EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA

Similar documents
Industrial and Commercial Power Systems Topic 7 EARTHING

The Lightning Event. White Paper

Grounding for Power Quality

Importance of Grounding in Power System. Presented by Mr. H Jayakumar Ex- Joint Director CPRI

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor

Earthing of Electrical Devices and Safety

The Role of the Grounding System in Electronics Lightning Protection

Practical Lightning Mitigation

ABSTRACTS of SESSION 6

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Principle & operating. Lightning conductor with excitation device In compliance with the NFC standard Franklin France Patent

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

Transmission of Electrical Energy

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Investigation on the Performance of Different Lightning Protection System Designs

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

National Radio Astronomy Observatory Socorro, NM EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable. T. Baldwin June 05, 2002

Minimizing Lightning and Static Discharge in Broadcasting

LIGHTNING PROTECTION for RADIO COMMUNICATION SITES

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU

Grounding. Review of Grounding Considerations and Options. Rick Fletcher, W7YP. FVARC November 22, 2017

Lightning Strikes. Presented to the Greater Norwalk Amateur Radio Corporation Inc. February 8, 2017 Steven M. Simons W1SMS

University of Zagreb Faculty of Electrical Engineering and Computing

Outdoor Installation 2: Lightning Protection and Grounding

ABSTRACT 1 INTRODUCTION

Grounding and Lightning arrestors

Lightning transient analysis in wind turbine blades

Analysis of lightning performance of 132KV transmission line by application of surge arresters

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

7P Series - Surge Protection Device (SPD) Features 7P P P

Protection of photovoltaic systems against lightning

6. Internal lightning protection

New Release - Latest Technology

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

INTERNATIONAL STANDARD

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse

Lightning Protection. Wisconsin Broadcasters Association Broadcasters Clinic. 14 th October 2009 Jeff Welton Regional Sales Manager, Central U.S.

Grounding Strategies for Solar PV Panels

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

Evaluation of Soil Resistivity Characteristics forsubstation Grounding: a Case Study of a University Campus in South-West Zone, Nigeria

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD GROUNDING RESISTANCE MEASUREMENTS AND IMPROVEMENT

Lightning Protection: History and Modern Approaches

Tested in accordance IEC Std: 60-1: 1989

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

Tower and Station Grounding

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

Specialists in HV and MV test and diagnostics. Testing in Substations

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE

Triggered-Lightning Testing of the Protective System of a Residential Building: 2004 and 2005 Results

Electrical Measurement Safety. Sponsored By:

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

High-Voltage Test Techniques

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

INFORMATION AND CONSULTATION

American Electrical Institute

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Options to Improve the MEN System into the 21 st Century

Testing 320 kv HVDC XLPE Cable System

SCIENCE & TECHNOLOGY

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Article 250 Grounding & Bonding

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

RADIO AND TELEVISION SATELLITE EQUIPMENT

AC Voltage- Pipeline Safety and Corrosion MEA 2015

Insulation Test System

Modeling insulation in high-voltage substations

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

EPR Safety Mat Modelling & Field Testing Summary Report

Air Terminal. transmitter

Analysis of Response of a Guyed FM Radio Broadcasting Tower Subjected to a Lightning Strike

IMP/007/011 - Code of Practice for the Application of Lightning Protection

Lightning Protection for Cellular Tower Mounted Electronics

2007 DEHN + SÖHNE / protected by ISO EXFS / 5392

HIGH VOLTAGE Insulation Coordination

High Voltage Pylon Earth Measurements

Protection against unacceptable voltages in railway systems

Earthing of Low Voltage Electrical Systems: Personnel Protection Equipment Protection

Underground System Design TADP 547

Effective Elimination Factors to the Generated Lightning Flashover in High Voltage Transmission Network

GROUNDING OF CONTROL CABLE SHIELDS: DO WE HAVE A SOLUTION?

