A Single-Phase Voltage Sag Generator for Testing Electrical Equipments

Similar documents
Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

PQ Monitoring Standards

Power Quality Basics. Presented by. Scott Peele PE

II. RESEARCH METHODOLOGY

Protection from Voltage Sags and Swells by Using FACTS Controller

Roadmap For Power Quality Standards Development

A Novel Approach for Assessing the Impacts of Voltage Sag Events on Customer Operations

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

Harmonic control devices. ECE 528 Understanding Power Quality

Voltage Sag and Mitigation Using Dynamic Voltage Restorer (DVR) System

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

T-68 Protecting Your Equipment through Power Quality Solutions

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

Research and Trends in Power Quality

A Novel Power Conditioner Based On Electronic Transformer for High Frequency Ac Link

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Voltage Variation Compensation

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY

ISSN Vol.03,Issue.11, December-2015, Pages:

Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

A new SAIFI based voltage sag index

COMPARITIVE STUDY ON VOLTAGE SAG COMPENSATION UTILIZING PWM SWITCHED AUTOTRANSFORMER BY HVC

Power Quality in Metering

Power Control Scheme of D-Statcom

A SPWM CONTROLLED THREE-PHASE UPS FOR NONLINEAR LOADS

Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis

A NOVEL APPROACH TO ENHANCE THE POWER QUALITY USING CMLI BASED CUSTOM POWER DEVICES

Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

HIGH LOW Astable multivibrators HIGH LOW 1:1

ASTABLE MULTIVIBRATOR

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

Power quality as a reliability problem for electronic equipment

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Industrial Electronics

Performance of DVR under various Fault conditions in Electrical Distribution System

Power Quality Improvement using Hysteresis Voltage Control of DVR

Design of Interline Dynamic Voltage Restorer for Voltage Sag Compensation

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors

Harmonic Immunity And Power Factor Correction By Instantaneous Power Control Of D-STATCOM

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

APPLICATION OF INVERTER BASED SHUNT DEVICE FOR VOLTAGE SAG MITIGATION DUE TO STARTING OF AN INDUCTION MOTOR LOAD

Design Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM

Voltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM

LM2240 Programmable Timer Counter

SERIES ACTIVE power filters have proved to be an interesting

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

SUPERCONDUCTING MAGNETIC ENERGY

Design Requirements for a Dynamic Series Compensator for Voltage Sags Mitigation in Low Voltage Distribution System

Multivibrators. Department of Electrical & Electronics Engineering, Amrita School of Engineering

CHROMA ATE INC. Programmable AC Source 61500/61600 Series. Product Manager: Galen Chou

Field Programmable Gate Array-Based Pulse-Width Modulation for Single Phase Active Power Filter

Design and Development of Protective Circuit against Voltage Disturbances

Compensation of Different Types of Voltage Sags in Low Voltage Distribution System Using Dynamic Voltage Restorer

Amelioration of Power Quality in Isolated Power Systems

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners

Development and Simulation of Dynamic Voltage Restorer for Voltage SAG Mitigation using Matrix Converter

Design of Dynamic Voltage Restorer for three phase network as steady state device in the Distribution System

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

Compensation of Balanced and Unbalanced voltage disturbance using SRF controlled DVR

Power Quality and the Need for Compensation

Improving Passive Filter Compensation Performance With Active Techniques

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Design and Simulation of Dynamic Voltage Restorer (DVR) Using Sinusoidal Pulse Width Modulation (SPWM)

Using Optical Isolation Amplifiers in Power Inverters for Voltage, Current and Temperature Sensing

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online):

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

UNDERSTANDING POWER QUALITY

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453

Automatic Transfer Switch (ATS) Using Programmable Logic Controller (PLC)

Voltage Flicker Compensation using STATCOM to Improve Power Quality

Volume I Issue VI 2012 September-2012 ISSN

New Approaches for Harmonic Reduction Using Cascaded H- Bridge and Level Modules

Lab 7: DELTA AND SIGMA-DELTA A/D CONVERTERS

Fundamentals of Power Quality

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

I. INTRODUCTION A. GENERAL INTRODUCTION

Power Factor Improvement Using Thyristor Switched Capacitor Using Microcontroller Kacholiya Saurabh 1, Phapale Sudhir 2, Satpute Yuvraj 3, Kale.S.

