Stabilized Differential Relay SPAD 346. Product Guide

Similar documents
SPAD 346 C Stabilized differential relay

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

SPAD 346 C. Stabilized Differential Relay. User s manual and Technical description SPAD 346 C V ~ V. f n SPCD 3D53 SPCJ 4D28

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

SPAE 010, 011 High Impedance Protection Relay

SPAS 348 C. Feeder Protection Relay. User s manual and Technical description SPAS 348 C V ~ V. t 2 > [ s ] f n = 50Hz 60Hz

Harmonic restraint earth fault or single-phase overcurrent protection

SPAJ 110 C. Earth-fault relay SPAJ 110 C. User s manual and Technical description. U aux V ~ V f n. n ( I o>> SPCJ 1C8

SPAA 341 C. Feeder Protection Relay. User s manual and Technical description SPAA 341 C. U aux V ~ V. f n. t 2 > [ s ] 0 I 0 >> Trip

SPAA 120 C and SPAA 121 C Feeder protection relay

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

SPAJ 144 C. Combined overcurrent and earth-fault relay SPAJ 144 C. User s manual and Technical description A CBFP V ~ V.

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual

SPAJ 135 C. Combined overcurrent and earth-fault relay SPAJ 135 C. User s manual and Technical description. U aux V ~ V.

Transformer differential protection

Phase and neutral overcurrent protection

SPAF 340 C Frequency Relay

SPAJ 111 C. Sensitive earth-fault relay SPAJ 111 C. User s manual and Technical description. U aux V ~ V. f n. n ( I o>> SPCJ 1C7

Overcurrent Protection / 7SJ45

SPAC 335 C and SPAC 336 C Feeder terminals

Instantaneous Overcurrent Relay

)HDWXUHV Voltage restraint overcurrent stage with five different inverse or definite time characteristics

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK

Transformer protection IED RET 670

REF 610 Feeder Protection Relay. Technical Reference Manual

Time over/underfrequency relay with protection assemblies

PD300. Transformer, generator and motor protection Data sheet

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

Plug-in microprocessor controlled multifuncional relay with automatic shorting of c.t.

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

presentation contents application advantages

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

Differential Protection with REF 542plus Feeder Terminal

SPAS 120 C Directional earth-fault relay

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION

Time-overcurrent relays and protection assemblies

Current and voltage measuring relays RXIK 1, RXEEB 1 and RXIB 24

Protection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique

SPAC 320 C. Motor protection terminal. User s manual and Technical description SPAC 320 C. U aux V _ V _ I >> / I.

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

SPAJ 160 C. Capacitor protection relay SPAJ 160 C. User s manual and Technical description V ~ V 3I > 3I < f n 2 > TRIP.

IRI1-ER - Stabilized Earth Fault Current Relay

Multimeter 500CVD21 RTU500 series

Type CP-S, CP-C & CP-A Switch mode

User s manual and Technical description. Self-Powered Feeder Protection REJ603

SFIBER Fibre-optic Option Card for Lon Star Coupler RER 111. Technical Reference Manual

Compact current relay and protection assemblies RXHL 401 and RAHL 401

TD 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

Time relay RXKA 1. (xx jpg) RXKA 1

SPECIFICATION FOR OVERCURRENT RELAYS

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

IRI1-ER - Stabilized Earth Fault Current Relay. Manual IRI1-ER (Revision A)

BUS2000 Busbar Differential Protection System

ASHIDA Numerical 3OC + 1EF Protection Relay

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

Earth fault protection for isolated neutral systems with frequency converters

4Q POWER AMPLIFIERS AC AND DC 3000VA 3x3000VA

Fixed Series Compensation

Modular multifunction generator protection

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

POWER AMPLIFIERS 4 QUADRANTS 3x500 VA to 3x1500 VA - THREE-PHASES

MHCO MHCO-RI. General Characteristics The transducer MHCO provide a measurement of current or voltage fully isolated and safe.

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

DIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges)

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd.

