Stray Voltage and Swimming Pools

Similar documents
EPRI Contact Voltage R&D Program Update Doug Dorr EPRI

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

Boat Dock Exposure Voltage Mitigation

CONTINUING EDUC ATION

Standardized Measurements for Elevated NEV and Energized Object Concerns Doug Dorr, Charles Perry, Mark McGranaghan Arindam Maitra, Wes Sunderman

IEEE WORKING GROUP ON VOLTAGES AT PUBLICLY AND PRIVATELY ACCESSIBLE LOCATIONS. Web Cast May 17, 2007

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

Industrial and Commercial Power Systems Topic 7 EARTHING

American Electrical Institute

Grounding for Power Quality

High Voltage Pylon Earth Measurements

Article 250 Grounding & Bonding

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

Wisconsin Contractors Institute Continuing Education

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy

The Confusion Surrounding Stray Voltage

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor

SECTION 5 TRANSFORMERS

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

HV Substation Earthing Design for Mines

MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

Touch and Step Voltage Measurements on Field Installed Ground Grid Overlaid with Gravel and Asphalt Beds

kv AC substation

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES

The Variable Threshold Neutral Isolator (VTNI)

Attendee Announcements

Single Line Diagram of Substations

Customer Requirements RF Antenna Installations

UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS

Education & Training

FAQ ON EARTHING STANDARDS 16/08/2018

Contact Voltage Detection


OAH No , MPUC Dkt No. IP6701/WS STATE OF MINNESOTA OFFICE OF ADMINISTRATIVE HEARINGS

3.7 Grounding Design for EAST Superconducting Tokamak

6B.6 Substation Grounding

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT OFFICE

Earth Grounding Resistance

Unit 2. Single Line Diagram of Substations

Device Interconnection

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

Standard Recommended Practice. Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems

ELECTRICAL SHOCK HAZARD DUE TO STRAY CURRENT THE SHOCKING SHOWER

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

25kV A.C. Electrified Lines - Traction Bonding

Reference Number PDS 07 (RIC Standard: EP SP)

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Earthing of Electrical Devices and Safety

Power System Neutral/Ground Voltages Causes, Safety Concerns and Mitigation

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.

ENGINEERING REPORT PHASES I & II MITIGATOR PERFORMANCE TESTS

AC INTERFERENCE OF TRANSMISSION LINES ON RAILWAYS: INFLUENCE OF TRACK-CONNECTED EQUIPMENT I. ABSTRACT

Quality Control Checklist - Design Drawings

Smart Ground Test Report. Springfield Energy - Springfield Power Station Grounding System Evaluation

Licensed Electricians Practical Assessment (LEP)

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments

Grounding and Bonding

IEEE WORKING GROUP ON VOLTAGES AT PUBLICLY AND PRIVATELY ACCESSIBLE LOCATIONS. Web Cast November 30, 2006

AC Voltage- Pipeline Safety and Corrosion MEA 2015

Grounding Recommendations for On Site Power Systems

National Radio Astronomy Observatory Socorro, NM EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable. T. Baldwin June 05, 2002

LONGITUDINAL INDUCTION VOLTAGE MEASUREMENT ON COMMUNICATION CABLES RUNNING PARALLEL TO OVERHEAD LINES

6. Internal lightning protection

Page Electric Utility Service Specifications

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

Licensed Electricians Practical Assessment (LEP)

Minimizing Lightning and Static Discharge in Broadcasting

EPG. by Chris C. Kleronomos

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

CONTINUOUS COUNTERPOISE ON POLES

A New Technology. for Measuring Overhead Line and Cable Impedance Values and the Ground Impedance of Large Substations. Feature

Examples of Design for Cathodic Protection Systems

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

Grounding for EMC at the European XFEL

LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE

WinIGS. Windows Based Integrated Grounding System Design Program. Training Guide. Last Revision: June 2017

Technique for Accurate Voltage Measurement of Energized Street Level Objects

ECE 528 Understanding Power Quality

IEEE Southern Alberta Section, Industrial Applications and Power & Energy Chapter Technical Program. Venue: Operator. Speaker Travel: Stantec

FTTH ENGINEERING AND INSTALLATION INTRODUCTION

Grounding Complications

EPR Safety Mat Modelling & Field Testing Summary Report

GROUND TESTERS For all of your Ground Testing needs...

