The power transformer

Similar documents
EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Basic Operating Principles of Transformers

Spring 2000 EE361: MIDTERM EXAM 1

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

148 Electric Machines

El-Hawary, M.E. The Transformer Electrical Energy Systems. Series Ed. Leo Grigsby Boca Raton: CRC Press LLC, 2000

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES

Generalized Theory Of Electrical Machines

CHAPTER 2. Transformers. Dr Gamal Sowilam

Practical Transformer on Load

Chapter 2-1 Transformers

EE 340 Power Transformers

ECG 741 Power Distribution Transformers. Y. Baghzouz Spring 2014

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)

Transformers. gpmacademics.weebly.com

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

cos sin XqIq cos sin V X Consider a simple case ignoring R a and X l d axis q axis V q I q V d I d Approximately, the second item can be ignored:

CHAPTER 4. Distribution Transformers

ECE 3600 Transformers b

SECTION 4 TRANSFORMERS. Yilu (Ellen) Liu. Associate Professor Electrical Engineering Department Virginia Tech University

VALLIAMMAI ENGINEERING COLLEGE

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

Transformers. Dr. Gamal Sowilam

Example of Transformer Connections and Ground Currents

86 chapter 2 Transformers

~=E.i!=h. Pre-certification Transformers

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Exercises on overhead power lines (and underground cables)

ELECTRICAL ENGINEERING ESE TOPIC WISE OBJECTIVE SOLVED PAPER-II

Transformers. Department of Physics & Astronomy Texas Christian University, Fort Worth, TX. April 23, 2013

PHYS 1441 Section 001 Lecture #22 Wednesday, Nov. 29, 2017

Module 1. Introduction. Version 2 EE IIT, Kharagpur

Module 7. Transformer. Version 2 EE IIT, Kharagpur

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Code No: R Set No. 1

Transmission Line Models Part 1

Electrical Machines I : Transformers

Transformers 21.1 INTRODUCTION 21.2 MUTUAL INDUCTANCE

Transformers. Objectives

Power systems 2: Transformation

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Combined analytical and FEM method for prediction of synchronous generator no-load voltage waveform

Preface...x Chapter 1 Electrical Fundamentals

Hours / 100 Marks Seat No.

PHYS 1444 Section 501 Lecture #20

Practical Tricks with Transformers. Larry Weinstein K0NA

By Gill ( ) PDF created with FinePrint pdffactory trial version

1 K Hinds 2012 TRANSFORMERS

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

Transformer & Induction M/C

Simultaneous AC-DC Transmission Scheme Under Unbalanced Load Condition

An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks

UNIT 1 CIRCUIT ANALYSIS 1 What is a graph of a network? When all the elements in a network is replaced by lines with circles or dots at both ends.

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

CHAPTER 2 D-Q AXES FLUX MEASUREMENT IN SYNCHRONOUS MACHINES

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

LECTURE NOTES ON ELECTRICAL MACHINE-II. Subject Code-PCEL4302

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

Table of Contents. Table of Figures. Table of Tables

ELECTRICAL POWER TRANSMISSION TRAINER

APPLICATION NOTE - 018

SYNCHRONOUS MACHINES

Electromagnetic Oscillations and Currents. March 23, 2014 Chapter 30 1

IVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad ELECTRICAL AND ELECTRONICS ENGINEERING

TEST VOLTAGES INFLUENCE ON TURN RATIO TESTING ndb Technologies model ART-3D

Electrical Circuits and Systems

Chapter 16: Mutual Inductance

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

PAPER-II (Subjective)

Oscillators. An oscillator may be described as a source of alternating voltage. It is different than amplifier.

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Walchand Institute of Technology. Basic Electrical and Electronics Engineering. Transformer

MATHEMATICAL MODELING OF POWER TRANSFORMERS

CHAPTER 9. Sinusoidal Steady-State Analysis

EE2022 Electrical Energy Systems

Basic Principles and Operation of Transformer

TUNED AMPLIFIERS 5.1 Introduction: Coil Losses:

In Class Examples (ICE)

Three phase transformer 1

TRANSFORMER THEORY. Mutual Induction

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

Open Circuit (OC) and Short Circuit (SC) Tests on Single Phase Transformer

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

, ,54 A

1. Explain in detail the constructional details and working of DC motor.

Design and Simulation of Passive Filter

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Reg. No. : BASIC ELECTRICAL TECHNOLOGY (ELE 101)

Downloaded From All JNTU World

AUTO-TRANSFORMER. This is having only one winding; part of this winding is common to both primary and secondary.

