Including Surge Arresters in the Lightning Performance Analysis of 132kV Transmission Line

Similar documents
Analysis of lightning performance of 132KV transmission line by application of surge arresters

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

Investigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas Insulated Substations

Lightning performance of a HV/MV substation

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Study of Tower Grounding Resistance Effected Back Flashover to 500 kv Transmission Line in Thailand by using ATP/EMTP

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines

Electric Stresses on Surge Arrester Insulation under Standard and

Effective Elimination Factors to the Generated Lightning Flashover in High Voltage Transmission Network

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

Substation Insulation Coordination Study

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Utility System Lightning Protection

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

Lightning Overvoltage Performance of 110 kv Air-Insulated Substation

Transmission of Electrical Energy

The Effect of High Frequency Model of Tower- Footing Grounding Systems on the Back Flashover Rate of Transmission lines

Modeling insulation in high-voltage substations

HIGH VOLTAGE Insulation Coordination

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Lightning overvoltage and protection of power substations

ABSTRACTS of SESSION 6

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

A SIMPLIFIED LIGHTNING MODEL FOR METAL OXIDE SURGE ARRESTER. K. P. Mardira and T. K. Saha s: and

Comparison between Different InstallationLocations of Surge Arresters at Transmission Line Using EMTP-RV

Estimating BFOR on HV Transmission Lines Using EMTP and Curve of Limiting Parameters

Accuracy of Lightning Surge Analysis of Tower Surge Response

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

University of Zagreb Faculty of Electrical Engineering and Computing

Lightning Current Observation on UHVAC Transmission Lines by Improved Magnetic Steel Rod Method

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

INSTALLATION OF LSA ON A 400 KV DOUBLE-CIRCUIT LINE IN RUSSIA

Analysis of Arrester Energy for 132kV Overhead Transmission Line due to Back Flashover and Shielding Failure

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

X International Symposium on Lightning Protection

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

Journal of Applied Research and Technology 15 (2017)

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

WORLD MEETING ON LIGHTNING Lightning Performance Research on Mexican High Voltage Transmission Lines

Sensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves

Analysis of current distribution among long-flashover arresters for 10 kv overhead line protection against direct lightning strikes

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

The Many Uses of Transmission Line Arresters

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

High voltage engineering

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

New Modeling of Metal Oxide Surge Arresters

Statistical Lightning Simulations for a HV "Mixed" Overhead-Cable Line: Preliminary Studies

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission Lines

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

Tab 8 Surge Arresters

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

The line-lightning performance and mitigation studies of shielded steelstructure

Mitigation of Back-Flashovers for 110-kV Lines at Multi-Circuit Overhead Line Towers

Lightning transient analysis in wind turbine blades

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

ABSTRACT 1 INTRODUCTION

Metal-Oxide Surge Arresters Integrated in High-Voltage AIS Disconnectors An Economical Solution for Overvoltage Protection in Substations

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

Introduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Roll No. :... Invigilator s Signature :.. CS/B.TECH(EE)/SEM-5/EE-502/ POWER SYSTEM-I. Time Allotted : 3 Hours Full Marks : 70

Estimating the Lightning Performance of a Multi- Circuit Transmission Tower

A Study of Lightning Surge on Underground Cables in a Cable Connection Station

Lightning Performance of Transmission Lines with Tall Sections

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

ELC 131 CIRCUIT ANALYSIS I

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS

Back-flashover Investigation of HV Transmission Lines Using Transient Modeling of the Grounding Systems

Electric Power Systems Research

Tab 2 Voltage Stresses Switching Transients

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

Mitigation Methods to Improve the Lightning Performance of Hybrid Transmission Line

Insulation Coordination Study of 275kV AIS Substation in Malaysia

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Journal of Asian Scientific Research SUBSTATION PROTECTION AND THE CLIMATIC ENVIRONMENT OF NIGER DELTA. John Tarilanyo Afa

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

Investigation on the Performance of Different Lightning Protection System Designs