DIGITAL ELECTRONICS: LOGIC AND CLOCKS

EE283 Electrical Measurement Laboratory Laboratory Exercise #7: Digital Counter

A NEW SINGLE STAGE THREE LEVEL ISOLATED PFC CONVERTER FOR LOW POWER APPLICATIONS

Power Quality Symptoms What Is Normal? Power Quality Approach. Other Power Quality Solutions

Closed Loop Single Phase Bidirectional AC to AC Buck Boost Converter for Power Quality Improvement

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

AND8056/D. Control Solution using Logic, Analog Switches, and Discrete Semiconductor Devices for Reversing a One-Phase Motor APPLICATION NOTE

AC/DC WLED Driver with External MOSFET Universal High Brightness

Reduced PWM Harmonic Distortion for a New Topology of Multilevel Inverters

A NOVEL APPROACH ON INSTANTANEOUS POWER CONTROL OF D-STATCOM WITH CONSIDERATION OF POWER FACTOR CORRECTION

Transcription:

1 A Single-Phase Voltage Sag Generator for Testing Electrical Equipments Yan Ma, Student Member, IEEE, George G. Karady, Fellow, IEEE Abstract This paper describes a transformer-based voltage sag generator (VSG) suitable to evaluate the susceptibility of electrical equipment to voltage sag. The built VSG utilized one auto-transformer and two solid state relays (SSRs) to provide nominal voltage and sag voltage to the load. The switch statuses of two SSRs are controlled by nominal voltage and sag voltage duration signal produced by electronic circuits. The VSG operating result shows that it enables effective control of sag magnitude, duration, beginning and ending points on output voltage wave. If needed, it can work as a voltage swell generator and a voltage interruption generator. By supplying high voltage (HV) transformer from the primary side, the VSG also can provide HV sag, swell, and interruption. The presented VSG is easier to set up in the lab, and the construction cost is much lower than buying VSG products at the current market. Index Terms Equipment susceptibility, voltage interruption, voltage sag, voltage sag generator, voltage swell. M I. INTRODUCTION odern power systems are becoming more and more sensitive to the quality of supplied power. The reason is that not only does modern equipment include a vast variety of electronic components which can be very vulnerable to power disturbance, but also the customers become more susceptible to the losses produced by equipment malfunction. As one of the most common power disturbances, voltage sag typically happens randomly and usually lasts only a few cycles. However, sensitive equipment often trips or shuts down for those sags, even if nominal voltage returns in just a few cycles. Thus, voltage sag brings the greatest financial loss compared with most other kinds of power disturbances [1], [2]. There are some devices installed in power systems to mitigate voltage disturbance, such as uninterruptible power supply, voltage regulator, and dynamic sag restorers. These devices are effective but expensive. It makes more economic sense to improve the sustainability of electrical equipment so they can tolerate common power disturbances without additional support [3]. The VSG is a kind of device which can This work was supported by Power Systems Engineering Research Center (PSERC). Y. Ma is with the Department of Electrical Engineering, Arizona State University, Tempe, AZ 85287 USA (e-mail: yan.ma@asu.edu). G. Karady is Salt River Chair Professor in the Department of Electrical Engineering at Arizona State University, Tempe, AZ 85287 USA (e-mail: karady@asu.edu ). supply reliable and repeatable voltage sags to measure equipment susceptibility to the voltage sags. With the help of the VSG, engineers can have improved knowledge about the equipment susceptibility to voltage disturbance, and further adjust the design of the equipment [4], [5]. Moreover, some standard methodologies have proposed recommended performance limits for equipment response to voltage sag with specific voltage sag magnitudes and durations. To fulfill these recommendations, engineers need the help of the device like the VSG [1], [6], [7]. Depending on different realization methods, there are four types of VSGs, which are amplifier-based, transformer-based, switching-impedance-based, and generator-based. Amplifiedbased VSG generates output voltages and currents with desirable characteristics by using a waveform generator and power amplifier. It can provide voltage sags with varying magnitude, duration, frequency and harmonics. Normally amplified-based VSG is more complicated and expensive than transformer-based VSG [8]. Transformer-based VSG is usually realized as a combination of transformers and appropriate switching devices. It can not provide changeable frequency and harmonic distortion. However it is low cost, and it is easily constructed in the lab [9]. Switchingimpedance-based VSG creates voltage sags by switching impedance into a power system by using the thyristor controlled reactor (TCR). It can provide harmonics by controlling firing angles of the TCR. Switching-impedancebased VSG is good at testing equipment in HV power circuits [10]. Generator-based VSG provides voltage sag by changing the exciting current of the generator. The weight and scale of the generator are the challenges [2]. Since transformer-based VSG is capable of generating the sag defined in reference [1] - a decrease in rms voltage or current at the power frequency for durations of 0.5 cycle to 1 min, it has more economic and reliability advantages than the other three types of the VSG. Some VSG products are already selling in the current market, such as Industry Power Corruptor by Power Standard Lab, and Porto-Sag by EPRI PEAC Corporation. They work well, however they are very expensive. In this paper, we propose a transformer-base VSG, which is very easy to construct in the lab, and has low cost - less than $300. 978-1-4244-1904-3/08/$25.00 2008 IEEE