13. Magnetically Coupled Circuits

ECE 241L Fundamentals of Electrical Engineering. Experiment 8 A-C Transformer, Magnetization & Hysteresis

ELECTRICAL POWER ENGINEERING

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

Electric Circuits II Magnetically Coupled Circuits. Dr. Firas Obeidat

Transcription:

ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35

Power transformers are used: to transmit electrical energy under high voltages step-up transformers at the terminal of generators step-down transformers to distribute energy at the end-users to control the voltages at some busbars: in sub-transmission networks in distribution networks to control the power flows in some parts of a meshed network. 2 / 35

The single-phase transformer Principle The single-phase transformer step-up transformer: secondary voltage > primary voltage step-down transformer: secondary voltage < primary voltage. alternating voltage v 1 at terminals of coil 1 alternating current i 1 in coil 1 alternating magnetic field voltage induced in coil 2 current i 2 in coil 2 magnetic field superposed to the one created by i 1. 3 / 35

The single-phase transformer Fluxes in coils n 1 i 1 +n 2 i 2 = Rφ m φ m : magnetic flux in a cross section of the iron core R : reluctance of the magnetic circuit + sign: due to the way coils are wound and the direction of currents ψ 1 = ψ l1 + n 1 φ m ψ 1 : flux linkage in coil 1 ψ l1 : leakage flux in coil 1 (lines of magnetic field crossing coil 1 but not passing through the iron core) ψ 2 = ψ l2 + n 2 φ m ψ 2 : flux linkage in coil 2 ψ l2 : leakage flux in coil 2 (lines of magnetic field crossing coil 2 but not passing through the iron core) 4 / 35

Ideal transformer The power transformer The single-phase transformer The coils have no resistance the coils have no leakage flux the permeability of the core material is infinite. R 0 i 2 = n 1 n 2 i 1 v 1 = dψ 1 dt = n 1 dφ m dt v 2 = dψ 2 dt = n 2 dφ m dt v 2 = n 2 n 1 v 1 Step-down transformer: v 2 < v 1 n 2 < n 1 i 2 > i 1 coil 2 has fewer turns but higher cross-sectional area v 1 i 1 = v 2 i 2 : no losses in the ideal transformer! 5 / 35

Equations of the real transformer The single-phase transformer Leakage inductances: L l1 = ψ l1 i 1 L l2 = ψ l2 i 2 Magnetizing inductance (seen from coil 1) : L m1 = n2 1 R Flux linkages: ψ 1 = L l1 i 1 + n 1 n 1 i 1 + n 2 i 2 R = L l1 i 1 + n2 1 R i 1 + n 1n 2 R i 2 = L l1 i 1 + L m1 i 1 + n 2 n 1 L m1 i 2 ψ 2 = L l2 i 2 +n 2 n 1 i 1 + n 2 i 2 R = L l2 i 2 + n2 2 R i 2 + n 1n 2 R i 1 = L l2 i 2 +( n 2 n 1 ) 2 L m1 i 2 + n 2 n 1 L m1 i 1 Voltages at the terminals of the coils: v 1 = R 1 i 1 + dψ 1 dt v 2 = R 2 i 2 + dψ 2 dt di 1 = R 1 i 1 + L l1 dt + L di 1 m1 dt + n 2 di 2 L m1 n 1 dt di 2 = R 2 i 2 + L l2 dt + (n 2 ) 2 di 2 L m1 n 1 dt + n 2 di 1 L m1 n 1 dt 6 / 35

The single-phase transformer The transformer is a particular case of magnetically coupled circuits - if the currents enter by the terminals marked with, their contributions to the flux φ m are added - if the currents are counted positive when entering the terminals marked with, the mutual inductance is positive - the also indicate AC voltages which are in phase when the transformer is supposed ideal. One easily identifies: L 11 = L l1 + n2 1 R L 12 = n 1n 2 R L 22 = L l2 + n2 2 R 7 / 35

