Type CAEM 21 Battery Earth Fault Relay

Similar documents
Type VAEM 22 Negative Potential Biasing Relay

Type VDG 13 Undervoltage Relay

CDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Type MCAG 14, 34 T&D. High Stability Circulating Current Relay

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

Instantaneous Overcurrent Relay

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy

POWER SYSTEM II LAB MANUAL

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

3 Pole high impedance differential relay 7VH83

Current and voltage measuring relays RXIK 1, RXEEB 1 and RXIB 24

GE Power Management. Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C

Apprentice Electrical Technician Test (ETT) Preparation Guide

DEIF A/S. Insulation monitor. Type SIM-Q

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

Reyrolle Protection Devices. 7PG18 - TR-A High speed tripping Relay. Energy Management.

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

DIAC Type 66K. DIGITAL OVERCURRENT RELAY Instruction Manual. GE Power Management

Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping R. Table 1:

7PG21 Solkor Rf Feeder Protection Energy Management

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

05/09/2014

DEIF A/S. Insulation monitor. Type SIM-Q/SIM-Q LF

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

[ECEN 1400] Introduction to Digital and Analog Electronics R. McLeod. HW #4: Power Supply

Reyrolle Protection Devices. 7PG11-18 Alpha Electromechanical Relays. Siemens. Answers for energy.

DIGITAL EARTH FAULT RELAY

INSPECTION 1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

VP Series Relay 1. SUMMARY OF TYPES. C&S Controls Limited 22 Upland Road Bexleyheath KENT. DA7 4NR

Mors Smitt Industrial Technology. High performance plug-in relays

Earth Fault Relay EFSPL-1A/5A

Status Date Prepared Reviewed Endorsed Approved

ESO 210 Introduction to Electrical Engineering

STATIC EARTH FAULT RELAY

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work

IGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards

MBCI (Translay S) Technical Manual. Differential Feeder and Transformer Feeder Protection. Publication Reference: GRID

Protective Relays Digitrip 3000

Exercise 10. Transformers EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to transformers

CIRCUITS THAT ARE AVAILABLE ON LODAR RECEIVERS Features listed below are available on 92 Series and 93 Series

SPAD 346 C Stabilized differential relay

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

CX-A6 Amplifier Installation & User Guide V9.0

Practical 2.1 BASIC ELECTRICAL MEASUREMENTS AND DATA PROCESSING

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Construction Electrician/Industrial Electrician/Power Electrician Common Core Level 2

SPAE 010, 011 High Impedance Protection Relay

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Stabilized Differential Relay SPAD 346. Product Guide

3.0 CHARACTERISTICS. Type CKO Overcurrent Relay. switch, which allows the operation indicator target to drop.

KENYA ELECTRICITY GENERATING COMPANY LTD

33609/J Limiter/Compressor

A 100-Watt Transmitter Using a Pair of VT1625s

Earth Fault Indicator EFI-BLZ-50 User Manual

DIGITAL EARTH FAULT RELAY

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-Voltage Capacitive Compensation Unit for Transformer and Shunt Reactor Testing, Type HVCC

Lecture (04) Uncontrolled Rectifier Circuits

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

+ 24V 3.3K - 1.5M. figure 01

Meters. Ampere Meter. Volt Meter. Watt Meter. Var. Meter. Power Factor Meter. Frequency Meter. Demand Meter. Meter Relay.

Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16

AS431. General Application Information. Application Note1

which is used to shift the phase angle between the two sets of coils to produce torque.

Installation/operation instructions. Insulation monitor type SIM-Q/SIM-Q LF D (UK) Measuring range 1...0Mohm or 10...

Capacitor Switching Contactors

Transformer Protection

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

THE PUBLIC ADDRESS AMPLIFIER SYSTEM WITH FLEXIBILITY BUILT-IN

which is used to shift the phase angle between the two sets of coils to produce torque.

1M122A Transformer Parallel Control System

Ordering Information. Latching Relay MMK. Available Models. Models Conforming to Auxiliary Power Relay Specifications

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY

PERMA Series Revision 2 Amplifiers

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

VOLUME - 4 (GENERAL TECHNICAL SPECIFICATIONS)

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

www. ElectricalPartManuals. com Basler Electric P. 0. BOX 269 HIGHLAND, ILLINOIS 62249, U.S.A. PHONE FAX

MEDIUM-VOLTAGE MEASURING VOLTAGE TRANSFORMERS USER MANUAL

MILFORD INSTRUMENTS Limited

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

MEDIUM VOLTAGE PRODUCT. TJP 5.x Indoor voltage transformers

REPAIRING THE RM KL400 LINEAR AMPLIFIER.

