protim-r Module

Similar documents
protim-r Module

protim-c Module Bently Nevada* Asset Condition Monitoring

Low Frequency Velocity Sensor

1701/25 FieldMonitor Seismic Input Monitor for Velocity and Acceleration Input

High Temperature Velocity and Acceleration Sensor

Trendmaster * Dynamic Scanning Module

Underwater Probes. Bently Nevada* Asset Condition Monitoring. Description

Underwater Probes. Description

3500/64M Dynamic Pressure Monitor

the 3500/44M Aeroderivitive GT Vibration Monitor for the

Intrinsically Safe Pressure Transmitter for applications in hazardous environments and shipbuilding industry Model IS-20-S, IS-21-S, IS-20-F, IS-21-F

STANDARD RTD's INDEX

Specifications. Specifications. Transfer Characteristics Accuracy at 20 C (68 F) Temperature Drift

ED701 General Industry Pressure Transmitter

IP26 Series Current to Pneumatic Converter

Rosemount 848L Logic Transmitter with FOUNDATION Fieldbus

ST5484E Seismic Velocity 4-20 ma Transmitter Datasheet

Detailed Specifications & Technical Data

Intrinsically Safe Pressure Transmitter for highest pressure applications in hazardous environments Model IS-20-H

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

MIL-C-17 Standard RF Coaxial Cable Low Loss & Ultra Low Loss RF Microwave Cable ANTENNA & TEST Cable up to 26.5 GHz

Intrinsically safe pressure transmitter MBS 4201, MBS 4251, MBS 4701 and MBS 4751

Temposonics. Magnetostrictive Linear Position Sensors. ET Analog Data Sheet

Resistance Thermometers Model Series TR7X0, Sheathed Design

Rosemount 3101, 3102, and 3105

CIR (Crush & Impact Resistant) VFD Power Cable

Differential-Hall-Effect based Sensors Ex ia for Detection of Speed and Direction of Rotation in Hazardous Areas Zone 0 or 1 Series A5S1DD3 / A5S1DS3

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

Level Measurement Continuous level measurement Radar transmitters

Mobrey Ultrasonic. MSP422, MSP400RH, and MSP900GH Level Transmitters. Product Data Sheet February 2015 IP2045, Rev EA

Proximity Transmitters and Seismic Vibration Transmitters

Loop Powered Indicator

Model 144H NEW. PC-Programmable Temperature Transmitter. Product Data Sheet

Isolators A3/1. Vibration Transducer Supply Unit Series

1443 Series Accelerometers Specifications

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.

4-20 ma Vibration Transmitter, Top connector

Detailed Specifications & Technical Data

Head mounted Temperature Transmitter TF02/TF02-Ex

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters

Differential-Hall-Effect based Sensors for Detection of Speed and Direction of Rotation with two phase-shifted speed signals Series A5S0DD4 / A5S0DS4

TQ 402 & TQ 412 / EA 402 / Proximity System : TQ 402 & TQ 412 Proximity Transducers EA 402 Extension Cable IQS 452 Signal Conditioner FEATURES

Temperature Input Module for Zone 1 Series 9482/32

Datasheet Platinum Resistance Pt100 In-head (Push Button) Temperature Transmitter TX203P mA output, default range supplied C

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

TQ 401 / EA 401 / IQS 451. Proximity System : TQ 401 Proximity Transducer EA 401 Extension Cable IQS 451 Signal Conditioner FEATURES

Isolators A3/1. Ex i Power Supply Field Circuit Ex i Series

Electrodynamic Velocity Sensor

MJK Expert 700 / 800 / 900 / 1100 / 2100 MJK Expert 1400 / 3400

Torque Sensor Accessories and Services

RP SMA Male Right Angle Connector Solder Attachment for PE-SR402AL, PE-SR402FL, RG402

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i

EXTRA-PREMIUM GRADE PVC JACKET FOR EXTENDED CABLE LIFE. 24 AWG (0,23mm 2 ), 7/32 (7x0,20mm), Insulation Thickness: 0.010" (0,25mm)