Cisco Aironet 13.5-dBi Yagi Mast Mount Antenna (AIR-ANT1949)

LIGHTNING PROTECTION FOR MONITORING FACILITIES INTRODUCTION

Stake-less earth / ground testing

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Attendee Announcements

ATP SIMULATION OF FARADAY CAGE FOR THE ANALYSIS OF LIGHTNING SURGES

Technical Requirements for Resistibility of Telecommunications Equipment to. Overvoltage and Overcurrent

Electromagnetic and Radio Frequency Interference (EMI/RFI) Considerations For Nuclear Power Plant Upgrades

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

DEPARTMENT OF EEE QUESTION BANK

Earth Mat Design for a 66kv Substation

STATIC ELECTRICITY & ANTISTATIC FLOORING EXPLAINED Test Methods, Flooring Classification & More.

The Simulation Experiments on Impulse Characteristics of Tower Grounding Devices in Layered Soil

Transcription:

EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA Rajat Verma Project Engineer BHEL EDN, BANGALURU, MYSORE ROAD, KARNATAKA 560024, India ABSTRACT The earth is the most ubiquitous conductive surface, and so it was assumed in the very beginnings of electrical transmission and distribution systems as a nearly universal standard for all electric systems. As the construction of the solar power plants has been initiated by the power developers in India since 2011[1]. The safety parameters of the equipment and manpower have become the most prominent issue for all against lightning strokes. Conventional earthing always played a vital role in avoiding all hazardous incidents. This paper theoretically analyzes the resistance value for the earth pits with the respective techniques which adequately meet with the earth resistance benchmark as per the international standards followed by the world. The Early Streamer Emission Lightning Arrestor (ESELA) is the most recognizable technique for the earthing system, which protects structures such as Inverter Rooms, Control Rooms, Module Mounting Structures or any other installed equipment from damage by intercepting flashes of lightning and transmitting their current to the ground. Keywords: Earth Resistance Value; ESE LA; 1. Introduction Lightning is one of nature's most vigorous and calamitous incidents. Lightning discharges contain astounding amounts of electrical energy and have been measured from several thousand amps to over 200,000 amps - enough to light half a million 100 watt bulbs. Even though a lightning discharge is of a very short duration (typically 200 microseconds) and it is a very real cause of JETIR1612017 Journal of Emerging Technologies and Innovative Research (JETIR) www.jetir.org 120

damage and destruction. The effects of a direct strike are obvious and immediately apparent - buildings damaged, trees blown apart, personal injuries and even death. A reliable lightning protection scheme must encompass both structural lightning protection and transient overvoltage (electric systems) protection [2] The theory of early streamer emission proposes that if a lightning rod has a mechanism producing ionization near its tip, then its lightning capture area is greatly increased [3]. When the voltage between the cloud and the ground increases until an ionized path is created emanating from the cloud. That ionized path travels in leaps towards the earth. The extremity of the leader has the same potential as the cloud. As the leader nears the earth, the atmospheric potential increases above the ground and the air terminal is electrically charged. When the extremity of the leader arrives at a critical position, the ESE air terminal reaches its maximum electrical charge, and the streamer emission of the accumulated current is produced on its extremity which ionizes the air around the summit. The electrical arc, generated at the tip of the ESE air terminal, provokes a streamer emission which rises toward the leader more quickly than on a simple rod (it is the early streamer emission). The link between the earth and the cloud is formed and the lightning current passes along the ionized path. Several electrical discharges can rapidly follow the first one. The voltages between the cloud and ground are equalized and electrical discharges cease [4]. Following standards are applicable for the earth resistance value of ESE type Lightning Arrestor: 1. As per the India Standard code of practice for earthing, the value of the earth resistance as using a common earth where the earth electrode resistance, including the parallel resistance of any bonded metalwork, etc, to earth is 1 Ω or less, as is usual at power stations, large outdoor substations or substations supplying a network of cables whose sheaths have a low impedance to earth [5]. This standard has been followed at all the solar plant in India, but this precise value sometimes does not observe exactly through earth resistance tester after completion of the JETIR1612017 Journal of Emerging Technologies and Innovative Research (JETIR) www.jetir.org 121