Reyrolle Protection Devices. 7SG14 Duobias M Transformer Protection. Answers for energy

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Type: ADR233A (ADITYA V2 Series) (Preliminary) ASHIDA Numerical 3 Phase Tx. Differential Protection Relay

XD1-T Transformer differential protection relay. Manual XD1-T (Revision A)

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

Three-phase monitoring relays

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

Thermistor motor protection relays

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

XP2-R Power and Reverse Power Relay

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

3 Pole high impedance differential relay 7VH83

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

PS-3000-AVAS PS-5000-AVAS DC SOURCE FOR AUTOMOTIVE TESTS

Transformer Fault Categories

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

1 INTRODUCTION ORDER CODE / INFORMATION

T 1000 PLUS Secondary Injection Relay Test Set

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

XD1-T - Transformer differential protection relay

DRTS 66 The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

Transcription:

Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault relay Alarm channels activated by normally open or normally closed contact Stabilized differential relay module providing winding short-circuit and interturn fault protection for two-winding power transformers and generator-transformer units, and interwinding short-circuit protection for generators Earth-fault relay module providing protection for transformer HV and LV side according to the principle selected: stabilized differential current principle, high-impedance principle, residual current principle or neutral current principle Three-stage overcurrent module providing protection for power transformers and generators and two-stage back-up earth-fault protection Short operate time even at partial saturation of the current transformers Operation characteristic of differential relay module easily adapted for different applications Stabilized against unwanted operations at faults occurring outside the protected area and at transformer inrush currents Second harmonic restraint for prevention of unwanted relay operations at transformer inrush currents Fifth harmonic restraint for prevention of unwanted relay operations at transformer overexcitation. The fifth harmonic restraint can be aborted if the ratio of the fifth harmonic and the basic frequency component rises too high at dangerous overvoltages Wide CT ratio correction range: accurate correction through digital setting No interposing current transformers needed for the protection of two-winding power transformers: numerical vector group matching on HV and LV side Four heavy-duty output relays for circuit breaker tripping and five output relays for signalling Five programmable external control inputs intended for alarm and trip signals from gas relays, oil temperature sensors and other sensors of transformer auxiliary devices Integrated circuit-breaker failure protection with adjustable operate time Differential relay and earth-fault relay modules provided with integrated disturbance recorder functions for analog and digital signals: signals to be used for triggering selectable Sensitive phase current and phase angle displays facilitate checking of energizing circuit connections and vector group matchings High immunity to electrical and electromagnetic interference allows the relay to be used in severe environments High availability and system reliability due to continuous supervision of hardware and software Powerful software supports relay parameterization and reading of measured and recorded values and event data Member of the SPACOM product family and ABB s Distribution Automation system CE marking according to the EC directive for EMC Application The stabilized differential relay C is designed for protecting two-winding power transformers and generator-transformer units against winding short-circuit, interturn fault, earth fault and short circuit, and generators and motors against interwinding faults and pole short circuit. In addition, the relay can be used for the protection of three-winding power transformers, provided 75% of the short circuit power to the power transformer is supplied from the same direction, and for the protection of compensating chokes and short cable lines. No interposing transformers are needed for the protection of two-winding power transformers, as the relay allows the vector group matching, the elimination of the zerosequence component of the phase currents and the CT ratio corrections to be carried out numerically. 3