2 II. STRUCTURE OF THE VSG The structure of the VSG is demonstrated in Fig. 1. Four parts are needed for the realization of the transformer-based VSG: 1) Duration control circuit, which regulates the duration of nominal voltage and voltage sag. 2) Signal shifting circuit, used to adjust sag beginning and ending points on voltage wave. 3) Drive circuit, providing nominal voltage or voltage sag based on the control signal generated by the signal shifting circuit. 4) Single-phase auto-transformer, for generating two voltage levels: nominal voltage and voltage sag. Fig. 1. The structure of the built transformer-based VSG The functions of the duration control circuit, signal shifting circuit, drive circuit, and autotransformer are described below. A. Duration control circuit The duration control circuit was built and Fig. 2 shows its detailed hardware diagram for 20 cycles pre-sag nominal voltage, 2 cycles voltage sag, and 20 cycles post-sag nominal voltage. The circuit is composed of one voltage comparator (LM311), one JK flip-flop, three 10 decoded counters (CD4017), some 3-input AND gates (7411), etc. The VSG was designed to operate after receiving a starting signal generated by an on-off-(on) toggle switch, and stop after getting an ending signal automatically produced by the duration control circuit. The debouncing circuit is used to mitigate the effects of mechanical toggle switch bounce, and provide smooth, reliable single pulse acting as a starting signal. The ending signal can be different according to the various voltage sag durations. In current design, the 115 th pulse was selected to be the ending signal. The starting signal and ending signal are combined together by one OR gate. The combined signal is provided to the counters as reset signal and the JK flip-flop as its input. Since the JK flip-flop is falling edge-triggered, the output of the JK flip-flop will be low during the time after the falling edge of starting signal and before the falling edge of ending signal, which enable the counters begin to work. As a result the working time of the counters is controlled based on starting signal and ending signal and further VSG operation time is controlled. The AC line voltage (115Vac) is supplied to voltage comparator through an isolation transformer (117/6.3Vac). The voltage comparator compares 3Vac with the ground, then output a synchronous voltage square waveform, which has the same frequency with the input AC source and 0.5 duty ratio. The synchronous voltage square waveform is supplied to the first counter as its clock signal. The carryout output (10 cycles duration and 0.5 duty ratio) of the first counter acts as the

3 clock signal for the second counter. The carryout output of the second counter (100 cycles duration and 0.5 duty ratio) acts as the clock signal for the third counter. By using three counters, any cycle after VSG initiation and before 1000 th cycle can be captured individually. For example, if we want to get 123 rd cycle, we just need to use 3-input AND gates to combine 1 st pulse output of the 3 rd counter, 2 nd pulse output of the 2 nd counter, and 3 rd pulse output of the 1 st counter, and then the output of 3-input AND gates will be the 123 rd cycle. Four special pulses/cycles are generated by the duration control circuit for regulating the duration of nominal voltage and sag voltage. The functions of these four specific pulses are as follows: 1 st special pulse: Beginning pre-sag nominal voltage. 2 nd special pulse: Ending pre-sag nominal voltage and beginning voltage sag. 3 rd special pulse: Ending voltage sag and beginning postsag nominal voltage. 4 th special pulse: Finishing post-sag nominal voltage. A PSpice simulation diagram was drawn to verify the design of the duration control circuit. Fig. 3 displays the simulation result of the duration control circuit, which includes the synchronous voltage square waveform generated by voltage comparator, starting signal, ending signal, enable signal for the counters, and the combination of four special pulses (1 st, 21 st, 26 th, and 46 th cycles) for 20 cycles pre-sag nominal voltage, 5 cycles voltage sag, and 20 cycles post-sag nominal voltage. (a) Synchronous voltage square wave generated by voltage comparator (b) Starting signal (left pulse) and ending signal (right pulse) (c) Enable signal for the counters (VSG operation duration) (d) The combination of four special pulses for 5 cycles sag, 20 cycles pre-sag nominal voltage, and 20 cycles post-sag nominal voltage Fig. 3. The simulation result of the duration control circuit Based on the different duration requirements for nominal voltage and sag voltage, the different four special pulses are generated, combined, and supplied to the signal shifting circuit. B. Signal shifting circuit Since voltage sag may begin and finish at any point of the voltage wave, a signal shifting circuit is built to shift the 2 nd and 3 rd special pulses which determine the beginning and ending of the sag. Fig. 4 shows the detailed hardware diagram of the signal shifting circuit. With the current VSG design, the pulse shifting circuits for the 2 nd and 3 rd specific pulse are the same, and the 2 nd and 3 rd specific pulse can be shifted up to 1 cycle afterward. Fig. 5 shows the simulation result of the pulse shifting circuits simulated with the PSpice. The pulse is shifted by the following steps: The pulse (Fig. 5 (a)) with 1 cycle duration is inverted by one inverter (7404) and the inverted pulse is provided to one 555 timer. The inverter is used here for the 555 timer is falling edge-triggered. The output of the 555 timer is a prolonged pulse (Fig. 5 (b)) with 2 cycles duration. The pulse with 2 cycles duration passes the RC circuit composed of one 10 kω resister and one 1uF capacitor (as shown in Fig. 4), and becomes an exponential signal (Fig. 5 (c)). By using one voltage comparator (LM311), the exponential signal is compared with one adjustable voltage (Fig. 5 (c)) to get a delayed pulse (Fig. 5 (d)) compared to the original pulse. The delay time is determined by the high level duration of the prolonged pulse generated by the 555 timer and compared adjustable voltage of the voltage comparator. Fig. 4. The simulation diagram of VSG signal shifting circuit with 2 cycles sag duration