Equivalent circuits of the real transformer The single-phase transformer R 1 i 2 1 + R 2i 2 2 : copper losses Passing R 2 et L l2 from side 2 to side 1: Possible improvements: shunt resistance to account for iron losses (due to eddy currents) kept small by using laminated cores negligible compared to the power passing through the transformer non-linear inductance L m1 to account for iron saturation. 8 / 35

The single-phase transformer Usual simplified equivalent circuit Usual simplification taking into account that: ωl m1 >> R 1, R 2, ωl l1, ωl l2 n = n 2 R = R 1 + R 2 n 1 n 2 X = ωl l1 + ωl l2 n 2 X m = ωl m1 Equivalent circuit justified by the measurements provided by manufacturers X = leakage reactance (combined) X = short-circuit reactance = reactance seen from port 1 when port 2 is short-circuited (considering that X m is very large compared to X ) 9 / 35

The three-phase transformer The three-phase transformer First type Three separate single-phase transformers. No magnetic coupling between phases. Appropriate for transformers of large nominal power: in case of failure of one of the transformers, only that transformer is replaced easier to carry. 10 / 35

Second type The power transformer The three-phase transformer The three phases are mounted on a common iron core. core configuration shell configuration Volume of the common core smaller than three times the volume of a single core. 11 / 35

The three-phase transformer Star vs. Delta configuration Four possible mountings. Transformer side connected to extra high voltage network: star configuration preferred since the voltage across each winding is 3 times smaller star configuration: possibility to connect the neutral to ground (safety) star configuration preferred to place a load tap changer (see later in this chapter) transformer side carrying high currents (f.i. the generator side of a step-up transformer): delta configuration preferred since the currents in the branches are 3 times smaller delta configuration used to eliminate the harmonics of order 3, 6, 9, etc. 12 / 35

The three-phase transformer Single-phase equivalents of three-phase transformers transformer with single core: the phases are magnetically coupled perform a per-phase analysis (see Chapter 2) for simplicity, we consider a transformer with three separate cores we focus on the impact of the star vs. delta configuration. 1. Star-star configuration Yy0 Per-phase equivalent circuit = equivalent circuit of one phase. 13 / 35

The three-phase transformer 2. Delta-delta configuration Dd0 Equivalent circuit: 14 / 35

The three-phase transformer 3. Star-delta configuration Yd11 / Dy1 V a = 1 3 e jπ/6 Va c = n 2 3n1 e jπ/6 V1n = n V 1n où n = n 2 3 n1 e jπ/6 Ī a = Īa c Īb a = 3 e jπ/6 Ī a c = 3 n1 n 2 1 e jπ/6 Ī1 = 1 n Ī1 15 / 35

The three-phase transformer Equivalent circuit: Ideal transformer with complex ratio n : is characterized by : Va = n V 1 Ī a = Ī1/ n reduces to the standard ideal transformer if n is real transfers complex power without losses: Va Ī a = n V 1 1 n Ī 1 = V 1 Ī 1 The above two-port is non reciprocal: Ī a ] V a=0, V a =1 Īa ] V a=1, V a =0 16 / 35

The three-phase transformer 4. Delta-star configuration Dy1 / Yd11 Derivation similar to that of the Star-delta configuration, leading to a single-phase equivalent circuit with: the complex transformer ratio: n = a series resistance R/3 a series reactance X /3 a shunt reactance X m /3. 3 n2 n 1 e jπ/6 17 / 35

The three-phase transformer Designation of a transformer Standardized abbreviation of I.E.C. (International Electrotechnical Commission) Also referred to as vector group of a transformer 3 symbols: an uppercase letter for the high-voltage side: Y for a star connection or D for a delta a lowercase letter for the low-voltage side: y for a star connection or d for a delta an integer p {0, 1,..., 11}: an indication of the phase displacement between the primary and secondary voltages of the same phase, the transformer being assumed ideal the phasor of the high voltage being on the number 12 of a clock, p is the number pointed by the phasor of the low voltage and for the star configuration: n after y or Y to indicate that the neutral is grounded. 18 / 35