Design The feeder protection relay is provided with six energizing inputs for phase currents and inputs for residual or neutral currents. The relay is also equipped with nine output relays for CB control, signalling, etc. The differential relay consists of three protection relay modules, i.e. a differential relay module, an earth-fault relay module and a combined overcurrent and earth-fault relay module. The modules are withdrawable as are the power supply module and the I/O relay module located behind the system front panel. Differential relay module SPCD 3D53 The differential relay module includes three protection units, i.e. a stabilized differential current unit, an instantaneous differential current unit and a circuit-breaker failure protection unit. In addition, the module contains a disturbance recorder unit. The stabilized differential current unit constitutes the main differential protection. The unit is provided with second and third harmonic restraint, selectable transformer vector group, zero-sequence current elimination, numerical correction of CT ratios and flexible configuration of tripping, blocking and control signals. The instantaneous, non-stabilized differential current unit functions as an ultra-fast protection unit with an operate time less than 30 ms at heavy faults. The circuit-breaker failure protection unit is activated by the main trip signal of the other protection units and it provides a second trip signal to be routed to a back-up circuit breaker if the main CB fails to operate. The differential relay module also incorporates a digital disturbance recorder module. The module continuously monitors the object protected and stores pre- and post-fault network information, which can be used for post-fault analysis. Earth-fault relay module SPCD 2D55 The earth-fault relay module measures the neutral current and/or residual current on both sides of the object protected. The earth-fault protection can be implemented by four different principles, i.e. the high-impedance principle, the numerical stabilized differential current principle, the residual overcurrent principle or the neutral overcurrent principle. Both sides of the object can be protected independent of each other, which means that the protection principle on one side does not have to be the same as that of the other side. The circuit-breaker failure protection unit is activated by the main trip signal of the protection units and it provides a second trip signal to be routed to a back-up circuit breaker if the main CB fails to operate. The earth-fault relay module also incorporates a digital disturbance recorder module. The module continuously monitors the object protected and stores pre- and post-fault network information, which can be used for post-fault analysis. Combined overcurrent and earth-fault relay module SPCJ 4D28 The combined overcurrent and earth-fault module includes four protection units, i.e. an overcurrent unit, an earth-fault unit, a phase discontinuity unit and a circuit-breaker failure protection unit. The three-phase overcurrent unit comprises three overcurrent stages, i.e. a low-set stage I>, a high-set stage I>> and a super high-set stage I>>>. The low-set stage can be given definite time characteristic or inverse time characteristic while the high-set stage and the super high-set stage have a definite time characteristic. The non-directional earth-fault unit comprises two protection stages, i.e. a low-set stage I 0 > and a high-set stage I 0 >>. The lowset stage can be given definite time characteristic or inverse time characteristic while the high-set stage has a definite time characteristic. The phase discontinuity protection unit measures the phase unbalance and has a definite time characteristic. The circuit-breaker failure protection unit is activated by the main trip signal of the protection units and it provides a second trip signal to be routed to a back-up circuit breaker if the main CB fails to operate. 4

Design (cont d) Data communication The feeder protection relay is equipped with a serial communication port on the rear panel. The serial port is used for connecting the relay to the SPA bus via an optional bus connection module. Two bus connection module types are available: SPA-ZC 17 and SPA- ZC 21. The former can be powered from the host relay and from a separate power source at the same time, while the latter is powered from the host relay via the D-type connector. Output relays and circuit breaker control The feeder protection relay is provided with nine output auxiliary relays, four of which are heavy-duty output relays for the direct control of the circuit breaker. Single-pole or doublepole circuit breaker control can be used. One of the five signalling relays is permanently allocated for the self-supervision system. The function of the other four relays can be defined by the user. Self-supervision The relay incorporates a sophisticated selfsupervision system with auto-diagnosis, which increases the availability of the relay and the reliability of the system. The selfsupervision system continuously monitors the hardware and the software of the relay. The system also supervises the operation of the auxiliary supply module and the voltages generated by the module. Auxiliary supply voltage The auxiliary supply of the relay is obtained from an internal plug-in type power supply module. Two auxiliary power module versions are available: type SPGU 240A1 for the supply voltage range 80 265 V ac/dc and type SPGU 48B2 for the supply voltage range 18 80 V dc. The power supply module forms the internal voltages required by the protection relay and the I/O module. 5

Technical data Table 1: Energizing inputs Terminals X0/1-3, 4-6, 7-9, X0/13-15, 16-18, X0/19-21, 25-27 X0/37-39 X0/1-2, 4-5, 7-8, X0/13-14, 16-17, X0/19-20, 25-26, X0/37-38 Rated current I n 1 A 5 A Thermal current continuously 4 A 20 A withstand for 10 s 25 A 100 A for 1 s 100 A 500 A Dynamic current Half-wave value 250 A 1250 A withstand Input impedance <100 mω <20 mω Rated frequency f n, according to order 50 Hz or 60 Hz Table 2: Output contact ratings Type of contact Tripping Signalling Terminals X1/11-12-13-14 X1/15-16-17-18 X2/3-4, 5-6 X2/7-8, 9-10 X2/11-12-13 X2/14-15 X2/16-17-18 Rated voltage 250 V ac/dc Thermal withstand Carry continuously 5 A 5 A capability Make and carry for 0.5 s 30 A 10 A Make and carry for 3 s 15 A 8 A Breaking capacity for dc, 220 V dc 1 A 0.15 A when the signal circuit 110 V dc 3 A 0.25 A time constant L/R 40 ms, at the signalling voltage levels 48 V dc 5 A 1 A Table 3: External control inputs Terminals X1/1-2, 3-4, 5-6, 7-8, 9-10 Control voltage Operative range 18 265 V dc or 80 265 V ac Current drain of activated control input 2 20 ma Active state of input Input active when energized Input active when non-energized Table 4: Auxiliary supply modules Terminal numbers X2/1-2 Type of module Rated voltages U n SPGU 240A1 110/120/230/240 V ac 110/125/220 V dc SPGU 48B2 24/48/60 V ac Operative range SPGU 240A1 80 265 V ac/dc SPGU 48B2 18 80 V dc Power consumption under quiescent ~10 W conditions under operating conditions ~15 W 6

