Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Similar documents
CDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION

Type VDG 13 Undervoltage Relay

Type CAEM 21 Battery Earth Fault Relay

Type VAEM 22 Negative Potential Biasing Relay

Instantaneous Overcurrent Relay

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

Type MCAG 14, 34 T&D. High Stability Circulating Current Relay

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

Protective Relays Digitrip 3000

Current and voltage measuring relays RXIK 1, RXEEB 1 and RXIB 24

MULTI FUNCTION OVER CURRENT AND EARTH FAULT RELAY[50/51X3,50/51N]

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

POWER SYSTEM II LAB MANUAL

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

DIAC Type 66K. DIGITAL OVERCURRENT RELAY Instruction Manual. GE Power Management

Stabilized Differential Relay SPAD 346. Product Guide

Overcurrent Protection / 7SJ45

3 Pole high impedance differential relay 7VH83

N. TEST TEST DESCRIPTION

BE1-32R, BE1-32 O/U DIRECTIONAL POWER RELAY

Enhanced Quality with a Touch of Style

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University

Phase and neutral overcurrent protection

Multimeter 500CVD21 RTU500 series

Power System Protection Manual

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

* Short-circuit detection at On pushbutton. Applications. Indication. S M6801_a S11 A3 S12 S21 S23 S22 S (+)

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Electrical Protection System Design and Operation

1 INTRODUCTION ORDER CODE / INFORMATION

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Transformer Fault Categories

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New)

General Requirements. Technical Specification LVAC Systems

N. TEST TEST DESCRIPTION

ASHIDA Numerical OC/EF Protection Relay

Series P. Applications

Protection and control VIP300. Technical manual

Reyrolle Protection Devices. 7PG18 - TR-A High speed tripping Relay. Energy Management.

3.0 CHARACTERISTICS. Type CKO Overcurrent Relay. switch, which allows the operation indicator target to drop.

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)


T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

PROTECTION of electricity distribution networks

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

DATA SHEET Differential current relays, RMC-131D ANSI code 87

Conventional Paper-II-2011 Part-1A

Overcurrent Protective Relays

SYNCHRONISING AND VOLTAGE SELECTION

Electronic Circuit Protector ESX10-T

Power systems Protection course

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

Modeion OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS

L O V A G. T E S T I N S T R U C T I O N I E C / E N E d C O N D I T I O N S F O R T E S T I N G

DATA SHEET Reverse power relays, RMP-121D ANSI code 32

SPAD 346 C Stabilized differential relay

Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16

www. ElectricalPartManuals. com Basler Electric P. 0. BOX 269 HIGHLAND, ILLINOIS 62249, U.S.A. PHONE FAX

Relay Types and Applications Dr. Sasidharan Sreedharan

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525.

7PG21 Solkor Rf Feeder Protection Energy Management

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11

GE Power Management. Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C

PD300. Transformer, generator and motor protection Data sheet

technical information

Type KLF Generator Field Protection-Loss of Field Relay

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID

MEDIUM-VOLTAGE MEASURING VOLTAGE TRANSFORMERS USER MANUAL

9 Overcurrent Protection for Phase and Earth Faults

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

Current / residual current and voltage transformers. Current / residual current and voltage transformers

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Earth Fault Relay EFSPL-1A/5A

POWER TRANSDUCERS ACTIVE AND REACTIVE SERIES: T-W WATT T-V VAR

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

DATA SHEET Selectable AC transducer TAS-311DG

Overcurrent and Overload Protection of AC Machines and Power Transformers

RING CORE CURRENT TRANSFORMERS FOR LOW VOLTAGE TYPE AOS USER MANUAL

RUDOLF Digital power analyzer. Advanced Version

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

3 - Protection components Circuit-breakers

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY

PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY

Positive-guided relay outputs: 8 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

Busbars and lines are important elements

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

EASUN REYROLLE LIMITED

DEIF A/S. Insulation monitor. Type SIM-Q

SECTION PANELBOARDS

Preface...x Chapter 1 Electrical Fundamentals

Transcription:

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Relay withdrawn from case Application The type CDG 11 relay is a heavily damped induction disc unit with an inverse definite minimum time/ current characteristic. The relay gives selective phase and earth fault overcurrent protection in time graded systems to transformers, ac machines and feeders, etc., and ensures that a minimum number of circuit breakers is tripped to clear a faulted section (see application publication R5087). Description The operating coil is wound to give time/current curves of the same shape on each of seven current taps which are selected by a plug setting bridge. The highest current tap is automatically selected when the plug is removed, so that adjustments can be made on load without opencircuiting the current transformer. The relay has a high torque movement to ensure consistent timing, even under adverse conditions, and a low burden and overshoot. Adjustment of the time setting is made by rotating a knurled moulded disc against a graduated time multiplier scale. To give instantaneous protection under short circuit conditions, a high set overcurrent unit (either CAG 13 or CAG 19) can be fitted in the same case. The CDG 21 relay is a CDG 11 with an instantaneous unit. The CDG 31 is a triple pole version of the CDG 11 (with three overcurrent units or two overcurrent units and one earth fault unit in the centre). The CDG 16 is a variant of the CDG 11 arrangement, incorporating two normally open electrically isolated contacts. Technical data Starting current 3-1% of current setting. Closing current 130% of current setting. Resetting current The maximum current up to which the disc will completely reset is 90% of current setting. Time settings 0-3s at times current setting. 0-1.3s at times current setting. Resetting time With the time multiplier set at 1.0 the resetting times of the above are 9s and 4s respectively. Overshoot On removal of a current equal to 20 times current setting the overshoot times of the above are 0.065s and 0.04s respectively. 2

Accuracy l The relay is calibrated at 50Hz or 60Hz and 20 C and falls into error class index E7.5 as given in BS142. Frequency error: Less than 8% for frequency variation of 2Hz; the time grading of a protective system would be unaffected by this error since all the relays would be similarly affected. Temperature error: For an overload equal to times the current setting, the percentage timing errors at +45 C and 5 C are respectively: 1.3 second relay 4% and +4%, 3.0 second relay 3% and +4% Auxiliary units and operation indicators Shunt reinforcing or series seal in auxiliary attracted armature units with a hand reset operation indicator, can be fitted. Relays supplied without an auxiliary unit have a hand reset operation indicator mechanically operated by the disc. Standard coil ratings Voltage operated (shunt) auxiliary units: 30, 1, 125 or 220V dc at a nominal burden of 3W continuously rated. Current settings Table 1 - Preferred increments Setting range (A) Table 2 - Standard increments Setting range (A) Current settings available 0.05-0.2 0.05 0.06 0.075 0. 0.12 0.15 0.2 0.1-0.4 0.1 0.12 0.15 0.2 0.24 0.3 0.4 0.2-0.8 0.2 0.24 0.3 0.4 0.48 0.6 0.8 0.25-1 0.25 0.3 0.375 0.5 0.6 0.75 1.0 0.5-2 0.5 0.6 0.75 1.0 1.2 1.5 2.0 1-4 1.0 1.2 1.5 2.0 2.4 3.0 4.0 1.5-6 1.5 1.8 2.25 3.0 3.6 4.5 6.0 2.5-2.5 3.0 3.75 5.0 6.0 7.5.0 4-16 4.0 4.8 5.0 8.0 9.6 12.0 16.0 Current settings available 0.05-0.2 0.05 0.075 0.1 0.125 0.15 0.175 0.2 0.1-0.4 0.1 0.15 0.2 0.25 0.30 0.35 0.4 0.2-0.8 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.25-1 0.25 0.375 0.5 0.625 0.75 0.875 1.0 0.5-2 0.5 0.75 1.0 1.25 1.5 1.75 2.0 1-4 1.0 1.5 2.0 2.5 3.0 3.5 4.0 2.5-2.5 3.75 5.0 6.25 7.5 8.75.0 Contacts One or two electrically separate normally-open self or hand reset contacts are fitted which will make and carry 7500VA for 0.5s with maxima of 30A and 660V ac or dc. Relays supplied without an auxiliary unit have one or two pairs of normally-open self reset contacts which will make and carry 2500VA for 0.5s with maxima of A and 660V ac or dc. The two contact relay has a modified disc/contact assembly and is designated CDG 16, CDG 26 or CDG 36. Thermal rating Continuous current rating Tap 1 2 3 4 5 6 7 Multiples of tap setting current 4.5 3.7 3.2 2.7 2.6 2.4 2.2 Short time current rating Current operated (series) auxiliary units The relay will withstand 20 x the maximum tap setting for 3s. Minimum operating 0.5 second Coil resistance current in A (two taps) current rating in A in ohms 0.1 and 0.3 18 and 22 9.2 and 2.1 0.2 and 2.0 22 and 92 6.0 and 0.125 0.6 and 2.4 92 and 188 0.29 and 0.031 Other coil ratings can be supplied for both types of auxiliary unit. 3