The three-phase transformer Caution as regards using transformers with different phase displacements When a given sub-network is fed by two (or more) transformers operating in parallel (i.e. located in at least one loop), the latter must have the same phase displacement p. Otherwise, the different phase displacements would cause unacceptable power flows. 19 / 35

Simplification of computations The power transformer The three-phase transformer Two transformers with the same phase displacement: ϕ A = ϕ B = ϕ The ideal transformers with complex ratio e jϕ can be removed without changing: the magnitudes of the branch currents and bus voltages the complex powers flowing in the branches. The phase displacements in the transformer models are ignored when computing the steady-state balanced operation of power systems. 20 / 35

Nominal values, per unit system and orders of magnitudes Nominal values, per unit system and orders of magnitudes Nominal values Nominal primary voltage U 1N and nominal secondary voltage U 2N : voltages for which the transformer has been designed (in particular its insulation). The real voltages may deviate from these values by a few %. Nominal primary current I 1N and nominal secondary current I 2N : currents for which the transformer has been designed (in particular the cross-sections of the conductors). Maximum currents that can be accepted without limit in time. nominal apparent power S N : S N = 3U 1N I 1N = 3U 2N I 2N 21 / 35

Conversion of parameters in per unit values Nominal values, per unit system and orders of magnitudes choose the (three-phase) base power S B = S N on primary side, choose the (phase-to-neutral) base voltage V 1B = U 1B / 3 on secondary side, choose the (phase-to-neutral) base voltage V 2B = U 2B / 3 the impedances of the equivalent circuit, which are located on the primary side, are divided by Z 1B = 3V 2 1B /S B = U 2 1B /S B the value of the transformer ratio n = n 2 /n 1 in per unit is obtained as follows: v 2 = n 2 n 1 v 1 v 2pu = v 2 V 2B = n 2 n 1 V 2B v 1 = n 2 V 1B n 1 V 2B v 1 V 1B = n 2 V 1B n 1 V 2B v 1pu n pu = n 2 V 1B n 1 V 2B If V 2B /V 1B = n 2 /n 1 : n pu = 1 : the ideal transformer disappears from the equivalent circuit! In practice, V 2B /V 1B n 2 /n 1 : the ideal transformer remains in the equivalent circuit but with a ratio n pu 1. 22 / 35

Nominal values, per unit system and orders of magnitudes Orders of magnitude resistance R < 0.005 pu leakage reactance 1 ωl range: 0.06 0.20 pu magnetizing reactance ωl m range: 20 50 pu transformer ratio n = n 2 /n 1 range: 0.85 1.15 pu values on the (S B, V 1B, V 2B ) base of the transformer!! Network computation in another base: convert the parameters to that base (see formula in the chapter on per unit system) 1 or short-circuit reactance 23 / 35

Autotransformers The power transformer Autotransformers Single-phase autotransformer Transformer whose primary and secondary sides are connected in such a way that they have a winding in common: 24 / 35

Autotransformers Let us assume that the inner transformer operates with its voltages and currents at their nominal values (all losses neglected, transformer assumed ideal). Ratio of the autotransformer? I1N auto = I 1N V2N auto = V 2N V1N auto = V 1N + V 2N = (1 + n 2 )V 1N n 1 I auto 2N = I 1N + I 2N = ( n 2 n 1 + 1)I 2N n auto = V 2N auto V1N auto = n V 2 2N n = 1 V 1N + V 2N 1 + n2 n 1 For the chosen primary and secondary, the transformer is of the step-down type. 25 / 35

Autotransformers Nominal apparent power of the autotransformer? S auto N = V1N auto I1N auto = (1 + n 2 )V 1N I 1N = (1 + n 2 )S N n 1 n 1 The autotransformer allows for a power transfer higher than S N. reduced investment costs and reduced losses! True for any n 1, n 2 values but for a higher amplification : n 2 n 1 However, if n 2 n 1, the autotransformer ratio n auto 1. Hence, the device cannot connect two very different voltage levels Autotransformers used to transfer high powers between two networks with relatively close nominal voltages Belgium : 550 MVA autotransformers between 400 and 150 kv France: autotransformers between 400 and 225 kv. drawback: metallic connection between primary and secondary voltage disturbances propagate more easily. Three-phase autotransformer Assembly of three single-phase autotransformers. 26 / 35