Technical data (cont d) Table 5: Stabilized differential relay module SPCD 3D53 Selectable rated frequency f n CT ratio correction range on power transformer HV side I 1 /I n CT ratio correction range on power transformer LV side I 2 /I n Stabilized differential current stage 3 I> Basic start ratio P/I n Starting ratio setting S Second turning point I 2tp /I n of characteristic curve Harmonics blocking ratio I d2f /I d1f Harmonics blocking ratio I d5f /I d1f Harmonics deblocking ratio I d5f /I d1f Operate time (including heavy-duty output relays at currents 1.5 4 operate value Operation accuracy Instantaneous differential current stage 3 I>> at currents above 4 operate value 16 2 / 3 60 Hz 10 50% 1.0 3.0 7 20% 10 50% 10 50% <50 ms <45 ms ±4% of set value or ±2% I n Start ratio I d /I n >> 5 30 Operate time (including heavy-duty output relays at ratios in the range of <35 ms 1.1 2.6 I d /I n >> at ratios above 2.6 <30 ms I d /I n >> Operation accuracy ±4% of set value of 2% I n Circuit-breaker failure protection Operate time 0.1 1.0 s Integrated disturbance recorder Recording length 38 cycles Recording memory capacity 1 recording = 38 cycles Sampling frequency 40 samples/cycle Signals to be recorded 6 analog signals 11 digital signals Triggering when the selected digital is activated signal when the selected digital resets signal Length of recording preceding triggering 0 38 cycles Table 6: Earth-fault relay module SPCD 2D55 Selectable rated frequency f n Stabilized differential relay principle Basic start ratio on HV side P 1 /I n Operate time on HV side t 01 > Basic start ratio on LV side P 2 /I n Operate time setting on LV side t 02 > Correction range of HV side neutral connection CT ratio I 01 /I n Setting of minimum ratio of HV side neutral current and residual current of phase currents I 01 / I 1 Correction range of LV side neutral connection CT ratio I 02 /I n Setting of minimum ratio of LV side neutral current and residual current of phase currents I 02 / I 2 Second harmonics restraint ratio I 2f /I 1f of HV side neutral current I 01 Second harmonics restraint ratio I 2f /I 1f of LV side neutral current I 02 Correction range of HV side phase CT ratio I 1 /I n Correction range of HV side phase CT ratio I 2 /I n Operate time at minimum delay (including heavy-duty output relays) 16 2 / 3 60 Hz 0.03 100 s 0.03 100 s 0 20% 0 20% 10 50% 10 50% 30 40 ms 7

Technical data (cont d) Table 6: Earth-fault relay module SPCD 2D55 Operation accuracy Principle based on calculated residual current Basic start ratio P 1 /I n on HV side Operate time t 01 > on HV side Basic start ratio P 2 /I n on LV side Operate time setting t 02 > on LV side Correction range of HV side phase CT ratio I 1 /I n Correction range of HV side phase CT ratio I 2 /I n Operate time at minimum delay (including heavy-duty output relays) Operation accuracy Principle based on measured residual current or neutral current Basic start ratio P 1 /I n on HV side Operate time t 01 > on HV side Basic start ratio P 2 /I n on LV side Operate time setting t 02 > on LV side Correction range of HV side neutral connection CT ratio I 01 /I n Correction range of LV side neutral connection CT ratio I 02 /I n Second harmonics restraint ratio I 2f /I 1f of HV side neutral current I 01 Second harmonics restraint ratio I 2f /I 1f of LV side neutral current I 02 Operate time at minimum delay (including heavy-duty output relays) Operation accuracy Restricted earth-fault principle (high-impedance type earth-fault protection) Basic start ratio P 1 /I n on HV side Operate time t 01 > on HV side Basic start ratio P 2 /I n on LV side Operate time setting t 02 > on LV side Correction range of HV side neutral connection CT ratio I 01 /I n Correction range of LV side neutral connection CT ratio I 02 /I n Operate time at minimum delay (including heavy-duty output relays) Operation accuracy Circuit-breaker failure protection Operate time Integrated disturbance recorder Recording length Recording memory capacity Sampling frequency Signals to be recorded Triggering Length of recording preceding triggering when the selected digital signal when the selected digital signal ±4% of set value or ±2% of I n 0.03 100 s 0.03 100 s 30 40 ms ±4% of set value or ±2% of I n 0.03 100 s 0.03 100 s 10 50% 10 50% 30 40 ms ±4% of set value or ±2% of I n 0.03 100 s 0.03 100 s 30 40 ms ±4% of set value or ±2% of I n 0.1 1.0 s 30 cycles 1 recording = 30 cycles 40 samples/cycle 8 analog signals 12 digital signals is activated resets 0 30 cycles 8