4 One inverter and one 555 timer are used to stabilize the output signal of the voltage comparator. were selected as the switches to provide output voltage with nominal voltage and voltage sag. The SSR1 is closed for nominal voltage, and the SSR2 is closed for sag voltage. (a) Pulse input (b) Prolonged pulse by 555 timer (c) The exponential signal and compared voltage Fig. 7 The construction of the drive circuit (e) Shifted pulse Fig. 5 Pulse shifting The shifted 2 nd and 3 rd special pulses and un-shifted 1 st and 4 th special pulse are combined together and supplied to 4 th counter. The 4 th counter has the same reset signal and enable signal as the 1 st, 2 nd, 3 rd counters. The 1 st and 3 rd output signals of the 4 th counter are combined by an OR gate, and the combined signal is the final duration signal for nominal voltage. The 2 nd output signal of the 4 th counter is the final duration signal for sag voltage. The final duration signals for nominal voltage and sag voltage will be provided to the drive circuit. Fig. 6 shows simulation result for the input and output signals of the signal shifting circuit. The 2 nd pulse is shifted half cycle, the 3 rd pulse is shifted one cycle, and the duration of sag voltage is actually 5.5 cycles. (a) Four special pulses provided to the signal shifting circuit from the duration control circuit (b) The 2 nd and 3 rd pulse are shifted afterward in the signal shifting circuit (c) The combination of the 1 st and 3 rd output signals of 4 th counter, which is control signal for nominal voltage (d) The 2 nd output signal of the 4 th counter, which is control signal for sag voltage Fig. 6 The input and output signals of the signal shifting circuit C. Drive circuit Fig. 7 shows the internal construction of the drive circuit and its connection with auto-transformer, signal shifting circuit and the load. The output voltage waveform of the drive circuit can be provided to a HV transformer to generate HV voltage sag for testing HV equipments. Two non-zero crossing SSRs (S216SE1) SSR1 and SSR2 The switch statuses of the SSR1 and SSR2 are controlled by the duration signals generated by the signal shifting circuit. As a characteristic of the SSR, it switches on when there is a gate voltage applied to it, and switches off automatically when the gate signal disappears and the current passing it is zero. Accordingly when the drive circuit receives the duration signal for sag voltage, SSR2 is closed, while SSR1 will not be open until the current crossing it becomes zero. Similarly when the drive circuit receives the duration signal for post-sag nominal voltage, SSR1 is closed and SSR2 will stay close before the coming first current zero crossing. In some sense, the beginning and ending points of sag voltage on output voltage waveform are dependent on both the duration signal for sag voltage and the load. The maximum output power of the VSG is determined by the characteristics of the SSRs, such as maximum load voltage and maximum load current. In the built VSG, the SSRs are changeable so the SSRs can be selected based on different requirements. D. Single-phase auto-transformer The purpose of including single-phase auto-transformer in the VSG is to provide two voltage sources (nominal voltage and sag voltage) to the drive circuits. In exchanging the nominal voltage source with the sag voltage source, the VSG will act as a voltage swell generator. In reducing sag voltage to less than 10% nominal voltage or un-connecting the sag voltage source with the drive circuit, the VSG can be used as a voltage interruption generator. The auto-transformer also can be replaced by two single-phase transformers to obtain the special magnitudes of nominal voltage and sag voltage. III. VSG OPERATION Table I shows the specifications of the built VSG. TABLE I SPECIFICATIONS OF THE VSG Control voltage 75 to 185 Vac Operating frequency 45 to 65 Hz Maximum load voltage 260Vac Maximum load current 16Arms Peak one cycle surge current 160A

