Understanding Power Quality

Similar documents
22.0 Harmonics in Industrial Power Systems

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Understanding Harmonics

ABB n.v. Power Quality Products, October 2014

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Power Quality implications of new residential appliances. EEA Conference & Exhibition 2010, June 2010, Christchurch

UNDERSTANDING POWER QUALITY

Reducing Total Harmonic Distortion with Variable Frequency Drives

Technical Paper. Harmonic Distortion in Data Centers

AC Sources for IEC 1000 Harmonics and Flicker Testing

CHAPTER 4 HARMONICS AND POWER FACTOR

What does Power Factor mean?

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

Power Factor and Power Factor Correction

Active Harmonic Filter (AF3)

Power Quality Monitoring and Power Metering Tutorial

Analysis of Harmonic Distortion in Non-linear Loads

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

ECET Modern Power

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

Compensation of Reactive Power Case Study

Introduction to Harmonics and Power Quality

An Introduction to Power Quality

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

Application Guidance Notes: Technical Information from Cummins Generator Technologies

Generator Advanced Concepts

Increasing the Performance of PFC and LED Driver Applications

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

Production power on a budget: How to generate clean reliable power, Part 2 By Guy Holt

Fundamentals of Power Quality

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Intermediate Frequency Electric and Magnetic Emissions Testing

1C.4.1 Harmonic Distortion

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

Increasing the Performance of PFC and LED Driver Applications

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

NJWA - Harmonics and Drives Proper System Design

CHAPTER 5 SWITCH MODE POWER SUPPLIES

P2 Power Solutions Pvt. Ltd.

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

Harmonics I Harmonics White Paper. Power Protection Products, Inc. by Dan Maxcy l 2018 Update

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Reduction Of Harmonics By Using Active Harmonic Filter

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

Effects of Total Harmonic Distortion on Power System Equipment

Conceptual Physics. Chapter 23: ELECTRIC CURRENT

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

Power. Power is the rate of using energy in joules per second 1 joule per second Is 1 Watt

ET 40 - Electrician Theory Examination Marking Schedule

DESIGN AND ANALYSIS OF ELIMINATION OF HARMONICS USING WIND ENERGY CONVERSION SYSTEMS

Production power on a budget: How to generate clean reliable power, Part 1 By Guy Holt

2.0 AC CIRCUITS 2.1 AC VOLTAGE AND CURRENT CALCULATIONS. ECE 4501 Power Systems Laboratory Manual Rev OBJECTIVE

A primer for non-electrical engineers Harmonic Distortion in Electrical Systems

A Guide to Power Quality Testing

Outcomes of Harmonics & Its Reduction Techniques: A Comprehensive Review

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

Power Quality in modern lighting: comparison of LED, microled and CFL lamps

PF Correction Techniques in highly varying load

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

BENCHMARK LIGHTING: COST SAVING TECHNOLOGIES

Active Harmonic Filter (AHF)

Tuningintobetter power quality

Evaluation and Updating of Harmonic Voltage Limits

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Harmonic Design Considerations for Wind Farms

APPLICATION GUIDE. Harmonics in HVAC applications

AC Power Instructor Notes

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

TOPOLOGICAL ISSUES IN SINGLE PHASE POWER FACTOR CORRECTION

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

Power Quality Solutions

Guidelines to the standard EN

Correct cap type? e.g. Bayonet Edison Screw GU 10 MR 16. Suitable colour temperature? Warm (3000 K) Cool (4000 K) Bright White (5000+ K)

Study of Power Factor Correction in Single Phase AC-DC Converter

Harmonic control devices. ECE 528 Understanding Power Quality

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

Motors and drives. Module B- Introduction to input measurements

Voltage and Current Waveforms Enhancement using Harmonic Filters

Introduction to Rectifiers and their Performance Parameters

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

Harmonics study of common low wattage LED lamps

Reliable power onboard and offshore

ELG 4125: ELECTRICAL POWER TRANSMISSION AND DISTRIBUTION: TUTORIAL 1: - BY:

Improving the Power Factor of Isolated Flyback Converters for Residential ENERGY STAR LED Luminaire Power Supplies

ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF RESIDENTIAL LOAD

Fundamentals of AC Power Measurements

POWER FACTOR CORRECTION AND ITS PITFALLS

Chapter L Power factor correction and harmonic filtering

Thyristorised Automatic Power Factor

+ 24V 3.3K - 1.5M. figure 01

DESIGN OPTIMIZATION TECHNIQUES FOR IMPROVED POWER FACTOR AND ENERGY EFFICIENCY FOR INDUSTRIAL PROCESSES. Darren R. Rabosky

INTERNATIONAL JOURNAL OF ENHANCED RESEARCH IN SCIENCE TECHNOLOGY & ENGINEERING VOL. 2 ISSUE 2, FEB ISSN NO:

Emicon Engineering Consultants L.L.C.

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

Harmonic Analysis to Improve Power Quality

PowerMonitor 5000 Family Advanced Metering Functionality

Harmonic control devices

Transcription:

Understanding Power Quality Produced by Dr Bruce Girdwood For Energy Mad Ltd Version 1: 23 October 2007

The electronics revolution and the growing number of utility programmes promoting compact fluorescent lamps are making power quality an issue for the residential sector. There is a growing desire to reduce electrical loading by increasing the efficiency of the use of electrical energy. The use of energy efficient lighting is a rich source of cost effective energy savings. There is a high level of interest in replacing conventional incandescent lamps with Compact Fluorescent Lamps (CFL). What is power quality? Most new electronic equipment, while more efficient than their mechanical predecessors, consume electricity differently to traditional mechanical appliances. While older devices, like incandescent bulbs, use power as supplied by the utility, electronic devices draw currents in bursts, altering the electricity that flows through them, so that what comes out the other side and returns to the grid is distorted. This dirty power under-utilises utility equipment and increases line losses. Utilities must invest in costly filters and capacitors to clean this dirty power. Poor power quality causes transformers, cables and other transmission equipment to burn out more quickly, thus increasing utility equipment costs. For a specific electric device power quality describes the extent to which the device: 1. Distorts the voltage waveform; and 2. Changes the phase relationship between the voltage and the current. 1. Waveform distortion How is a voltage waveform distorted by CFLs? CFLs, with electronic ballasts, distort the current waveform by creating harmonics, introduced when the CFL draws current in short bursts (instead of drawing it smoothly as is the case for an incandescent lamp). Each harmonic waveform has a frequency which is an integer multiple of the original, or fundamental, waveform. High frequency harmonics can affect frequency sensitive equipment if these harmonics are of similar frequency to the line-carrier signal that operates such equipment. For example, the relays which manage the supply of electricity to hot water cylinders during times of system peak. The distorted current waveform distorts the voltage waveform. A constant voltage is important for the safe and efficient operation of equipment on an electricity system. 1

Harmonics are a distortion of the utility supplied waveform and are caused by non-linear (distorting) loads, which include motor controls, computers, office equipment, CFLs, light dimmers, televisions and, in general, most electronic loads. High harmonics increase lines losses and decrease equipment lifetime. Harmonic distortion is the difference between the shape of the current wave drawn by the device, and the shape of the voltage wave supplied to that device. Total harmonic distortion (THD) measures the degree to which the input is distorted, and is the relative value of all the harmonics combined, as a percentage of the fundamental current. Utilities typically supply voltage with less than 2% THD. However, the current THD for electronic devices may be over 100%. What consequences arise from harmonics? Problems caused by harmonic currents include: Introduce neutral currents above 100% of the phase current, resulting in overheating and failure of the neutral phase. Case studies in commercial buildings have shown neutral currents of between 150% and 210% of the phase currents in the presence of high 3 rd harmonic currents. Transformers can overheat resulting in reduced life and reduced rating (losses increase with the square of the harmonic number). Nuisance tripping of residual current circuit breakers. Over stressing of power factor correction capacitors. Problems caused by harmonic voltages include: Increased losses in motors resulting in reduced power output and increased heating (reduceing life expectancy) Problems caused by harmonic frequencies Devices that use power-line carrier signals, such as synchronised clocks, control modules for building management systems and ripple control relays for management of hot water load may experience problems if harmonics exist at frequencies close to the carrier signal. These harmonics cannot be filtered out as the filtering will also filter out the power-line carrier signals. 2