GEXOL WORLD CLASS OIL & GAS CABLES

EPHY-MESS GmbH phone: Berta-Cramer-Ring 1 fax: Wiesbaden Germany

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22

Mass and Volume Flow Transmitter

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

Load Cell Accessories and Services

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

Two-channel safety barriers Series 9002

7/16 DIN Male Right Angle Connector Clamp/Solder Attachment for RG213, RG214, RG8, RG9, RG225, RG393, RG215

Micro-Change. Cordset Family

Relative and absolute pressure transmitter type 528

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version

Pressure transmitters MBS 4201, MBS 4251, MBS 4701 and MBS 4751

DMP 343. Industrial Pressure Transmitter. Without Media Isolation. appmeas.co.uk +44 (0)

Alphaline Temperature Transmitters

Binary Output without Power Supply Series 9176

Humidity Sensor/Transmitter Assembly

SMA Male Connector Crimp/Solder Attachment for RG174, RG316, RG188 Gold Plated

TNC Male Right Angle Connector Crimp/ Solder Attachment for RG174, RG316, RG188, inch, PE-B100, PE-C100, LMR-100

Piezotron Coupler. Electronics & Software. Acoustic Emission Coupler for Safe or Hazardous Locations ATEX/IEC/Ex and CSA. Type 5125C...

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters

Tru products are now under the Tru-Win brand from Winchester Interconnect.

Fisher 646 Electro Pneumatic Transducer

LTE high-performance coaxial cables (RG replacement)

RF Connectors Technical Data Sheet. Description Minimum Typical Maximum Units. Frequency Range DC 3 GHz VSWR 1.25:1 Operating Voltage (AC) 335 Vrms.

QN Male Connector Crimp/Solder Attachment for RG55, RG141, RG142, RG223, RG400

Industrial Ethernet OPT cable manufactured for Petrol Forecourt Applications.

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

SEM210 SERIES. Programmable In-head Universal Temperature Transmitter INDEX SECTION CONTENTS PAGE NO.

N Male Right Angle Connector Clamp/Solder Attachment For 1/2 inch Annular, 1/2 inch Flexible, PE-1/2FAC. Cable Attachment Method (Shield/Contact)

Precision Junction Boxes

LOW COST SDI 2210, 2260 & 2266 HIGH PERFORMANCE SDI 2220 & 2276

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

FLEX Ex Power Supplies

Kotron Model 82 CE RF Level Transmitter

RP TNC Male Connector Crimp/Solder Attachment for PE-C240, RG8X, inch, LMR-240, LMR-240-DB, LMR-240-UF, B7808A

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting

TEK-TEMP 2100A. Explosion-Proof Temperature Transmitter. TEMPERATURE. Technology Solutions

Instrumentation Cables

IPC 704. Signal conditioner FEATURES. For CA piezoelectric accelerometers and CP dynamic pressure transducers

TQ 402 & TQ 412 / EA 402 / Proximity System. 三協インタナショナル株式会社東京 :Tel: 大阪 :Tel: 名古屋 :Tel: FEATURES

SMB Plug Connector Crimp/Solder Attachment for RG174, RG316, RG188, LMR-100, PE-B100, PE-C100, inch

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

Field Instrument Cable. Electrical Noise

Two-channel safety barriers Series 9002

Transcription:

200200 protim-r Module Bently Nevada* Asset Condition Monitoring Description The 200200 dual-input protim-r (DIN rail mount) provides 2 channels of measurement. All acceleration-to-velocity (A-V) channels condition the signal from an accelerometer and integrate it to velocity units. The low frequency A-V channels are better suited for slower speed applications. A-V with Acceleration Enveloping (AE) channels provide both integrated velocity units and advanced AE signal conditioning. Temperature channel types include K-type thermocouples and 100Ω Platinum (Pt) RTDs with electrical isolation. Each channel is independent and specified when the protim is ordered. Table 1: protim Measurement Types and Transducers Measurement Type Interfaced Transducer Acceleration-to-Velocity (General Purpose) 200150 Low Frequency Acceleration-to-Velocity 200155 Acceleration-to-Velocity with AE 200157 K-type Thermocouple 200125* 2, 3, or 4 Wire Platinum RTD Industry standard* *The 200125 is the recommended Trendmaster * sensor for temperature measurements when the range of a K-type thermocouple is adequate. We do not recommend the use of other K-type thermocouples to the unique electrical isolation requirements of the Trendmaster system, and highly recommend the use of only non-grounded RTDs and non-grounded tip thermocouples to prevent ground loops. Failure to comply may result in Not OK or NO DATA conditions, inaccurate readings, or protim-r damage. Consult the factory for further information. Page 1 of 12