5 Sag magnitude 0% to 100% Swell magnitude 100% to 345% Sag duration 0 to 16 second Sag beginning and ending points on voltage wave 0 to 360 Fig. 8 shows three kinds of VSG operating results (voltage sag, voltage swell, and voltage interruption) captured by digital scope. (a) 50% voltage sag with 1.5 cycles duration (b) 115% voltage swell with 2 cycles duration (c) Voltage interruption with 4.5 cycles duration Fig.8. VSG operation results captured by digital scope IV. CONCLUSION As one of the concerns in power quality, voltage sag brings lots of troubles to the performance of electrical equipment. The VSG is widely used to evaluate equipment susceptibility to voltage sag. In the current market, there are some VSG products which are successful but are very expensive. A transformer-based VSG is presented in this paper, and it is easy to build in the lab with a comparable low cost. The operation result showed that the designed VSG is capable of controlling effectively the magnitude and duration of nominal voltage and sag voltage, and the starting point and ending point of the sag voltage. With appropriate connection, the VSG also can work as voltage swell generator and voltage interruption generator. If needed, the VSG can provide HV sag, swell, and interruption by connecting with the primary side of the HV transformer. V. REFERENCES [1] IEEE recommended practice for evaluating electric power system compatibility with electronic process equipment, IEEE Standard 1346-1998, 20 July, 1998. [2] E. R. Collins, R. L. Morgan, A three-phase sag generator for testing industrial equipment, IEEE Trans. Power Delivery, vol. 11, pp. 526-532, Jan. 1996. [3] Alex Mceachern, Voltage sag generators: not as simple as they seen, http://www.powerquality.com/mag/power_voltage_sag_generators/index.h tml, July 1, 2001. [4] J. Lamoree, D. Mueller, P. Vinett, W. Jones, M. Samotyj, Voltage sag analysis case studies, IEEE Trans. Industry Applications, vol. 30, pp. 1083-1089, Jul.-Aug. 1994. [5] Saksena, S.; Karady, S.G, Effects of voltage sags on household loads, IEEE Power Engineering Society General Meeting, vol. 3, pp. 2456-2461, 12-16 Jun. 2005. [6] M. F. Alves, T.N. Ribeiro, Voltage sag: an overview of IEC and IEEE standards and application criteria, in proc. 1999 IEEE Transmission and Distribution Conf., vol. 2, pp. 585 589, 11-16, Apr. 1999. [7] Semiconductor Industry, SEMI F42-0600 test method for semiconductor processing equipment voltage sag immunity, June.1999. [8] S. Z. Dokic, J. V. Milanovic, K. A. Charalambous, Computer simulation of voltage sag generator, in proc. 10th international conference on harmonics and quality of power, vol. 2, pp. 649-654, 6-9 Oct. 2002. [9] Zhiyong Yu, Guangbin Liu, Hong Wu, Development of generator for voltage dips, short interruptions and voltage variations immunity test, in proc. 2002 3rd International Symposium on Electromagnetic Compatibility, pp. 67-70, 21-24 May 2002 [10] Y. H. Chung, G. H. Kwon, T. B. Park, G. Y. Lim, Voltage sag and swell generator with thyristor controlled reactor, in proc. 2002 International Conf. on Power System Technology, vol. 3, pp. 1933-1937, 13-17 Oct. 2002. VI. BIOGRAPHIES Yan Ma was born in Hegang, China. She received her B. S. degree and M. S. degree in Electrical Engineering from North China Electric Power University, Beijing, China. She is currently pursuing the Ph. D. degree at Arizona State University. Her current research and academic interests include digital protection system for power system, high-voltage engineering, fuel cell technology, and power electronics application in power system. George Karady received his BSEE and Doctor of Engineering degrees in electrical engineering from the Technical University of Budapest. Dr. Karady was appointed to Salt River Chair Professor at Arizona State University in 1986. Previously, he was with EBASCO Services where he served as Chief Consulting Electrical Engineer, Manager of Electrical Systems, and Chief Engineer of Computer Technology. He was Electrical Task Supervisor for the Tokomak Fusion Test reactor project in Princeton. Dr. Karady is a registered Professional Engineer in New York, New Jersey, and Quebec. He is the author of more than 100 technical papers.