earthing works at the premises. Henceforth, there are other standards which can be followed for the authentication of earthing values at respective plants. 2. As per the IEEE Guide for Safety in AC Substation Grounding - IEEE Std 80-2000 (Revision of IEEE Std 80-1986), the evaluation of ground resistance for the most transmission and other large substations, the ground resistance is usually about 1 Ω or less. In smaller distribution substations, the usually acceptable range is from 1Ωto 5Ω, depending on the local conditions. The solar plants are mostly designed and interconnected at 33 kv voltage levels which come under smaller distribution substations. 3. Also, as per IEC 62305-1, edition 2.0 2010-12, the conventional earthing impedance related to the earth termination system is 04 Ω for the soil resistivity less than or equal to 100 Ωm as shown in Table 1.1 Table 1.1 Conventional earthing impedance values Z and Z1 according to the resistivity of the soil ρ Z1* Conventional earthing impedance related to the type of LPS** Ωm Ω Z ***Ω I II III - IV 100 8 4 4 4 200 11 6 6 6 500 16 10 10 10 1000 22 10 15 20 2000 28 10 15 40 3000 35 10 15 60 NOTE Values reported in this table refer to the conventional earthing impedance of a buried conductor under impulse condition (10/350µs). JETIR1612017 Journal of Emerging Technologies and Innovative Research (JETIR) www.jetir.org 122

* Values referred to external parts length over 100 m. For length of external parts lower than 100 m in high resistivity soil (>500Ωm) values of Z1 could be doubled. ** Lightning protection earthing system complying with 5.4 of IEC 62305-3:2010. ***The conventional earthing impedance of the earth termination system. For the purpose of IEC 62305, four lightning protection levels (I to IV) are introduced. For each LPL, a set of maximum and minimum lightning current parameters is fixed. 4. The NFC 17-102, July 1995 states that the resistance value measured using conventional equipment should be 10 ohms or less. This resistance should be measured on the earthing termination insulated from any other conductive component. Nomenclature ESE Early Streamer Emission IEEE Institute of Electrical and Electronics Engineers IEC NFC LA GI LPS 2. Structure International Electro technical Commission International French Standard Lightning Arrestor Galvanized Iron Lightning Protection System A 07 meters GI mast pipe in three equivalent lengths is joined on which ESE type LA assembly is mounted. This singular pipe length is supported by three guy wires tied at three anchors grouted in the ground. The ESE LA assembly is connected with the Copper strip (25 X 3 mm) for transmitting the lightning stroke to the ground directly. This copper strip is connected to the tripod earthing arrangement as shown in Fig.1. JETIR1612017 Journal of Emerging Technologies and Innovative Research (JETIR) www.jetir.org 123

This tripod earthing arrangement consists of three Cu cladded (250 microns) MS rod (2 meters) which are externally interconnected with the copper strip joining ESE LA assembly, an earthing chemical compound is also poured in it to reduce the earth resistivity as shown in Fig.2 Fig-1 Fig-2 JETIR1612017 Journal of Emerging Technologies and Innovative Research (JETIR) www.jetir.org 124

Conclusion The following above mentioned standards elaborated above help us out in the approval of the mentioned ESE type LA technique as per the standards. These standard guidelines will make the Indian Solar Plant execution and completion faster than the previous time period since 2011. References [1] https://en.wikipedia.org/wiki/solar_power_in_india. [2] http://new.abb.com/low-voltage/products/earthing-lightningprotection /furse/tools/why-do-we-need-lightning-protection. [3] B. Charpentier, S. Rodde: "Decommissioning of radioactive lightning rods in France", Autorité de sûreté nucléaire (ASN), March 2012. [4] http://www.jmv.co.in/lightning-protection/ese-lightning-arrester.html. [5] IS 3043.1987 Code of practice for earthing, page-43. JETIR1612017 Journal of Emerging Technologies and Innovative Research (JETIR) www.jetir.org 125