Burdens Standard (3VA nominal) - Alternative with lower operating 2.5VA at current setting torque (CDG 11, 21 & 31 only) on lowest tap (1VA nominal) - 3.5VA at current setting 1VA at current setting on lowest tap on highest tap 1.9VA at current setting on highest tap Typical burden CDG 11 1VA 50Hz 2.5 - A For 60Hz relays increase burden by 20% Table 3 VA burden Multiples of plug setting Tap setting value 1.0 3.0.0 20.0 2.5 1.0 5.5 34 130 3.75 1.1 6.8 44 168 5.0 1.1 7.8 60 220 6.25 1.4 9.8 78 297 7.5 1.5 11.0 92 360 8.75 1.7 12.7 7 413.0 1.9 14.4 120 460 Typical burden CDG 11 3VA 50Hz 2.5 - A For 60Hz relays increase burden by 20% Table 4 VA burden Multiples of plug setting Tap setting value 1.0 3.0.0 20.0 2.5 2.5 15 97 312 3.75 2.7 15 119 422 5.0 2.9 17 131 500 6.25 2.9 19 164 625 7.5 3.1 20 174 675 8.75 3.1 23 206 827.0 3.4 24 250 1,000 Table 5 Setting range (A) - Standard increments 0.05-0.2 0.1-0.4 0.2-0.8 0.25-1 0.5-2 1-4 2.5- K (50Hz) 2,500 625 156 0 25 6.3 1.0 K (60Hz) 2,750 687 171 1 28 6.8 1.1 Table 6 Setting range (A) - Preferred increments 0.05-0.2 0.1-0.4 0.2-0.8 0.25-1 0.5-2 1-4 1.5-6 2.5-4-16 K (50Hz) 2,500 625 156 0 25 6.3 2.8 1.0 0.39 Impedance characteristics The impedance of a relay may be calculated by using Table 5 or Table 6 in conjunction with the relevant impedance current curve, see Figure 3 or 4. Example: To calculate the impedance, at times setting, of a 3VA rated CDG 11 relay, setting range 1-4A 50Hz with preferred taps, and set to 2A, i.e. 50%: Refer to curves, Figure 4, i.e. for 3VA, and select the 50% curve from which the value at times setting is 0.052. Referring now to Table 6, for preferred taps 1-4A range, select the multiplying factor K for 50Hz, which gives: 6.3 x 0.052 = 0.325 ohms. AC trip circuit Where an external tripping supply is not available, a relay can be supplied which trips the circuit breaker directly using current from the line current transformer. Under fault conditions, the tertiary winding on the relay current coil develops an ac voltage. This is rectified to energise the auxiliary tripping relay, causing current to flow through the trip coil of the circuit breaker. See Figure 5. The contacts are rated for series trip coil currents up to 150A at 150V. Earthing arrangements Although not included in the diagram, it is assumed that secondary CT and/ or VT circuits will be earthed as necessary in compliance with standard safety requirements and determined by the switchgear contractor user. If in doubt, please consult ALSTOM T & D Protection & Control for advice. Insulation The relay will withstand 2.0 kv rms 50Hz for 1 minute between all live parts and earth and between all circuits not intended to be connected together. It will also withstand 1 kv rms 50Hz for 1 minute across open contacts. K (60Hz) 2,750 687 171 1 28 6.8 3.1 1.1 0.45 4

Technical data for CAG 13 Current rating 1A or 5A. Settings } 500 2000% 400 1600% 200 800% 0 400% Resetting current The relay will reset at approximately 15% of current setting. Operating time Approximately milli seconds at 5 times current setting. Burdens 1.4 VA at lowest current setting to 18 VA at highest current setting. VA burdens given above are applicable to all setting ranges. Thermal rating The relay will withstand 1.5 times the minimum current setting continuously and 12 times the maximum current setting for 3 seconds. Accuracy The relay conforms to error class index E.0 as per B.S.142:1966. Operation indicator The relay is fitted with an operation indicator which is hand reset by means of a push-rod protruding through the relay case. Contacts 2 make self reset. at rated current continuously adjustable Technical data for CAG 19 Current rating 1A or 5A. Settings 500-2000% } 400-1600% 200-800% 0-400% Resetting current Not less than 80% of current setting. Operating time Less than 30 milli seconds at 5 times setting current. Resetting time Within 30 milli seconds when resetting to no current. Transient overreach Less than 1% for system angles upto 88 on all settings. Burden } 1.0 VA on lowest setting 3.0 VA on highest setting Thermal rating Continuous : Maximum setting current Short time : 20 x max. setting current for 3 seconds Accuracy Error class index Contacts 2 make self reset. at rated current continuously adjustable at setting current : E 5 as per BS.142:1966 5