Earth fault protection for isolated neutral systems with frequency converters

Magnetic Switches. General Information on BERNSTEIN Magnetic Switches. Electromechanical and electronic variants

PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

Circuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You

Phase and neutral overcurrent protection

Electronic Circuit Breaker ESS1 for System SVS1

Electronic Circuit Protector ESX10-T

! CAUTION D TABLE 1

DC-DC Converter Module

Index. Capacitor Switching - 2 Contactors. Typical Circuit Diagram 2. Auxiliary Contact Blocks 2. Contactors 3. Dimensions 3. Technical Data 4,5,6

Transcription:

Type CAEM 21 Battery Earth Fault Relay

Type CAEM 21 Battery Earth Fault Relay CAEM 21 relay withdrawn from case Features l High sensitivity. l Variable setting range. l Fast operation. l High drop-off/pick-up ratio. l Self powered. No aux. supply is required. l Applicable for a wide range of battery voltages. l Provision for using external milliammeter. l Drawout case and tropicalised finish. Application The battery earth fault relay type CAEM 21 is used to detect earth faults and deterioration of wiring insulation in either pole of the battery. Description The scheme consists of a centre tapped resistor, a measuring relay, a plug setting bridge, an auxiliary relay and a rectifier bridge. For different battery voltages different values of centre tapped resistors are used. For ratings above 250V a standard 250V relay is used with a suitable external resistor board. Variable sensitivities are provided by means of the tapped coil whose taps are connected to the plug setting bridge. The centre tap of the resistor is brought to one of the terminals of the relay and this terminal is either directly earthed or earthed through a centre zero milliammeter. The schematic diagram shown (Figure 1) gives the general arrangement of the scheme. Under healthy condition no current flows through the measuring relay coil and in the event of an earth fault in any pole of the battery or a wiring insulation failure, current flows through the measuring relay coil and relay operates. The auxiliary relay operates through the measuring relay and initiates the alarm scheme. If a milliammeter is provided in the scheme its deflection also indicates the faulted pole of the battery. Technical data Ratings The relays can be supplied for application on battery voltages of 24V - 1000V dc Settings The relay settings are adjustable between 1 and 7 ma in 7 equal steps. With the relays set at 1mA, the corresponding insulation resistance of either the positive or negative bus for different dc voltages will be as shown in the Table given below. The Table also indicates the burden of the relay at rated voltage and the operating voltage band.

Table 1 Version Battery/dc Insulation Burden in watts Operating number rating in volts resistance at rated voltage band value in voltage kilo ohms at 1 ma tap 1 24/30 5/8.5 4/6 16.8V to 36V 2 48/60 17/23 7/12 33.6V to 72V 3 100/125 39/51 4/6 70V to 150V 4 200/250 87/111 8/12 100V to 300V 5 275/325 123/148 11/15 138V to 390V 6 400/480 181/221 15/22 200V to 576V 7 500/600 229/279 19/27 250V to 720V 8 625/750 289/353 25/35 313V to 900V 9 800/1000 370/470 48/74 400V to 1200V Case dimensions Maximum overall dimensions Case Height Width Depth* (mm) (mm) (mm) 1D 233 170 203 * Add 76 mm for maximum length of terminal studs, alternatively, 29 mm for terminal screws. The relays comply fully with the requirements of IS 3231 and are suitable for use in normal tropical environments. Contacts The relay will be fitted with two pairs of standard normally open output contacts. The contacts will be rated as follows: Make and carry Make and carry Break continuously for 3 seconds AC 1250VA with 7500VA with 1250VA with maxima of 5A maxima of 30A maxima of 5A and 660V and 660V and 660V DC 1250W with 7500W with 100W (resistive) maxima of 5A maxima of 30A 50W (inductive) and 660V and 66V with maxima of 5A and 660V

Notes 1. Additional resistor/capacitor/ diode will be included depending upon battery voltage. 2. Above 250V dc rating, the same relay with external resistor will be supplied. 3. The bias coil and the operating coil are wound on the same core. Figure 1: Schematic diagram of external and internal connections for CAEM 21 relay Notes 1. Even though two voltage ratings are indicated against each version number such as 24/30V, 48/60V etc. the same relay is used for a given version. For example, if it is version 3, the same relay will be used from 100V to 125V dc rating. 2. The insulation resistance values correspond to each voltage rating for a given version. Consider for example version 3. The insulation resistance values will be 39 and 51 kilo ohms for 100V and 125V dc systems respectively. 3. Similarly burden figures. For example relay burden is 4W and 6W at 100V and 125V dc respectively for version 3. 4. The indicated insulation resistance values are subject to a tolerance of ±10%. Operating time The operating time range is 40 to 60 milliseconds, at five times the setting. Drop-off/pick-up ratio Between 60% and 80%. Insulation The relay meets the requirements of IS 3231/IEC 225-5 Series C - 2 kv for 1 minute. Operation indicator A hand reset mechanically operated flag indicator is provided on auxiliary unit A as standard. Case The relay is supplied, mounted in a size 1D drawout case, suitable for flush mounting. The finish will be egg-shell black and the cases are fully tropicalised. The cases are also fitted with a breather unit to equalise the inside and outside pressures without admitting dust. Information required with order Battery rating (V dc)

ALSTOM Limited Pallavaram Works: 19/1, GST Road, Pallavaram, Chennai-600 043. India. Tel: 91-044-2368621 Fax: 91-044-2367276 Email: plw.applications@alstom.sprintrpg.eml.vsnl.net.in. 1998 ALSTOM Limited Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it. ALSTOM Limited cannot be held responsible for any reliance on any decision taken on its contents without specific advice PR:002:0799:A Printed in India.