Specifications All specifications are at +25 ± 5 C (+77 ± 9 F) unless otherwise specified. Operation outside the specified limits will result in false or inaccurate readings. 200200 protim-r and 200150, 200155, 200157 or 200125 transducer systems For detailed specification on the transducers, refer to the individual transducer data sheets. Electrical: A V (General Purpose) Channels (with 200150) Measurement Range Over Range Resolution Accuracy Frequency Response Not OK Range 0 to 50 mm/s pk (0 to 2 in/s pk) 63 mm/s pk (2.5 in/s pk) 0.025 mm/s (0.001 in/s pk) nominal ± 15% at 80 Hz 10 Hz to 1 khz (600 cpm to 60,000 cpm) ± 20% (± 2 db) Accuracy Frequency Response Not OK Range ±15% at 80 Hz 3 Hz to 1 khz (180 cpm to 60,000 cpm) ± 10% (±0.9 db)* * The A-V circuitry attenuates frequencies above 1 khz. Use of the 200155 transducer to obtain higher frequency information will be ineffective. Open transducer signal, power, or common is Not OK. Shorted leads are Not OK except for SIG+ shorted to SIG- or common shorted to shield. Electrical: A V w/ AE Channels (with 200157) Measurement Range Over Range Resolution Accuracy 0 to 50 mm/s pk (0 to 2 in/s pk) 63 mm/s pk (2.5 in/s pk) 0.025 mm/s (0.001 in/s pk) nominal Open transducer signal, power, or common is Not OK. Shorted leads are Not OK except for SIG+ shorted to SIG- or common shorted to shield. Electrical: Low Frequency A V Channels (with 200155) Measurement Range Over Range Resolution 0 to 50 mm/s pk (0 to 2 in/s pk) 63 mm/s pk (2.5 in/s pk) 0.025 mm/s (0.001 in/s pk) nominal Frequency Response A-V AE ±15% at 80 Hz 10 Hz to 10 khz (600 cpm to 600,000 cpm) ± 20% (± 2.0 db)** 500 Hz to 10 khz (30,000 cpm to 600,000 cpm) ± 20% (±2.0 db)*** ** The A-V circuitry attenuates frequencies above 1 khz. Use of the 200157 transducer to obtain higher frequency information will be ineffective. AE signals up to 10kHz are processed at the protim. *** The 500 Hz filter has a 4-pole attenuation slope. Page 2 of 12

Not OK Range: Open transducer signal, power, or common is Not OK. Shorted leads are Not OK except for SIG+ shorted to SIG- or common shorted to shield. Electrical: Temperature Channels Measurement Range Resolution Accuracy K-Type TC RTD OK Range Not OK Condition RTD Compensation Coefficient Alpha in Ω/Ω/ C European US Industrial Software Compensation -18 C to +204 C (0 F to +400 F) 0.07 C (0.12 F) ±8 C (±14 F), including protim-r, thermocouple & lead wire error, maximum length of 6 meters. ±4.45 C (±8 F), RTD lead wire error not included -31 C to +213 C (-25 F to +415 F) Temperatures outside the OK Range Open RTD or thermocouple wires are "Not OK" 0.00385 0.00392 At host computer Environmental Limits Operating Temperature Storage Temperature Humidity Enclosure Type Mechanical Housing Material Weight Dimensions -40 C to +85 C (-40 F to +185 F) -40 C to +100 C (-40 F to +212 F) 100% non-condensing Note: Apply DC4 grease on connecter contacts to improve environmental performance and prevent corrosion. Type 4 Powder-coated Aluminum 545 g (19 oz) See diagram Compliance and Certifications EMC Standards: EN 61000-6-2 Immunity for Industrial Environments EN 55011 ISM Equipment European Community Directives: EMC Directive 2004/108EC For further declaration of conformance information please visit the following website: http://www.ge-energy.com/prod_serv/products/oc/en/bently_nevada.htm Hazardous Area Approvals CSA Installed with intrinsically safe zener Page 3 of 12