Adjustment of the turn ratio Adjustment of the turn ratio Principle Objective: adjust voltage at a busbar (usually one of the transformer ends) adjustment in steps: between 15 and 25 tap positions to modify the number of turns in service: transformer taken out of service transformer kept in service: the on-load (or under-load or load) tap changer modifies the windings without interrupting the current (avoid electric arcs!) load tap changers can be controlled manually: remotely by operator supervising the network from a control center automatically: local feedback system (see chapter on voltage control) placement of tap changer: usually on the high-voltage side: current smaller, more turns in winding three-phase transformer: near neutral in Y configuration (lower voltages). 27 / 35

Adjustment of the turn ratio Accounting the tap position changes in equivalent circuit In principle, one set of (R, ωl, ωl m1, n) values for each tap position. In practice, ωl and n are the most affected, while R and ωl m1. Possible simplification: let us assume that: the turns are adjusted on side 2 in equivalent circuit the leakage inductance L l2 vary with the number of turns n 2 according to: and similarly for the resistance R 2 : This is arguable, but R 2 is small... L l2 = L o l2( n 2 n2 o ) 2 R 2 = R2 o ( n 2 n2 o ) 2 28 / 35

Adjustment of the turn ratio After passing R 2 and L l2 on the other side of the ideal transformer: When the tap position (and, hence, the number of turns n 2 ) changes: impedances located on the non-adjusted side remain constant only the transformer ratio n 2 /n 1 changes. 29 / 35

Three-winding transformers Three-winding transformers Shortcut for transformers with three windings per phase. Principle Single-phase transformer with 3 windings (= 1 phase of a 3-phase transformer) : Power transfer between three voltage levels share of power flows between the windings depends on what is connected to the transformer nominal apparent powers of the three windings usually different. 30 / 35

Three-winding transformers Other uses in switching stations, power supplied to auxiliaries by the third winding connection of a shunt inductance or capacitor for compensation purposes improvement of operation in unbalanced condition improvement of power quality in the presence of harmonics. Equivalent circuit R 1 + R 2 + j(x 1 + X 2 ) : impedance seen from 1 with 2 short-circuited and 3 opened R 1 + R 3 + j(x 1 + X 3 ) : impedance seen from 1 with 3 short-circuited and 2 opened Some reactances of this equivalent circuit can be negative (for instance if the windings have very different nominal apparent powers). 31 / 35

Phase shifting transformer Phase shifting transformer Also called simply phase shifter. Transformer aimed at shifting the secondary voltage phasor with respect to the primary voltage phasor, in order to adjust active power flows in the network. Two main configurations: transformer connecting two networks with different nominal voltages (as usual) to which a device is added to adjust the phase angle dedicated device, with the same primary and secondary nominal voltages, aimed at adjusting the phase angle. 32 / 35

Phase shifting transformer First scheme adjustment in quadrature some variation of the voltage magnitude with the phase angle there exist more elaborate schemes where the voltage magnitude is kept constant while the phase angle is adjusted drawback of this scheme: the whole line current passes through the tap changer (unavoidable electric arcs). 33 / 35

Phase shifting transformer Second scheme excitation shunt transformer + series transformer nominal voltage of series transformer = fraction of nominal phase-to-neutral voltage V N nominal apparent power = fraction of 3V N I max compared to previous scheme: lower current in the tap changer. 34 / 35

Phase shifting transformer Example: phase shifting transformers on the borders of Belgium 380/380 kv : in series with: 1 line Zandvliet (B) - Borssele (NL) and Zandvliet (B) - Geertruidenberg (NL) 2 line Meerhout (B) - Maasbracht (NL) 3 line Gramme (B) - Maasbracht (NL) nominal power 3V N I max = 1400 MVA phase shift adjustment: 35 positions, +17/-17 1.5 o (at no load) 220/150 kv : in series with the Chooz (F) - Monceau (B) line nominal power: 400 MVA in-phase adjustment : 21 positions, +10/-10 1.5 % quadrature adjustment: 21 positions, +10/-10 1.2 o 35 / 35