The Lightning Event. White Paper

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

7P Series - Surge Protection Device (SPD) Features 7P P P

B2-301 IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN

Transcription:

ncluding Surge Arresters in the Lightning Performance Analysis of 32kV Transmission Line Saeed Mohajeryami, Milad Doostan University of North Carolina at Charlotte Department of Electrical and Computer Engineering Charlotte, NC {smohajer,mdoostan}@uncc.com Abstract- Line arresters are considered as an effective way to improve the lightning performance of transmission lines, especially in parts of line that suffer from high soil resistivity and lightning ground flash density. This paper presents results of the application of line surge arresters on the 32KV double circuit transmission line in EMTP-V and all the practical scenarios for installation of surge arresters. The study has shown that a significant level of improvement can be reached by installing arresters at all or only some of the line phases. t can increase the strength of the line to withstand lightning currents up to -292kA. the probability of having this lightning current, is practically zero. ndex Terms Surge Arrester, Backflashover, Lightning Overvoltage, Volt-time model, EMTP-V. NTODUCTON Power equipment failure can incur huge financial losses to the transmission companies and it has necessitated the need for paying attention to these widely exposed lines which are subject to vast variety of faults. One of the most frequent issues occurring at the transmission lines are outages caused by the lightning strikes []. These outages can be decreased by the proper insulation design and the design of varied devices hinges on lightning overvoltage in the network [2]. To decrease the outage rate due to the lightning, many methods have been proposed such as tower footing resistance reduction, increase of line insulation level, installation of additional ground and guy wires, addition of under-built ground wires, etc. limited effect or being expensive or difficult to use, are some of the reasons that make some of them impractical [3]. Thanks to the development of polymer-housed metal-oxide surge arresters, it became practical to use arresters to control line lightning performance, with reasonable price and without tower structure reinforcement [4]. Authors in [5] have investigated the effectiveness of external and internal surge arresters on 500kV DC gas insulated lines. n [6] also it has been shown that the surge arresters are effective in controlling the switching overvoltages. The authors in [7] have investigated the surge arrester application for 750kV transmission lines and have obtained the right size. To assess the effectiveness of surge arresters, a probabilistic approach has been adopted by [8] to estimate the failure risk of such surge arresters. This paper presents results of the application of transmission line surge arresters on the 32kV double circuit transmission line with using accurate models of line components in EMTP-V environment. At first, a brief description of test line has been presented and then, models used for modeling lightning source, tower and transmission line, tower footing resistance, insulator gap and surge arrester in EMTP-V have been introduced and their parameters have been calculated and finally simulation results and their characterization and conclusion have been presented.. BEF DESCPTON OF TEST LNE Arvandkenar-Abadan 32kV double circuit is a transmission line located in ran which has been used as a case study. The complete transmission line information is tabulated in table. Fig. shows tower structure, phase and shield wire configuration.. MODELNG A. Lightning current source model n order to calculate lightning outage rate, the probability of exceeding stroke of current,, is needed. This probability distribution function can approximately be computed from (2) [9].

TABLE TANSMSSON LNE DATA General Data Shield Wire Data Voltage Level 32 kv Core Type Hawk Line Length 53 km Number per tower Location Mahshahr, ran Diameter 8.04 mm Number of Thunderstorms 5.2 day in year Cross Section Area 39.46mm2 DC esistance 2.9 Ω/Km Conductor Data Tower Data Type Hawk/AL,26/3.87,477MCM Type HS2-0 Number of Bundles 2 nsulator Gap Length 350mm Bundle Spacing 45.7 cm Footing esistance 20 ohm maximum Diameter 2.8 mm Soil esistivity 00-50 Ω.meter Total Area 28.03 mm2 Lightning Discharge Path DC esistance 0.99 Ω/Km mpedance 400Ω GM 0.8245cm uling Span 350m P = + ( ) 3 2.6 (2) n this paper, double exponential formula which is provided in (3) has been employed to model the current source [0]. t t T T2 ( ) =.04 ( ) (3) m it e e T =.36543 T (4) Ts T = (5) 2 2.282835 Where TT ss is rise time and TT is tail time. ndeed, as the positive polarity lightning stroke is nearly 5% of all strokes, it is neglected in this work. Moreover, the impedance of the lightning discharge channel is assumed to be 400Ω. B. Tower and Transmission line model Double circuit transmission line is modeled with frequency-dependent model in EMTP-V. Phase coupling is considered in this model. Multistory model [] is used for tower model. t is multistoried as shown in Fig. 2. Tower surge impedance is calculated from CGE recommended equation (6) and then because of similar structure of HS2-0 vertical tower and [], the same ratio has been chosen for dividing surge impedance between upper and lower halves. Z surge Where = h 60ln[cot(0.5 tan ( ))] (6) rh + rh+ rh h 2 2 3 = h= h+ h2, (7) Height and radius has been shown in Fig. 3. Calculated tower model parameters and their formulas have been listed in Table. Fig. 2 Multistory tower model Fig. 3 Tower schematic Fig. HS2-0 type tower structure C. Tower footing resistance model Several methods have been proposed to calculate the tower footing resistance while there are fast transient surges which can ionize the soil and change the resistance. However, one of the most simple and practical approaches which takes the surges considerations into account is provided by CGE [9].