barriers per drawing 164160 Installed without barriers per drawing 164161 ATEX Approvals Installed with intrinsically safe zener barriers per drawing 164160 Installed without barriers per drawing 164161 Brazil Class I, Div 1 Groups A, B, C & D Class II, Div 1 Groups E, F & G Class III, Div 1 A/Ex ia IIC; Class I, Zone 0 T4 T4 @ -40 C Ta +100 C Class I, Div 2 Groups A, B, C & D T4 @ -40 C Ta +100 C A/Ex na IIC, Class I, Zone 2 T4 T4 @ -40 C Ta +100 C II 1 G EEx ia IIC T4 LCIE 03 ATEX 6459 X T4 @ -40 C Ta +100 C II 3 G EEx na II T4 LCIE 03 ATEX 6460 X T4 @ -40 C Ta +100 C BR-Ex ia IIC T4 MC, AEX-8307-X T4 @ -40 C Ta +100 C Intrinsically safe entity parameters Maximum Number of ProTIMs Per Line Power Supply Requirements Signal Terminals Field Wiring Parameters 32 (all gas groups) Ui 15V Ii 150 ma Ui 12V See Table 2. Ci 0 (negligible) Li 0 (negligible) Ii 12 ma Table 2: ProTIM-R Field Wiring Parameters Gas Group Capacitance (μf) Inductance (mh) L/R (μh/ohm) IIC 0.09 2 16 IIB 0.705 8 64 IIA 2.23 16 130 Non-incendive (Zone 2 or Div 2) entity parameters Power Supply Requirements Maximum cable Maximum Number of ProTIMs per Line Un = 12 V to 15 V (nominal) In = 50 ma (nominal) See Table 3. See Table 3. Page 4 of 12

Table 3: Maximum Cable Length and Number of ProTIMs per Line Gas Group Maximum Cable Length Maximum Number of ProTIMs per line IIC 1000 125 IIB 3599 127 IIA 4876 127 For further certification and approvals information please visit the following website: http://www.ge-energy.com/prod_serv/products/oc/en/bently_nevada.htm 200151 and 200152 Transducer Cables Used to connect the acceleration transducers to the protim-r. Operating Temperature Minimum Bend Radius Construction Connectors 200152 Cables 200151 Cables -20 C to +100 C (-4 F to +212 F). Note: These cables may be used at lower temperatures down to 40 C (-40 F), if the cable is not allowed to move or flex. Flexing these cables at temperatures below 20 C (-4 F) may damage them. 63.5 mm (2.5 in) 4-conductor (22 AWG) with foil shield and drain wire (100% coverage), polyvinyl chloride (PVC) outer jacket. PT06F8-4S (or equivalent) on the transducer end; stripped stranded wire at protim end. Connector coupling nut material is 1/2-20 2011 T3 aluminum or UNF-threaded nickel-plated brass. Connector contact material is gold-plated brass. Screw-on, 5-pin, keyed connector on the ProTIM-R end and a PT06F8-4S (or equivalent) on the transducer end. Connector coupling nuts consist of 1/2-20 Classifications: UNF-threaded 2011 T3 aluminum or UV-stabilized black nylon. Contact material is gold-plated nickel-coated brass. Cable assembly meets UL 2238. Cable meets IP67 ingress protection. 85033 Trendmaster SPA/TIM line cable Use to connect a SPA to the protim For substitutions, reference guide 101206. Operating Temperature Conductors Shielding Insulation Conductors Outer Classifications Voltage rating Capacitance Between Conductors -70 C to +200 C (-94 F to +392 F). 4x 18 AWG stranded, tinned copper 1x 18 AWG stranded copper, tinned overcoat uninsulated drain wire 100% aluminum mylar foil out with helically applied drain wire 85% braided tinned copper Fluoroethylene propylene (FEP) Teflon 0.25 mm (0.010 in) thick FEP Teflon 0.38 mm (0.015 in) thick NEC article 725 class 3 UL Listed 300 Vrms Page 5 of 12