2. Phase relationship between the voltage and the current When phase displacements occur there are periods in the cycle when the current is positive and the voltage is negative (or vice versa) as illustrated by the shaded area in the figure below. During these periods the device creates reactive power and does not produce any useful work (active power). Figure 2 Phase displacement and reactive power Reactive power arises when there are phase differences between the voltage and the current waveforms and has the units of VA. Reactive power creates no useful work but must be generated and uses up the capacity of the network. Reactive power does not distort the voltage but it is an important power quality concern because the electricity system must have the capacity to produce and carry reactive power even though it accomplishes no useful work. Active power is the measure of useful work done by a device and has the unit of Watt (W). Power factor is the measure of how effectively a device converts input current and voltage into active, or useful, power. It describes the combined effect of THD and reactive power (caused by phase displacement). A device with a power factor of 1 has 0% THD and a current draw that is synchronised with the voltage. These devices convert all the input current and voltage into useful work. Resistive loads such as incandescent lamps have power factors of 1. 3

Power factors can be less than or equal to 1. The lower the power factor the less efficient the device is in converting input power into useful power. These devices create more reactive power that uses up system capacity for no useful purpose. Electronic devices such as televisions, CFLs and computers have low power factors unless corrected. For example, a load with a power factor of 0.5 will require twice as much current as a load with a power factor of 1.0 for the same amount of useful power. A low power factor is a power drain that decreases system efficiency. Leading and lagging power factor. When the current leads the voltage the power factor is said to be leading. When the current lags the voltage the power factor is said to be lagging. Resistive loads, such as incandescent lamps and resistive heaters, have power factor of unity. Inductive loads, such as electric motors, have lagging power factors less than 1. Capacitive loads, such as CFLs with electronic ballast, have leading power factors less than 1. 3. What can be done to correct power factor and minimise harmonics? To understand the effect of power factor and harmonics the nature of the whole load needs to be considered. In a perfect world the reactive power created by devices with leading power factor would balance the reactive power created by devices with lagging power factor. Unfortunately this is rarely the case so regulators require distribution networks to maintain power factors at levels >0.95 and have no more than 5% voltage distortion at the service entrance. In the past the harmonics injected into networks by CFLs have been ignored as each 20 Watt CFL makes a small contribution. International standards assume that the greatest contribution to harmonic distortion comes from lighting units that consume more than 25W of power. Most residential CFLs are not affected by these standards. Given the increasing use of devices that have poor power quality characteristics, regulators will act to ensure devices are designed to standards, which, economically, minimise power quality concerns. To this end, responsible manufacturers will act sooner, rather than later, to produce quality devices. CFLs are not the only devices that create harmonics or have low power factor, however, with the widespread adoption of CFLs, the combined effect of these small sources can be as detrimental as one large source and is harder to mitigate because CFLs are distributed across the network rather than in one location, as for example a manufacturing plant. 4

Distribution networks seek to align financial consequences with good behaviour, for example, a large manufacturing plant can manage its power factor and harmonics and will therefore face a penalty if its load fails to comply with the standards set by its electricity supplier. Due to the distributed nature of household electronics, including CFLs, it is harder for distribution networks to expect individual householders to manage power factor and harmonics in the same way as large energy users. Rather, utilities provide good power quality as part of their service. This can be achieved through a combination of measures, including: requiring large energy users to clean their own dirty power, regulating the power quality characteristics of devices and by correcting for power factor and harmonics in the network itself. Power factor can be corrected by installing capacitors in the electricity system and harmonics can be filtered out. No matter how well large electricity users perform there will always be the need for some power factor correction and harmonic filtering within the electricity system but this should be kept to a minimum as there are significant complications associated with this practice, particularly when harmonics are high. Studies estimate that it is about 10 times cheaper to manufacture high power factor (0.9), low harmonic CFLs than it is for utilities to correct power factor and filter harmonics caused by CFLs with power factors in the range 0.5-0.6. 5