TABLE. MULTSTOY TOWE MODEL PAAMETES ZZ ssssssssss = 79.2 ZZ tt = ZZ tt2 = ZZ tt3 =.9ZZ = 23.2 ZZ tt4 = 0.8ZZ = 45.5 vv tt = vv tt2 = vv tt3 = vv tt4 = vv = 300 [m/μμμμ] γγ = 0.8944 ττ = 2HH vv=0.28 rr = (2 ZZ tt ln γγ)/(h + h 2 + h 3 ) = 2.5 [Ω/m] rr 2 = (2 ZZ tt4 ln γγ)/h 4 =.25 [Ω/m] = rr h = 4 2 = rr h 2 = 6.8 3 = rr h 3 = 6.8 4 = rr 2 h 4 = 32.4 LL = ττ = 3.92 LL 2 = 2 ττ = 4.07 LL 3 = 3 ττ = 4.07 LL 4 = 4 ττ = 9. According to this method the tower footing resistance could be calculated from (8). 0 F = (8) + g Where: 0 : Tower footing resistance at low current and low frequency (ohm), gg : Limiting current initiating soil ionization (ka) which can be calculated by (9): E0 ρ g = (9) 2 2π 0 Where ρρ is soil resistivity (ohm-meter), and EE 0 is soil ionization gradient (about 400 kv/m). D. Backflashover model n volt-time model [9], it is assumed that Backflashover occurs when tower voltage is higher than lightning impulse withstand voltage or Basic insulation level (BL) of the insulator strings. The lightning impulse withstand voltage of the insulator string, is not a unique number. The insulator string may withstand a high magnitude impulse voltage with short duration while it fails to withstand a lower magnitude impulse voltage with longer duration. A simplified expression of withstand voltage capability for an insulator string can be calculated as in (0): VV ff0 = KK + KK 2 tt 0.75 (0) Where V fo = flashover voltage (kv), K = 400*L K 2 = 70*L L = insulator length (m) t = elapsed time after lightning stroke, μs. Fig. 4 shows the V-t relationship of a sample insulator. Fig. 4 Volt-time model E. surge arrester model Metal Oxide surge arresters protect power equipment insulation from system overvoltage. These arresters have high resistance at the normal system operation but when facing system overvoltage, they will show low resistance. There are several models proposed in literature to describe this nonlinear behavior but in this study EEE frequency dependent model [3] has been chosen because of its enough accuracy for lightning studies. Fig. 5 EEE frequency dependent model The inductance L 0 in the model represents the inductance associated with magnetic fields near the arrester. The resistor 0 is used to stabilize the numerical integration in the software. The capacitance C represents the terminal-to-terminal capacitance of the arrester. The inductance L and the resistance make a filter between the two nonlinear resistances. For slow-front surges, this -L filter has very little impedance and the two non-linear sections of the model are in parallel. For fast-front surges the impedance of the -L filter becomes more significant. This results in more current in the non-linear section named A 0 than in the section named A. L = 5 µ H () = 65 Ω (2)

Fig. 7 Simulated line schematic Fig. 8 (upper left) insulator induced voltage without arrester, Fig. 9 (upper middle) insulator induced voltage with arrester, Fig. 0 (upper right) installation scenarios, Fig. (middle left) Scenarios with one arrester, Fig. 2 (middle middle) Scenarios with two arresters, Fig. 3 (middle right) Scenarios with three arresters, Fig. 4 (lower left) Scenarios with four arresters, Fig. 5 (lower middle) Scenarios with five arresters, Fig. 6 (lower right) Lightning current flashover in all scenarios L0 = 0.2 µ H (3) 0 = 00 Ω (4) n C = 00 pf (5) d Where d is the estimated height of the arrester in meters (from catalog data) and n is the number of parallel columns of metal oxide in the arrester The non-linear V- characteristics A 0 and A can be estimated from per unitized curves given in Figure 6. Fig. 6 V- elationships for Non-Linear esistor Part of Model