Between Conductor and Drain Wire 131 pf/m (40 pf/ft) 262 pf/m (80 pf/ft) Ordering Information ProTIM-R 200200-AXX-BXX-CXX A: Channel A Input Option 0 1 Acceleration to Velocity (200150) 0 2 K-Type Thermocouple (200125) 0 3 2 or 3 Wire Pt. RTD 0 4 4 Wire Pt. RTD 0 5 Low Freq Accel-to-Velocity (200155) 0 6 Accel to Velocity w/ AE (200157) B: Channel B Input Option 0 1 Acceleration to Velocity (200150) 0 2 K-Type Thermocouple (200125) 0 3 2 or 3 Wire Pt. RTD 0 4 4 Wire Pt. RTD 0 5 Low Freq Accel-to-Velocity (200155) 0 6 Accel to Velocity w/ AE (200157) Note: BXX option availability is dependent on AXX options chosen. Not all BXX options are available with each AXX option. C: Approvals 0 0 CSA: Class 1 DIV 2, No Barriers ATEX: Zone 2, No Barriers 0 5 Multi Approvals Transducer Cable (for use with 200150, 100255, and 200 157 accelerometers) 200152-AXX-BXX A: Cable Length: B: Nut Option: 0 4 4.0 metre (13.1 feet) cable 1 5 15.0 metre (49.2 feet) cable 2 5 25.0 metre (82.0 feet) cable (for use with 200150 only) 0 0 Standard aluminum or brass coupling nut 1 0 Knurled aluminum or brass coupling nut Transducer Cable (for use with 200150, 200150, and 200157 accelerometers) 200151-AXX-BXX-CXX Note: Use the 200151 with the 200200 protim only with applications using either a 142485 Housing Cable Adapter or a 141887 Conduit Cable Adapter A: Cable Length: B: Armor Option: C: Nut Option: Accessories 163986-01 162411 149831-01 164045 164046 164352 00500128 04500006 2 0 2.0 metre (6.6 feet) cable 4 0 4.0 metre (13.1 feet) cable 6 0 6.0 metre (19.7 feet) cable 0 2 Standard cable, unarmored. 0 3 Stainless steel over braid (armored) cable 0 0 Standard aluminum coupling nut 0 2 Nylon coupling nut 1 0 Knurled aluminum coupling nut protim-r Installation Manual. Trendmaster System Manual. Trendmaster DSM Datasheet. Extra Female Terminal Plugs. For TIM line connections. Extra Male Terminal Plugs. For TIM line connections. T-Connector. For splitting TIM line cable into 2 directions. Terminal Connector. For Transducer inputs into protim-r. Dow Corning 4, Electrical Insulating Compound (5.3 Oz). Page 6 of 12

149326-01 85033-02-00 85033-01-00 02180005 200152 Accel Cable Environmental Boot Field Installation Kit. Contains everything needed to install the boot in the field. It includes 10 sets of boots and clamps, silicone lubricant, easy-to-use installation tool, and an instruction sheet. The kit is not compatible with armored cables and only compatible with older, plastic versions of accelerometers; not compatible with existing stainless steel accelerometers. 300 Meter (1000 ft) Cable. For TIM line. 150 Meter (500 ft) Cable. For TIM line. Jumper. For the RTD protim-r terminals. 88315-01 142485-01 141887-01 141887-02 03817040 03814237 03839129 maximum. See Error! Reference source not found.. 2-unit I.S. SST W/P Housing. Div 1, Type 4X. Houses 2 TIMs maximum. See Error! Reference source not found.. Housing Cable Adapter. See Figure 4. Single Conduit Cable Adapter. Double Conduit Cable Adapter. See Figure 5. Bonding and Ground Wedge. 1/2 NPT. Conduit Hub. 1/2-14 NPT. 85716-01 Conduit Fitting. 1/2-14 NPT. 85717-01 2-unit Polyester W/P Housing. Div 2, Type 4X. Houses 2 protim- R units maximum. See Figure 2. 03839240 Cable Seal. 1/4-12 NPT. Diameter 5.0 to 6.7 mm (0.20 to 0.26 in);. Use with 200152 cable. 88312-01 88313-01 4-unit Polyester W/P Housing. Div 2, Type 4X,. Houses 4 protim-r units maximum. See Figure 2. 4-unit I.S. Polyester W/P Housing. Div 1, Type 4X. Houses 4 protim-r units maximum. See Figure 2. 2-unit I.S. Polyester W/P Housing,. Div 1, Type 4X. Houses 2 protim-r units maximum. See Figure 2. 03839241 03839242 03839243 03880243 Cable Seal. 1/4-12 NPT. Diameter 1.9 to 3.4mm (0.07 to 0.13 in). Cable Seal. 1/4-12 NPT. Diameter 3.4 to 5.0 mm (0.13 to 0.20 in). Use with 200125 armored thermocouple. Cable Seal. 1/2-14 NPT. Diameter 6.4 to 7.9 mm (0.25 to 0.31 in). 88314-01 4-unit I.S. SST W/P Housing. Div1, Type 4X, Houses 4 TIMs Thread Seal. For 1/4-12 NPT fittings. Page 7 of 12