Technical data (cont d) Table 7: Relay module SPCJ 4D28, overcurrent unit Features Stage I> Stage I>> Stage I>>> Start current at definite time 0.5 5.0 I n 0.5 40.0 I n and 0.5 40.0 I n and at inverse time 0.5 2.5 I n Start time, typically 70 ms 40 ms 40 ms Operate time at definite time 0.05 300 s 0.04 300 s 0.04 30 s characteristic Time/current characteristic at inverse Extremely inverse time mode Very inverse Normal inverse Long-time inverse RI type inverse RXIDG type inverse Time multiplier k 0.05 1.0 Reset time, typically 40 ms 40 ms 40 ms Retardation time <30 ms Reset ratio, typically 0.96 Operate time accuracy at definite time ±2% of set value or ±25 ms mode Accuracy class index E at inverse time 5 mode Operation accuracy ±3% of set value ±3% of set value ±3% of set value Table 8: Relay module SPCJ 4D28, earth-fault and phase discontinuity unit Features Stage I 0 > Stage I 0 >> Stage I> Start current 0.1 0.8 I n 0.1 10.0 I n and 10 100% and Start time, typically 70 ms 50 ms 150 ms Operate time at definite time 0.05 300 s 0.05 300 s 1 300 s characteristic Time/current characteristic at inverse Extremely inverse time mode Very inverse Normal inverse Long-time inverse RI type inverse RXIDG type inverse Time multiplier k 0.05 1.0 Reset time, typically 40 ms 40 ms 80 ms Retardation time <30 ms <30 ms Reset ratio, typically 0.96 0.96 0.90 Operate time accuracy at definite time ±2% of set value or ±25 ms mode Accuracy class index E at inverse time 5 mode Operation accuracy ±3% of set value ±3% of set value ±1 unit ±3% of set value 9

Technical data (cont d) Table 9: Data communication Transmission mode Data code Data transfer rate, selectable Electrical/optical bus connection module powered from the host relay Electrical/optical bus connection module powered from the host relay or from an external power source Table 10: Tests and standards for plastic core cables for glass fibre cables for plastic core cables for glass fibre cables Fibre-optic serial bus ASCII 4800 or 9600 Bd SPA-ZC 21BB SPA-ZC 21MM SPA-ZC 17BB SPA-ZC 17MM Test voltages Dielectric test voltage (IEC 60255-5) 2 kv, 50 Hz, 1 min Interference tests Impulse test voltage (IEC 60255-5) Insulation resistance (IEC 60255-5) High frequency disturbance test (IEC 60255-22-1), common mode High frequency disturbance test (IEC 60255-22-1), differential mode 5 kv, 1.2/50 µs, 0.5 J >100 MΩ, 500 V dc 2.5 kv, 1 MHz 1.0 kv, 1 MHz Electrostatic discharge (IEC 60255-22-2 8 kv and IEC 61000-4-2), air discharge Electrostatic discharge (IEC 60255-22-2 6 kv and IEC 61000-4-2), contact discharge Fast transients (IEC 60255-22-4 and 4 kv IEC 61000-4-4), power supply inputs Fast transients (IEC 60255-22-4 and 2 kv IEC 61000-4-4), other inputs Environmental conditions Service temperature range -10 +55 C Long term damp heat withstand <95%, +40 C, 56 d/a (IEC 60068-2-3) Temperature influence 0.1%/ C Damp heat test (IEC 60068-2-30) 93 95%, +55 C, 6 cycles Transport and storage temperature range -40 +70 C (IEC 60068-2-8) Degree of protection by enclosure of flush IP 54 mounting relay case (IEC 60529) Weight of fully equipped relay ~6 kg 10