For A 0 in Fig. 6, DDDDDDDDhaaaaaaaa, KKKK = [ iiii pp. uu. ffffff AA 0 (ii)] [VV 0.6] (6) Likewise for A, the DDDDDDDDhaaaaaaaa, KKKK = [ iiii pp. uu. ffffff AA (ii)] [VV 0.6] (7) Where V 0 is discharge voltage for 0kA current with 8/20 µs waveshape per kv. Table shows line arrester specification used for this simulation. TABLE SEMENS 3EL5 08-0LK23 SPECFCATON [2] Height(d).53 m Parallel column(n) Maximum value of esidual voltage at discharge current 8/20 µs and 0 ka(v 0) Maximum value of esidual voltage at discharge current 30/60 µs and 2kA Maximum Continuous Operation Voltage V. SMULATON AND ESULTS 308kV 259kV 86 kv Simulation has been done with accurate modeling of components in EMTP-V software. Fig. 7 shows the schematic of test line. Fig. 8 shows the induced voltage on insulator without surge arrester for standard lightning current of -00 ka that as it can be observed, flashover occurs across insulator. Fig. 9 shows the same situation for insulator but with surge arrester installed at the upper phase. For installation of surge arresters a comprehensive plan must be studied to consider all scenarios. Fig. 0 illustrates all the different practical scenarios for installation of insulators. Scenarios with the same number of surge arrester per tower have been compared in Figs. -5. Finally, in Fig. 6 lightning current causing flashover in all scenarios, have been shown graphically. V. CONCLUSON According to the simulation results, the standard lightning current of -77kA can cause flashover across insulators of the line without surge arrester. This current results 3.7 line outage per 00km per year, but with installing surge arrester, this line can withstand lightning currents up to -292kA. The probability of having this lightning current, is practically zero. As shown in Fig. 6, scenarios, 4 and 0 are the most efficient among other installation scenarios; as it is shown in Figs. -6, inefficient strategies for installing surge arresters can waste a lot of money even with more arresters per tower. The study has shown that, as expected, a significant level of improvement can be reached by installing arresters at all or only some of the line phases. The improvement of lightning performance can be very significant when arresters are installed at two phases, but even with the installation of a single arrester per tower at the upper phase, a significant reduction of the total flashover rate can be achieved. EFEENCES [] S.T. Mobarakei, T. Sami, B. Porkar, "Back Flashover phenomenon analysis in power transmission substation for insulation coordination," th nternational Conference on Environment and Electrical Engineering, pp.70-74, May 202 [2] M. Babaei, M. Babaei, M. Niasati, "Parametric analysis of overvoltages caused by back-flashover in Siah-bishe 400kV GS substation," 3rd nternational Conference on Electric Power and Energy Conversion Systems, pp.-6, Oct. 203 [3] K. Munukutla et al, A Practical Evaluation of Surge Arrester Placement for Transmission Line Lightning Protection, EEE Trans. on Power Delivery, Vol. 25, No. 3, July 200 [4] J.A. Martinez, F. Castro-Aranda, Modeling Overhead Transmission Lines for Line Arrester Studies, EEE Power Engineering Society General Meeting, pp.25-30 June 2004 [5] F. Goll,. Witzmann, "Lightning Protection of 500-kV DC Gas- nsulated Lines (GL) With ntegrated Surge Arresters," EEE Trans. on Power Delivery, vol.30, no.3, pp.602-60, June 205 [6] P. Bunov, et al "Transmission line arresters application for control of switching overvoltages on 500-kV transmission line," EEE T&D Conference and Exposition, pp.-5, April 204 [7] J. Wang, et al "The research and design of parameters for 750kV transmission line metal-oxide surge arresters with series gap," nternational Conference on High Voltage Engineering and Application (CHVE), pp.-4, Sept. 204 [8]. Shariatinasab, F. Ajri, H. Daman-Khorshid, "Probabilistic evaluation of failure risk of transmission line surge arresters caused by lightning flash," ET Generation, Transmission & Distribution, vol.8, no.2, pp.93-202, February 204 [9] CGE WG 33-0: Guide to Procedures for Estimating the Lightning Performance of Transmission Lines, Technical Brochure, October 99. [0] B.Vahidi, M.Ghorat, E.Goudarzi, Overvoltage calculation on Bam substation by monte carlo method with accurate substation components modeling, EEE conference on power technology, pp.807-8, July 2007 [] M. shii, T. Kawamura, T. Kouno, E. Ohsaki, K. Muromi, T.Higuchi, Multistory Transmission Tower Model for Lightning surge Analysis, EEE Trans. on Power Delivery, Vol. 6, No. 3, pp.327-335, July 99 [2] SEMENS surge arrester 3EL, Germany, 200. [3] EEEWorking Group 3.4., Modeling of metal oxide surge arrester, EEE Trans. on Power Del., vol. 7, no., pp. 302 309, Jan. 992.