03840490 Square Cut O-ring. For 1/2-14 NPT fittings. Dimensional Diagram Note: All dimensions in millimetres (inches) except as noted. 85.0 (3.35) 1 P/N: 200200-XX-XX-XX S/N: XXXXXXXX PHY ADDR: XXXXMFG YR: XXXX 100.9 (3.97) 2 79.0 ( 3.11) 200200 Trendmaster protim-r 86.2 (3.39) 43.2 (1.70) 4 3 52.9 (2.08) 1. Top view 2. Side view 3. Side view #2 4. Powder coated aluminum housing Figure 1: protim Dimensional Diagram Page 8 of 12

1. Side view. See Table 4 for dimensions. 2. Top view. See Table 4 for dimensions. 3. If not using Quick Release, use 10-32 pan head screw (2 places). Figure 2: Polyester Housing Dimensions Table 4: ProTIM Enclosure Dimensions Part number Overall (L x W) Mounting (G x H) J K Q 85716-01 (2-position) 165 x 165 (6.50 x 6.50) 171 x 102 (6.75 x 4.00) 82.5 (3.25) 25.4 (1.00) 143 (5.64) 88313-01 (2 position) 165 x 165 (6.50 x 6.50) 171 x 102 (6.75 x 4.00) 82.5 (3.25) 25.4 (1.00) 143 (5.64) 85717-01 (4 position) 267 x 216 (10.50 x 8.50) 273 x 152 (10.75 x 6.00) 125 (4.94) 33.3 (1.31) 244 (9.61) 88312-01 (4 position) 267 x 216 (10.50 x 8.50) 273 x 152 (10.75 x 6.00) 125 (4.94) 33.3 (1.31) 244 (9.61) Page 9 of 12

1. Side view. See Table 5 for dimensions. 2. Top view. See Table 5 for dimensions. 3. 8 mm (0.31 in) diameter, 4 places Note: The number of clamps and the placement is shown for the large enclosure. The small enclosure has only one clamp, centered on the side opposite the hinge. Figure 3: Stainless Steel Housing Dimensions Table 5: Stainless Steel ProTIM Enclosure Dimensions Part number Overall (L x W) Mounting (G x H) Box Size (A x B x C) 85315-01 (2-position) 191 x 176 (7.50 x 6.94) 171 x 102 (6.75 x 4.00) 152 x 152 x 102 (6.00 x 6.00 x 4.00) 88314-01 (4 position) 292 x 227 (11.50 x 8.94) 273 x 152 (10.75 x 6.00) 254 x 203 x 152 (10.00 x 8.00 x 6.00) Page 10 of 12

1. Housing cable adapter, 142485-01 2. 200151 cable 3. Accel to Velocity protim-r 4. TIM housing 5. 200150 accelerometer 6. Machine casing Figure 4: Housing Cable Adapter Page 11 of 12

1. To SPA 2. TIM housing 3. Accel to Velocity protim-r 4. 200151 cable 5. 200150 accelerometer 6. Wiring in rigid conduit 7. 1-inch conduit body near machine 8. 141887-02 Conduit Cable Adapter Figure 5: Dual Conduit Cable Adapter * denotes trademarks of Bently Nevada, LLC, a wholly owned subsidiary of General Electric Company. Teflon is a trademark of E.I. du Pont de Nemours and Company. Dow Corning is a trademark of Dow Corning Corporation. 2003 2009 Bently Nevada LLC. All rights reserved. 1631 Bently Parkway South, Minden, Nevada USA 89423 Phone: 775.782.3611 Fax: 775.215.2873 www.ge-energy.com/bently Page 12 of 12