Model CB Embedded References

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

IP Transport Communications for Power Stations and Other High-Reliability Locations- Challenges and Protection

Substation: From the Outside Looking In.

Status Date Prepared Reviewed Endorsed Approved

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Doing It Right. Phasor Labs. March voice fax

There are a wide variety of ground resistance testers available on the

Transcription:

Stray Voltage and Swimming Pools Marty L. Page, P.E. Southern Company malpage@southernco.com October 19 th 2009 2009 Jodie Lane National Conference for Stray Voltage Detection, Mitigation & Prevention

Southern Company SouthernLINC Wireless Southern Power Southern Nuclear Southern Telecom One of the largest electricity generators in the nation with more than 42,000 MW of capacity 4.3 million Customers 120,000 square miles in 4-state region 3,400 substations Grid of Transmission and Distribution lines that would circle the earth

Presentation Roadmap IEEE Working Group effort regarding exposure voltages What is stray voltage (in the classical sense) The National Electric Code and pool safety How can a pool have stray voltage EPRI 2009 Pool Tests Vision for the results of the testing

IEEE Working Group IEEE Working Group on Voltages at Publicly and Privately Accessible Locations IEEE WG is writing a trial-use guide for assessing voltages at publicly and privaly accessible locations. Topics include: Definitions, Causes, Testing Protocols, Measurement Equipment, Mitigation Options, Levels of Concern One desired outcome is clear distinction of stray voltage

Proposed IEEE Working Group Definitions: Stray Voltage: A voltage resulting from the normal delivery and/or use of electricity (usually smaller than 10 volts) that may be present between two conductive surfaces that can be simultaneously contacted by members of the general public and/or their animals....stray voltage is not related to power system faults, and is generally not considered hazardous. Contact Voltage: A voltage resulting from abnormal power system conditions that may be present between two conductive surfaces

Definitions in this presentation: Stray Voltage is a small open-circuit voltage (usually less than 10 volts) measured between any two points that can be simultaneously contacted by a human or an animal. Neutral to earth voltage (NEV) is the voltage measured between any point on a neutral or its extension and an isolated reference electrode placed in earth with zero or nearly zero potential (remote earth). Grounding Electrode Resistance (Rg) is the resistance of a grounding electrode system with respect to remote earth. Grounding Electrode Current (Ig) is the total current flowing in the surrounding earth via the grounding electrode system.

NEV = Ig x Rg NEV = 0.05A x 25 ohms = 1.25V Remote Earth Ground Rod

Substation Transformer PriØ N Multi-grounded neutral distribution line T T T N T T T PriØ PriØ SØA N N SØB T = Single Phase Service Transformer Ø N Ø Residential Customer Meter PriØ = Primary Phase Conductor SØA,B = Secondary Conductor N = Neutral

Just balance the loads and cancel out the neutral current right? The distribution neutral current will usually be a combination of 60hz and triplen harmonics. Triplen order harmonics do not cancel.

