voltage ride through parameter settings LVRT - - OFF - OFF/ON This option sets the LVRT capability to OFF or ON state. When LVRT is ON, the inverter will remain grid connected during fault conditions and provide reactive power. LVRT normal Volt V1 LVRT tolera Volt V2 V 0 85% 100 1% User set parameter V 0 15% 100 1% User set parameter LVRT T1 S 10 ms 620 10 s 10 ms User set parameter 12 of 13 976-0381-01-01 rev B

Active and Reactive Power Control and LVRT Table 10 Low voltage ride through parameter settings LVRT T2 S 10 ms 3s 10s 10ms User set parameter LVRT kf - 0 2 4 1 User set parameter 976-0381-01-01 rev B 13 of 13