0 0 Operating time (seconds) 1 0.1 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 Time Multiplier settings Operating time (seconds) 11 0.1 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 Time Multiplier settings Instantaneous unit (CAG 19) Instantaneous unit (CAG 19) 0.01 Instantaneous unit (CAG 13) 0.01 Instantaneous unit (CAG 13) 0.001 1 0 Multiples of setting current Figure 1: Time-current characteristic, inverse time relay CDG 11, 1.3s 0.001 1 0 Multiples of setting current Figure 2: Time-current characteristic, inverse time relay CDG 11, 3s Figure 3: CDG 11 impedance characteristic 1VA 50Hz. Figure 4: CDG 11 impedance characteristic 3VA 50Hz. 6

v See note A o W 1 2 3 4 3 + 1 2 BK 5 MZGO6... 1 2 5 6 BE 6 Trip coil Terminals viewed from front 8 9 Figure 5: Connection diagram for ac series tripping, hand-reset See note A Note: Coil leads are supplied with units. A leads are to be 1/1. 1mm tinned copper flex with a 0.5mm thk. Wall insulation block. All other leads to be 13/0.2mm tinned copper wire with a 0.5mm thk. wall insulation block. A leads are to be covered with extra sleeving TPV3404 001 A B C Alarm 1 Note: All three elements are the same and only one is shown. Alarm and trip Ckt are paralleled. A B C CT connection for overcurrent and earth fault protection 2 C Trip Ckt. 3 4 5 Three phase overcurrent protection 6 A Trip Ckt. Isolator 7 B 8 9 C 5 6 7 8 9 O/C E/F O/C CT shorting contacts Figure 6: Typical application and internal circuit diagram of Type CDG 31 relay with series seal in A B 1 2 3 4 5 6 When fitted 1 2 4 3 8 9 CAG 3 7 CDG 4 8 9 Violet Orange Brown Grey V O B N GY BK BE Y PK 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 + + Figure 7: Connection diagram for CDG 11 relay. Figure 8: Connection diagram for CDG 26 relay. 7

Dimensions and weights Maximum overall dimensions Relay Case Height Width Depth* mm mm mm CDG 11 CDG 21 1D 237 173 218 CDG 21 2D (vert) 425 174 218 (double pole) CDG 31 3D (vert) 527 174 218 3D (horiz) 238 458 218 * Add 7 mm. for maximum length of M5 terminal screws. Cases Relays are supplied in drawout cases designed for either flush or projection mounting. Case wrappers are manufactured from hot dipped galvanised steel with a black pvc outer coating/powder coating. Relays comply with 56 day humidity requirements as specified in IEC 68, climatic category 20/50/56. Dimensioned drawings of case outlines, panel cut-outs and mounting details are available on request. Information required with order 1. Relay type 2. Current setting range 3. Preferred or standard increments 4. Current transformer secondary rating 5. Characteristic (time setting at times I S ) 6. Burden (1VA or 3VA) 7. Trip circuit (series seal in, shunt reinforcing or ac) 8. Trip circuit current (series seal in) 9. Trip circuit voltage (shunt reinforcing). Operation indicator inscription if required 11. Auxiliary contacts (hand or self reset) 12. Details of instantaneous unit (CAG) if required 13. Case mounting 8

9

ALSTOM Limited Pallavaram Works: 19/1, GST Road, Pallavaram, Chennai-600 043. India. Tel: 91-044-2368621 Fax: 91-044-2367276 Email: plw.applications@alstom.sprintrpg.eml.vsnl.net.in. 1998 ALSTOM Limited Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it. ALSTOM Limited cannot be held responsible for any reliance on any decision taken on its contents without specific advice. PR:015:0799:A Printed in India.