NEC and Swimming Pools 2008: Requirement to bond the pool water included 2005: Added Equipotential Bonding Grid (680.26C); also a TIA Tentative Interim Amendment allowing #8 copper encircling entire pool contour 1999: The revised wording of the 1999 Code makes it clear that the No. 8 conductor is only for the elimination of the voltage gradient in the pool area and is not required to provide a path for fault currents 1984: stressed eliminating voltage gradients as a FPN: employed to eliminate voltage gradients in the pool area 1975: Common bonding grid defined as either 1)structural reinforcing steel 2)wall of welded metal pool 3)#8 solid copper 1962: The first Article on Swimming Pools (requires bonding)

2005 NEC Section 680.26 Equipotential Bonding (A) Performance. The purpose of equipotential bonding is to eliminate voltage gradients in the pool area. (B) Bonded Parts. The parts listed below shall be bonded together: (1) Metallic Structural Components- all metal parts of the pool structure including reinforcing steel. (2) Underwater Lighting- all no-niche luminaires unless of a listed low voltage lighting system with nonmetallic forming shells. (3) Metal Fittings- all metal fittings within or attached to the pool structure..

Typical NEC 680.26 Pool Bonding

How can a swimming pool have stray V? There is an extension of the system neutral in the swimming pool environment. Ladder Electric Panel G N Light Pool Water Handrail Remote Earth? Pump

Swimming Pool with a significant voltage gradient only on one side of pool. Meter Pool Panel 0.3 V 2.8 V 3.6V 3.3 V Voltage Measurements Aug. 24, 2004

EPRI Project Evaluation of Bonding and Grounding Effects for Residential Swimming Pools and Spas The purpose of this research project is to replicate a wet area that allows for controlled measurements with variable NEV sources, variable grounding and bonding configurations, and controlled fault setups. Successful project results will benefit the public bringing a more comprehensive understanding of the suitability of different grounding configurations and supplemental mitigation techniques.

EPRI Test Facility in Lenox, MA. 23,000 V Overhead Line ~800 feet 23-kV Feed from Utility 23-kV Substation 23-kV to 4160 V stepdown bank Stray Voltage Test Structure 4160 V Overhead Line ~1200 feet

20 0 Simulated Simulated Residences Residences and and Variable Variable NEV NEV Source Source rom from Overhead Overhead and and Underground Underground Distribution Distribution Previous Stray Voltage Testing Structure

New pool structure built beside existing stray voltage testing structure.

4 types of Decks to model various field conditions = Underwater Light = Metal Handrail = Ladder Rebar deck section Fiberglass deck section Water Pump and Sub Panel Wet Area will have #8 copper conductor surrounding shell Tile deck section Diagram courtesy EPRI D. Dorr Three solid #8 bare copper ground rings are connectable. (18in from water at 6in depth, 7ft from water at 6in depth, 7ft from water at 36in depth)

Red Lines indicate location of measurement rods. Yellow Lines indicate 12inch spacing between deck sections to be backfilled with gravel. Purple ring is #8 bare copper to be laid on surface of gravel below concrete. Conductive Concrete No Rebar Concrete w/rebar Concrete w/fiberglass Gravel or Paver Option

Pump House Equipment

Nearby distribution line to be faulted during testing

NEV Mitigation Issues Include: Effect of inner ring vs outer ring Effect of ring combinations Effect of vertical vs angled ground rods Effect of multiple ground rods and spacing Effect of horseshoe vs full ring Effect of depth of ground ring

Preliminary results indicating outer ring reduces voltage around pool area by 50% or more.

Swimming Pool Test Structure

Fault Testing to force current thru pool 1.) Red Line indicates location of trench for counterpoise 2.) Specifications: 1 ft deep, 1 ft wide, 32 ft long 3.) In the center and at each end, there will be one 8ft vertically driven ground rod clamped to the counterpoise Xf Ground Rods 16 ft apart Pool Counterpoise 32 ft long House Overhead Line

Power Accidents System are unpredictable Faults are unpredictable

Vision applied to future pool complaints Develop Appropriate Investigation Procedure and Solutions Identify whether a break or lack of proper Equipotential Grid exists Present the findings to the pool owner with the pro s and con s of available solutions Ensure that the safety of the public drives the solution and that risks are adequately identified

Questions? Breaks in swimming pool equipotential grids may cause voltages to be felt what should the utility do? 2009 Jodie Lane National Conference for Stray Voltage Detection, Mitigation & Prevention