Block diagram Fig. 1 Block diagram and sample connection diagram BSPAD346 11

Mounting and dimensions Flush mounting 226 30 293 259 229 34 214 ±1 162 136 139 ±1 Panel cut-out dim300 Fig. 2 Flush-mounting relay case (dimensions in mm) Semi-flush mounting a b Raising frame SPA-ZX 301 SPA-ZX 302 SPA-ZX 303 a 219 179 139 b 74 114 154 SFM300_1 Fig. 3 Semi-flush mounting relay case (dimensions in mm) Mounting in 19 inch cabinets and frames An ancillary mounting plate, height 4U (~177 mm), is recommended to be used when the protection relays are to be mounted in 19 inch frames or cabinets. The ancillary mounting plate type SPA-ZX 304 accommodates two size 300 relays and type SPA-ZX 305 one size 300 relay. Projecting mounting When projecting mounting is preferred, a relay case type SPA-ZX 317 is used. The relay case for projecting mounting is provided with front connectors. SPA-ZX304 SPA-ZX305 SPA-ZX201 SPA-ZX306 SPA-ZX307 SPA-ZX317 SPA-ZX318 +0,4 482,6 0 (19") 242 197 ø6 306 312 292 6 197 98 21,5 101,6 7 +0,4 177 0 (4U) 304_5_6 Fig. 4 Mounting cabinets and frames as well as projecting mounting (dimensions in mm) 12

Ordering When ordering, please specify: Ordering information Ordering example 1. Type designation and quantity C, 5 pieces 2. Order number RS 621 002-AA 3. Rated values I n =5 A, f n =50 Hz 4. Auxiliary voltage U aux =110 V dc 5. Accessories - 6. Special requirements - Order numbers Stabilized differential relay C_ C complete C1, incl. modules SPCD 3D53 and SPCD 2D55 C2, incl. modules SPCD 3D53 and SPCJ 4D28 C3, incl. module SPCD 3D53 C4, incl. modules SPCD 2D55 and SPCJ 4D28 C5, incl. module SPCD 2D55 C6, incl. module SPCJ 4D28 The last two letters of the order number indicate the rated frequency f n and the auxiliary voltage U aux of the relay as follows: RS 621 002-AA, CA, DA, FA RS 621 003-AA, CA, DA, FA RS 621 004-AA, CA, DA, FA RS 621 005-AA, CA, DA, FA RS 621 006-AA, CA, DA, FA RS 621 007-AA, CA, DA, FA RS 621 008-AA, CA, DA, FA AA equals f n = 50 Hz and U aux = 80 265 V ac/dc CA equals f n = 50 Hz and U aux = 18 80 V dc DA equals f n = 60 Hz and U aux = 80 265 V ac/dc FA equals f n = 60 Hz and U aux = 18 80 V dc Stabilized differential relay C_ including a test adapter type RTXP18 C complete RS 621 202-AA, CA, DA, FA C1, incl. modules SPCD 3D53 and RS 621 203-AA, CA, DA, FA SPCD 2D55 C2, incl. modules SPCD 3D53 and RS 621 204-AA, CA, DA, FA SPCJ 4D28 C3, incl. module SPCD 3D53 RS 621 205-AA, CA, DA, FA C4, incl. modules SPCD 2D55 and RS 621 206-AA, CA, DA, FA SPCJ 4D28 C5, incl. module SPCD 2D55 RS 621 207-AA, CA, DA, FA C6, incl. module SPCJ 4D28 RS 621 208-AA, CA, DA, FA The last two letters of the order number indicate the AA equals f n = 50 Hz and U aux = 80 265 V ac/dc rated frequency f n and the auxiliary voltage U aux of CA equals f n = 50 Hz and U aux = 18 80 V dc the relay as follows: DA equals f n = 60 Hz and U aux = 80 265 V ac/dc FA equals f n = 60 Hz and U aux = 18 80 V dc References Additional information User s manual and technical description Stabilized differential relay C 1MRS 750096-MUM EN 13

Copyright 2010 ABB. All rights reserved / D ABB Oy, Distribution Automation P.O.Box 699 FIN-65101 VAASA Finland Tel: +358 10 22 11 Fax: +358 10 22 41094 www.abb.com/substationautomation ABB Limited, Distribution Automation Maneja, Vadodara - 390013, India Tel: +91 265 260 4386 Fax: +91 265 263 8922 www.abb.com/substationautomation